Strip Footing Design Page 1 of 16

COMBINED FOUNDATION DESIGN(IS 456-2000)


Design For Combined Footing 1

Design For Combined Footing 2

Result Summary

Left Overhang Right Overhang Length Width Thickness


Footing No.
(m) (m) (m) (m) (m)
1 1.000 1.000 8.000 2.000 0.550
2 1.000 1.000 8.000 2.000 0.550

Footing No. Footing Reinforcement


- Main Steel Top Main Steel Bottom Secondary Steel Top Secondary Steel Bottom
1 Ø12 @ 170 mm c/c Ø12 @ 155 mm c/c Ø12 @ 170 mm c/c Ø12 @ 170 mm c/c
2 Ø12 @ 170 mm c/c Ø12 @ 155 mm c/c Ø12 @ 170 mm c/c Ø12 @ 170 mm c/c

Combined Footing 1
Input Data

Geometry of Footing
For Column 2

Column Dimensions

Column Shape : Rectangular

file:///C:/Staad.foundation%205.3/CalcXsl/Combined.xml 4/5/2021
Strip Footing Design Page 2 of 16

Column Length - X (Pl) : 0.300 m


Column Width - Z (Pw) : 0.300 m

Pedestal

Include Pedestal? No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
Pedestal Length - X (Pl) : N/A
Pedestal Width - Z (Pw) : N/A

For Column 8

Column Dimensions

Column Shape : Rectangular


Column Length - X (Pl) : 0.300 m
Column Width - Z (Pw) : 0.300 m

Pedestal

Include Pedestal? No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
Pedestal Length - X (Pl) : N/A
Pedestal Width - Z (Pw) : N/A

For Column 14

Column Dimensions

Column Shape : Rectangular


Column Length - X (Pl) : 0.300 m
Column Width - Z (Pw) : 0.300 m

Pedestal

Include Pedestal? No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
Pedestal Length - X (Pl) : N/A
Pedestal Width - Z (Pw) : N/A

Length of left overhang : 1.000 m


Length of right overhang : 1.000 m
Is the length of left overhang fixed? No
Is the length of right overhang fixed? No
Minimum width of footing (Wo) : 2.000 m
Minimum Thickness of footing (Do) : 300.000 mm
Maximum Width of Footing (Wo) : 40000.000 mm
Maximum Thickness of Footing (Do) : 550.000 mm
Maximum Length of Footing (Lo) : 40000.000 mm
Length Increment : 50.000 mm
Depth Increment : 50.000 mm

file:///C:/Staad.foundation%205.3/CalcXsl/Combined.xml 4/5/2021
Strip Footing Design Page 3 of 16

Cover and Soil Properties

Pedestal Clear Cover : 50.000 mm


Footing Clear Cover : 50.000 mm
Unit Weight of soil : 22.000 kN/m3
Soil Bearing Capacity : 125.000 kN/m2
Soil Surcharge : 0.000 kip/in2
Depth of Soil above Footing : 0.000 in
Depth of Water Table : 5.000 m

Concrete and Rebar Properties

Unit Weight of Concrete : 25.000 kN/m3


Compressive Strength of Concrete : 25.000 N/mm2
Yield Strength of Steel : 415.000 N/mm2
Minimum Bar Size : Ø12
Maximum Bar Size : Ø60
Minimum Bar Spacing : 50.000 mm
Maximum Bar Spacing : 400.000 mm

------------------------------------------------------

Design Calculations

Footing Size Calculations

Reduction of force due to buoyancy = 0.000 kN

Area from initial length and width, Ao = Lo X Wo = 16.000 sq m

Min. area required from bearing pressure, Amin = P / qmax = 9.844 sq m

Note: Amin is an initial estimation.


P = Critical Factored Axial Load(without self weight/buoyancy/soil).
qmax = Respective Factored Bearing Capacity.

Final footing dimensions are:

Length of footing, L : 8.000 m


Width of footing, W : 2.000 m
Depth of footing, Do : 0.550 m
Area, A : 16.000 sq m
Length of left overhang, Lleft_overhang : 1.000 m

Length of right overhang, Lright_overhang : 1.000 m

------------------------------------------------------

Load Combination/s- Service Stress Level


Load Combination

file:///C:/Staad.foundation%205.3/CalcXsl/Combined.xml 4/5/2021
Strip Footing Design Page 4 of 16

Number Load Combination Title


101 1.000 x DL+1.000 x DL+1.000 x DL
102 0.800 x DL+0.800 x DL+0.800 x DL
Load Combination/s- Strength Level
Load Combination
Load Combination Title
Number
201 1.500 x DL+1.500 x DL+1.500 x DL
202 0.960 x DL+0.960 x DL+0.960 x DL
203 1.200 x DL+1.200 x DL+1.200 x DL
204 0.900 x DL+0.900 x DL+0.900 x DL

Applied Loads - Service Stress Level


Axial Shear X Shear Z Moment X Moment Z
LC
(kN) (kN) (kN) (kNm) (kNm)
-
Column Number : 2
101 279.583 -14.566 0.097 0.328 13.972
102 223.667 -11.653 0.077 0.263 11.177
-
Column Number : 8
101 481.379 -0.483 0.213 0.458 -15.344
102 385.104 -0.387 0.170 0.366 -12.275
-
Column Number : 14
101 349.530 -14.723 -0.309 -0.022 14.160
102 279.624 -11.779 -0.247 -0.017 11.328

Applied Loads - Strength Level


Axial Shear X Shear Z Moment X Moment Z
LC
(kN) (kN) (kN) (kNm) (kNm)
-
Column Number : 2
201 419.375 -21.849 0.145 0.492 20.957
202 268.400 -13.984 0.093 0.315 13.413
203 335.500 -17.480 0.116 0.394 16.766
204 251.625 -13.110 0.087 0.295 12.574
-
Column Number : 8
201 722.069 -0.725 0.319 0.687 -23.016
202 462.124 -0.464 0.204 0.439 -14.730
203 577.655 -0.580 0.255 0.549 -18.413
204 433.241 -0.435 0.191 0.412 -13.810
-
Column Number : 14
201 524.295 -22.085 -0.464 -0.032 21.240
202 335.549 -14.134 -0.297 -0.021 13.594
203 419.436 -17.668 -0.371 -0.026 16.992
204 314.577 -13.251 -0.278 -0.019 12.744

Calculated Pressures at Four Corners

file:///C:/Staad.foundation%205.3/CalcXsl/Combined.xml 4/5/2021
Strip Footing Design Page 5 of 16

Pressure at Pressure at Pressure at Pressure at Area of footing in


Load Case corner 1 (q1) corner 2 (q2) corner 3 (q3) corner 4 (q4) uplift (Au)
(kN/m^2) (kN/m^2) (kN/m^2) (kN/m^2) (sq. m)

101 74.3152 71.3514 79.4963 82.4602 0.000

101 74.3152 71.3514 79.4963 82.4602 0.000

101 74.3152 71.3514 79.4963 82.4602 0.000

101 74.3152 71.3514 79.4963 82.4602 0.000

If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of
negative pressure will be set to zero and the pressure will be redistributed to remaining corners.

Summary of Adjusted Pressures at Four Corners

Pressure at Pressure at Pressure at Pressure at


Load Case corner 1 (q1) corner 2 (q2) corner 3 (q3) corner 4 (q4)
(kN/m^2) (kN/m^2) (kN/m^2) (kN/m^2)

101 74.3152 71.3514 79.4963 82.4602

101 74.3152 71.3514 79.4963 82.4602

101 74.3152 71.3514 79.4963 82.4602

101 74.3152 71.3514 79.4963 82.4602

------------------------------------------------------

Check for stability against overturning


Resisting Resisting
Moment X Moment Z
Load Case Moment X Moment Z Ratio X Ratio Z
(kNm) (kNm)
(kNm) (kNm)

101 21.719 31.613 1230.470 4921.880 56.653 155.690

102 17.376 25.291 1008.376 4033.502 58.034 159.486

------------------------------------------------------

Design for Flexure

Sagging moment along length

Critical load case : 201


Effective Depth = = 0.494 m
Governing moment (Mu) = 237.792 kNm

As Per IS 456 2000 ANNEX G G-1.1C

Limiting Factor1 (Kumax) = = 0.479107

Limiting Factor2 (Rumax) = = 3444.291146 kN/m^2

Limit Moment Of Resistance (Mumax) = = 1681.031322 kNm

Mu <= Mumax hence, safe

Hogging moment along length

file:///C:/Staad.foundation%205.3/CalcXsl/Combined.xml 4/5/2021
Strip Footing Design Page 6 of 16

Critical load case : 201


Effective Depth = = 0.494 m
Governing moment (Mu) = 146.776 kNm

As Per IS 456 2000 ANNEX G G-1.1C

Limiting Factor1 (Kumax) = = 0.479107

Limiting Factor2 (Rumax) = = 3444.291146 kN/m^2

Limit Moment Of Resistance (Mumax) = = 1681.031322 kNm

Mu <= Mumax hence, safe

Transverse direction

Critical load case : 201


Effective Depth = = 0.494 m
Governing moment (Mu) = = 305.686 kNm

As Per IS 456 2000 ANNEX G G-1.1C

Limiting Factor1 (Kumax) = = 0.479107

Limiting Factor2 (Rumax) = = 3444.291146 kN/m^2

Limit Moment Of Resistance (Mumax) = = 6724.125449 kNm

Mu <= Mumax hence, safe

Check trial depth for one way shear(along length)

Critical load case for maximum shear force along 201


the length of footing :
Shear Force(S) = 269.711 kN
Shear Stress(Tv) = 272.987160 kN/m^2

Percentage Of Steel(Pt) = 0.1381

As Per IS 456 2000 Clause 40 Table 19


Shear Strength Of Concrete(Tc) = 280.335 kN/m^2

Tv< Tc hence, safe

Check trial depth for two way shear

Critical Load case for Punching Shear Check : 201


For Column 1
Shear Force(S) = 352.690 kN
Shear Stress(Tv) = 224.794 kN/m^2

file:///C:/Staad.foundation%205.3/CalcXsl/Combined.xml 4/5/2021
Strip Footing Design Page 7 of 16

As Per IS 456 2000 Clause 31.6.3.1


Ks = = 1.000

Shear Strength(Tc)= = 1250.0000 kN/m^2

Ks X Tc = 1250.0000 kN/m^2

Tv<= Ks X Tc hence, safe

Critical Load case for Punching Shear Check : 201


For Column 2
Shear Force(S) = 656.260 kN
Shear Stress(Tv) = 418.281 kN/m^2

As Per IS 456 2000 Clause 31.6.3.1


Ks = = 1.000

Shear Strength(Tc)= = 1250.0000 kN/m^2

Ks X Tc = 1250.0000 kN/m^2

Tv<= Ks X Tc hence, safe

Critical Load case for Punching Shear Check : 201


For Column 3
Shear Force(S) = 459.712 kN
Shear Stress(Tv) = 293.007 kN/m^2

As Per IS 456 2000 Clause 31.6.3.1


Ks = = 1.000

Shear Strength(Tc)= = 1250.0000 kN/m^2

Ks X Tc = 1250.0000 kN/m^2

Tv<= Ks X Tc hence, safe

Selection of reinforcement

Top reinforcement along length

As Per IS 456 2000 Clause 26.5.2.1


Minimum Area of Steel (Astmin) = 1320.000 mm2

Calculated Area of Steel (Ast) = 834.647 mm2

Provided Area of Steel (Ast,Provided) = 1320.000 mm2

Astmin<= Ast,Provided Steel area is accepted

Selected bar Size (db) = Ø12

Minimum spacing allowed (Smin) = 50.000 mm

Selected spacing (S) = 171.636 mm


Smin <= S <= Smax and selected bar size < selected maximum bar size... The reinforcement is
accepted.

Along width

As Per IS 456 2000 Clause 26.5.2.1


Provided Minimum Area of Steel (Astmin) = 5280.000 mm2

file:///C:/Staad.foundation%205.3/CalcXsl/Combined.xml 4/5/2021
Strip Footing Design Page 8 of 16

Selected bar Size (db) = Ø12

Minimum spacing allowed (Smin) = 50.000 mm

Selected spacing (S) = 171.478 mm


Smin <= S <= Smax and selected bar size < selected maximum bar size... The reinforcement is
accepted.

Bottom reinforcement along length

As Per IS 456 2000 Clause 26.5.2.1


Minimum Area of Steel (Astmin) = 1320.000 mm2

Calculated Area of Steel (Ast) = 1364.531 mm2

Provided Area of Steel (Ast,Provided) = 1364.531 mm2

Astmin<= Ast,Provided Steel area is accepted

Selected bar Size (db) = Ø12

Minimum spacing allowed (Smin) = = 50.000 mm

Selected spacing (S) = 157.333 mm


Smin <= S <= Smax and selected bar size < selected maximum bar size... The reinforcement is
accepted.

Along width

As Per IS 456 2000 Clause 26.5.2.1


Minimum Area of Steel (Astmin) = 5280.000 mm2

Calculated Area of Steel (Ast) = 1726.437 mm2

Provided Area of Steel (Ast,Provided) = 5280.000 mm2

Astmin<= Ast,Provided Steel area is accepted

Selected bar Size (db) = Ø12

Minimum spacing allowed (Smin) = = 50.000 mm

Selected spacing (S) = 171.478 mm


Smin <= S <= Smax and selected bar size < selected maximum bar size... The reinforcement is
accepted.

Provided Reinforcement

Main bar no. for top Reinforcement: Ø12


Spacing of top reinforcement bar : 171.636 mm

Based on spacing reinforcement increment; provided reinforcement is

Ø12 @ 170 mm o.c.

Main bar no. for bottom Reinforcement: Ø12


Spacing of bottom reinforcement bar : 157.333 mm

Based on spacing reinforcement increment; provided reinforcement is

file:///C:/Staad.foundation%205.3/CalcXsl/Combined.xml 4/5/2021
Strip Footing Design Page 9 of 16

Ø12 @ 155 mm o.c.

Distribution bar no.: Ø12


Spacing of distribution bars : 171.478 mm

Based on spacing reinforcement increment; provided reinforcement is

Ø12 @ 170 mm o.c.

Distribution bar no.(Top): Ø12


Spacing of distribution bars(Top) : 171.478 mm

Based on spacing reinforcement increment; provided reinforcement is

Ø12 @ 170 mm o.c.

Combined Footing 2
Input Data

Geometry of Footing
For Column 1

Column Dimensions

Column Shape : Rectangular


Column Length - X (Pl) : 0.300 m
Column Width - Z (Pw) : 0.300 m

Pedestal

Include Pedestal? No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
Pedestal Length - X (Pl) : N/A
Pedestal Width - Z (Pw) : N/A

For Column 7

Column Dimensions

Column Shape : Rectangular


Column Length - X (Pl) : 0.300 m
Column Width - Z (Pw) : 0.300 m

Pedestal

Include Pedestal? No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
Pedestal Length - X (Pl) : N/A
Pedestal Width - Z (Pw) : N/A

For Column 13

Column Dimensions

Column Shape : Rectangular


Column Length - X (Pl) : 0.300 m
Column Width - Z (Pw) : 0.300 m

file:///C:/Staad.foundation%205.3/CalcXsl/Combined.xml 4/5/2021
Strip Footing Design Page 10 of 16

Pedestal

Include Pedestal? No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
Pedestal Length - X (Pl) : N/A
Pedestal Width - Z (Pw) : N/A

Length of left overhang : 1.000 m


Length of right overhang : 1.000 m
Is the length of left overhang fixed? No
Is the length of right overhang fixed? No
Minimum width of footing (Wo) : 2.000 m
Minimum Thickness of footing (Do) : 300.000 mm
Maximum Width of Footing (Wo) : 40000.000 mm
Maximum Thickness of Footing (Do) : 550.000 mm
Maximum Length of Footing (Lo) : 40000.000 mm
Length Increment : 50.000 mm
Depth Increment : 50.000 mm

Cover and Soil Properties

Pedestal Clear Cover : 50.000 mm


Footing Clear Cover : 50.000 mm
Unit Weight of soil : 22.000 kN/m3
Soil Bearing Capacity : 125.000 kN/m2
Soil Surcharge : 0.000 kip/in2
Depth of Soil above Footing : 0.000 in
Depth of Water Table : 5.000 m

Concrete and Rebar Properties

Unit Weight of Concrete : 25.000 kN/m3


Compressive Strength of Concrete : 25.000 N/mm2
Yield Strength of Steel : 415.000 N/mm2
Minimum Bar Size : Ø12
Maximum Bar Size : Ø60
Minimum Bar Spacing : 50.000 mm
Maximum Bar Spacing : 400.000 mm

------------------------------------------------------

Design Calculations

Footing Size Calculations

Reduction of force due to buoyancy = 0.000 kN

Area from initial length and width, Ao = Lo X Wo = 16.000 sq m

file:///C:/Staad.foundation%205.3/CalcXsl/Combined.xml 4/5/2021
Strip Footing Design Page 11 of 16

Min. area required from bearing pressure, Amin = P / qmax = 9.844 sq m

Note: Amin is an initial estimation.


P = Critical Factored Axial Load(without self weight/buoyancy/soil).
qmax = Respective Factored Bearing Capacity.

Final footing dimensions are:

Length of footing, L : 8.000 m


Width of footing, W : 2.000 m
Depth of footing, Do : 0.550 m
Area, A : 16.000 sq m
Length of left overhang, Lleft_overhang : 1.000 m

Length of right overhang, Lright_overhang : 1.000 m

------------------------------------------------------

Load Combination/s- Service Stress Level


Load Combination
Load Combination Title
Number
101 1.000 x DL+1.000 x DL+1.000 x DL
102 0.800 x DL+0.800 x DL+0.800 x DL
Load Combination/s- Strength Level
Load Combination
Load Combination Title
Number
201 1.500 x DL+1.500 x DL+1.500 x DL
202 0.960 x DL+0.960 x DL+0.960 x DL
203 1.200 x DL+1.200 x DL+1.200 x DL
204 0.900 x DL+0.900 x DL+0.900 x DL

Applied Loads - Service Stress Level


Axial Shear X Shear Z Moment X Moment Z
LC
(kN) (kN) (kN) (kNm) (kNm)
-
Column Number : 1
101 279.583 14.566 0.097 0.328 -13.972
102 223.667 11.653 0.077 0.263 -11.177
-
Column Number : 7
101 481.379 0.483 0.213 0.458 15.344
102 385.103 0.387 0.170 0.366 12.275
-
Column Number : 13
101 349.530 14.723 -0.309 -0.022 -14.160
102 279.624 11.779 -0.247 -0.017 -11.328

Applied Loads - Strength Level


Axial Shear X Shear Z Moment X Moment Z
LC
(kN) (kN) (kN) (kNm) (kNm)
-
Column Number : 1
201 419.375 21.849 0.145 0.492 -20.957
202 268.400 13.984 0.093 0.315 -13.413
203 335.500 17.480 0.116 0.394 -16.766
204 251.625 13.110 0.087 0.295 -12.574

file:///C:/Staad.foundation%205.3/CalcXsl/Combined.xml 4/5/2021
Strip Footing Design Page 12 of 16

-
Column Number : 7
201 722.069 0.725 0.319 0.687 23.016
202 462.124 0.464 0.204 0.439 14.730
203 577.655 0.580 0.255 0.549 18.413
204 433.241 0.435 0.191 0.412 13.810
-
Column Number : 13
201 524.295 22.085 -0.464 -0.032 -21.240
202 335.549 14.134 -0.297 -0.021 -13.594
203 419.436 17.668 -0.371 -0.026 -16.992
204 314.577 13.251 -0.278 -0.019 -12.744

Calculated Pressures at Four Corners

Pressure at Pressure at Pressure at Pressure at Area of footing in


Load Case corner 1 (q1) corner 2 (q2) corner 3 (q3) corner 4 (q4) uplift (Au)
(kN/m^2) (kN/m^2) (kN/m^2) (kN/m^2) (sq. m)

101 74.3152 71.3514 79.4963 82.4601 0.000

101 74.3152 71.3514 79.4963 82.4601 0.000

101 74.3152 71.3514 79.4963 82.4601 0.000

101 74.3152 71.3514 79.4963 82.4601 0.000

If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of
negative pressure will be set to zero and the pressure will be redistributed to remaining corners.

Summary of Adjusted Pressures at Four Corners

Pressure at Pressure at Pressure at Pressure at


Load Case corner 1 (q1) corner 2 (q2) corner 3 (q3) corner 4 (q4)
(kN/m^2) (kN/m^2) (kN/m^2) (kN/m^2)

101 74.3152 71.3514 79.4963 82.4601

101 74.3152 71.3514 79.4963 82.4601

101 74.3152 71.3514 79.4963 82.4601

101 74.3152 71.3514 79.4963 82.4601

------------------------------------------------------

Check for stability against overturning


Resisting Resisting
Moment X Moment Z
Load Case Moment X Moment Z Ratio X Ratio Z
(kNm) (kNm)
(kNm) (kNm)

101 21.719 31.613 1230.470 4921.880 56.653 155.690

102 17.376 25.291 1008.375 4033.502 58.034 159.486

file:///C:/Staad.foundation%205.3/CalcXsl/Combined.xml 4/5/2021
Strip Footing Design Page 13 of 16

------------------------------------------------------

Design for Flexure

Sagging moment along length

Critical load case : 201


Effective Depth = = 0.494 m
Governing moment (Mu) = 237.792 kNm

As Per IS 456 2000 ANNEX G G-1.1C

Limiting Factor1 (Kumax) = = 0.479107

Limiting Factor2 (Rumax) = = 3444.291146 kN/m^2

Limit Moment Of Resistance (Mumax) = = 1681.031322 kNm

Mu <= Mumax hence, safe

Hogging moment along length

Critical load case : 201


Effective Depth = = 0.494 m
Governing moment (Mu) = 146.776 kNm

As Per IS 456 2000 ANNEX G G-1.1C

Limiting Factor1 (Kumax) = = 0.479107

Limiting Factor2 (Rumax) = = 3444.291146 kN/m^2

Limit Moment Of Resistance (Mumax) = = 1681.031322 kNm

Mu <= Mumax hence, safe

Transverse direction

Critical load case : 201


Effective Depth = = 0.494 m
Governing moment (Mu) = = 305.686 kNm

As Per IS 456 2000 ANNEX G G-1.1C

Limiting Factor1 (Kumax) = = 0.479107

Limiting Factor2 (Rumax) = = 3444.291146 kN/m^2

Limit Moment Of Resistance (Mumax) = = 6724.125449 kNm

file:///C:/Staad.foundation%205.3/CalcXsl/Combined.xml 4/5/2021
Strip Footing Design Page 14 of 16

Mu <= Mumax hence, safe

Check trial depth for one way shear(along length)

Critical load case for maximum shear force along 201


the length of footing :
Shear Force(S) = 269.711 kN
Shear Stress(Tv) = 272.987135 kN/m^2

Percentage Of Steel(Pt) = 0.1381

As Per IS 456 2000 Clause 40 Table 19


Shear Strength Of Concrete(Tc) = 280.335 kN/m^2

Tv< Tc hence, safe

Check trial depth for two way shear

Critical Load case for Punching Shear Check : 201


For Column 1
Shear Force(S) = 352.690 kN
Shear Stress(Tv) = 224.794 kN/m^2

As Per IS 456 2000 Clause 31.6.3.1


Ks = = 1.000

Shear Strength(Tc)= = 1250.0000 kN/m^2

Ks X Tc = 1250.0000 kN/m^2

Tv<= Ks X Tc hence, safe

Critical Load case for Punching Shear Check : 201


For Column 2
Shear Force(S) = 656.260 kN
Shear Stress(Tv) = 418.281 kN/m^2

As Per IS 456 2000 Clause 31.6.3.1


Ks = = 1.000

Shear Strength(Tc)= = 1250.0000 kN/m^2

Ks X Tc = 1250.0000 kN/m^2

Tv<= Ks X Tc hence, safe

Critical Load case for Punching Shear Check : 201


For Column 3
Shear Force(S) = 459.712 kN
Shear Stress(Tv) = 293.007 kN/m^2

As Per IS 456 2000 Clause 31.6.3.1


Ks = = 1.000

Shear Strength(Tc)= = 1250.0000 kN/m^2

Ks X Tc = 1250.0000 kN/m^2

hence, safe

file:///C:/Staad.foundation%205.3/CalcXsl/Combined.xml 4/5/2021
Strip Footing Design Page 15 of 16

Tv<= Ks X Tc

Selection of reinforcement

Top reinforcement along length

As Per IS 456 2000 Clause 26.5.2.1


Minimum Area of Steel (Astmin) = 1320.000 mm2

Calculated Area of Steel (Ast) = 834.647 mm2

Provided Area of Steel (Ast,Provided) = 1320.000 mm2

Astmin<= Ast,Provided Steel area is accepted

Selected bar Size (db) = Ø12

Minimum spacing allowed (Smin) = 50.000 mm

Selected spacing (S) = 171.636 mm


Smin <= S <= Smax and selected bar size < selected maximum bar size... The reinforcement is
accepted.

Along width

As Per IS 456 2000 Clause 26.5.2.1


Provided Minimum Area of Steel (Astmin) = 5280.000 mm2

Selected bar Size (db) = Ø12

Minimum spacing allowed (Smin) = 50.000 mm

Selected spacing (S) = 171.478 mm


Smin <= S <= Smax and selected bar size < selected maximum bar size... The reinforcement is
accepted.

Bottom reinforcement along length

As Per IS 456 2000 Clause 26.5.2.1


Minimum Area of Steel (Astmin) = 1320.000 mm2

Calculated Area of Steel (Ast) = 1364.531 mm2

Provided Area of Steel (Ast,Provided) = 1364.531 mm2

Astmin<= Ast,Provided Steel area is accepted

Selected bar Size (db) = Ø12

Minimum spacing allowed (Smin) = = 50.000 mm

Selected spacing (S) = 157.333 mm


Smin <= S <= Smax and selected bar size < selected maximum bar size... The reinforcement is
accepted.

Along width

As Per IS 456 2000 Clause 26.5.2.1

file:///C:/Staad.foundation%205.3/CalcXsl/Combined.xml 4/5/2021
Strip Footing Design Page 16 of 16

Minimum Area of Steel (Astmin) = 5280.000 mm2

Calculated Area of Steel (Ast) = 1726.437 mm2

Provided Area of Steel (Ast,Provided) = 5280.000 mm2

Astmin<= Ast,Provided Steel area is accepted

Selected bar Size (db) = Ø12

Minimum spacing allowed (Smin) = = 50.000 mm

Selected spacing (S) = 171.478 mm


Smin <= S <= Smax and selected bar size < selected maximum bar size... The reinforcement is
accepted.

Provided Reinforcement

Main bar no. for top Reinforcement: Ø12


Spacing of top reinforcement bar : 171.636 mm

Based on spacing reinforcement increment; provided reinforcement is

Ø12 @ 170 mm o.c.

Main bar no. for bottom Reinforcement: Ø12


Spacing of bottom reinforcement bar : 157.333 mm

Based on spacing reinforcement increment; provided reinforcement is

Ø12 @ 155 mm o.c.

Distribution bar no.: Ø12


Spacing of distribution bars : 171.478 mm

Based on spacing reinforcement increment; provided reinforcement is

Ø12 @ 170 mm o.c.

Distribution bar no.(Top): Ø12


Spacing of distribution bars(Top) : 171.478 mm

Based on spacing reinforcement increment; provided reinforcement is

Ø12 @ 170 mm o.c.

------------------------------------------------------
Print Calculation Sheet

file:///C:/Staad.foundation%205.3/CalcXsl/Combined.xml 4/5/2021