NFS-320 Fire Alarm Control Panel
NFS-320 Fire Alarm Control Panel
Disclaimer: These battery calculations are designed exclusively for architects, engineers, consultants and NOTIFIER authorized
distributors to assist in the development of fire alarm equipment quotations. There are no implied warranties or guarantees in the
documents generated by this program other than the standard limited warranty offered by NOTIFIER. NOTIFIER cannot ensure that
any documents generated using this program meet all applicable codes and laws. The user of this program must be familiar with
required codes and laws as well as the requirements of the Authority Having Jurisdiction and must amend the generated documents
as necessary. At some point in time, some of these devices may no longer be available from NOTIFIER.
This workbook contains battery calculation worksheets that allow you to:
1
120 VAC 220/240 VAC
Device Qty Current Total
CPS-24 1 x 5.00 A 5.00 A
AA-30 0 x 1.00 A
AA-120 0 x 1.85 A
ACPS-2406 0 x 2.70 A
APS-6R 0 x 2.50 A
AVPS-24 0 x 1.00 A
CHG-120 0 x 2.00 A
FCPS-24 0 x 2.00 A
FCPS-24S6/S8 0 x 3.20 A
MPS-24A 0 x 1.80 A
MPS-24B 0 x 2.40 A
XPIQ 0 x 3.50 A
XRM-24 0 x 1.00 A
ACPS-610 0 x 5.00 A
APS2-6R 0 x 2.90 A
DAA Series 0 x 4.50 A
HPFF8 0 x 3.60 A
HPFF12 0 x 5.00 A
DS-AMP (25V) 0 x 4.10 A
DS-AMP (70V) 0 x 3.55 A
NFC-50/100 0 x 3.50 A
NFC-50DA (25v) 0 x 1.10 A
NFC-50DA (70.7v) 0 x 1.20 A
NFC-125DA 0 x 2.20 A
DAA2-5025 0 x 2.05 A
DAA2-5070 0 x 2.13 A
DAA2-7525 0 x 2.82 A
DAX-5025 0 x 0.50 A
DAX-5070 0 x 0.55 A
DAX-3525 0 x 0.50 A
DAX-3570 0 x 0.55 A
[ ] 0 x 0.00 A
[ ] 0 x 0.00 A
1 AC Branch 5.00 A
Required:
System Current Draw - NFS-320
Page 7 of 9
Battery Distribution Chart
Shows amp-hour distribution of your selections.
Comments
1. Batteries will fit in the FACP cabinet.
2. Selected battery size meets secondary load requirements.
3. The selected batteries (12AH) are outside the charger range of this power supply (18-200AH).
Spare Battery Capacity 3.58 Battery Selection (AH) - Secondary Load Requirements (AH)
Secondary Standby Load 8.35 Secondary Standby Load (AH) * Derating Factor
Secondary Alarm Load 0.07 Secondary Alarm Load (AH) * Derating Factor
Page 8 of 9
Device Current Draw
NFS-320 Fire Alarm Control Panel
Quantity x [device current draw] = total current draw per device (in amps)
Part Number Qty Primary Non-Alarm Primary Alarm Secondary Non-Alarm
CPU-320 1 x [0.25000] = 0.25000 x [0.25000] = 0.25000 x [0.25000] = 0.25000
CPS-24 1 x [0.00000] = 0.00000 x [0.00000] = 0.00000 x [0.04000] = 0.04000
SLC Loop Device Activation Current 1 x [0.00000] = 0.00000 x [0.40000] = 0.40000 x [0.00000] = 0.00000