Catalog Accessories Dust Collector Series 909 Asco en 4278956

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

SEQUENCERS

FOR DUST COLLECTOR SYSTEMS Series

without internal ∆P pressure sensor


E909
for the control of up to 48 solenoid valves

FEATURES
● Electronic controller for the control of solenoid valves in dust collector systems
● ON/OFF filter cleaning cycle from external switch
● Microprocessor management
● Supply and output voltage selectable via jumper
● 3 programming keys
● 3 digit LED display
● Adjustable pulse and interval times
● Automatic detection of number of valves
● Additional post-cleaning cycle mode
● High immunity from external interference
● Short-circuit protection of every single output
● 1 output relay (e.g. group alarm), 2 digital inputs (volt-free)

CONSTRUCTION
Housing ABS (acryl nitrile butadiene styrene), grey
Cover PC (polycarbonate), transparent

ELECTRICAL CHARACTERISTICS
Standard supply voltage AC (~) 230/115 V
Output voltage DC (=) 24 V
Other voltages on request.
max.
ambient electrical
load power
temperature enclosure
per output
protection
(W) (°C)
25 -10 to 60 IP65

SPECIFICATIONS
number adjustable adjustable
of pulse time interval time size catalogue numer
solenoid valves sec. sec.
4 E909PB4MU1.2
1
8 E909PB8MU1.2
12 E909PB12MU1.3
2
16 E909PB16MU1.3
20 E909PB20MU1.5
24 E909PB24MU1.5
0,05 - 5,0 1 - 999 3
Availability, design and specifications are subject to change without notice. All rights reserved.

28 E909PB28MU1.5
32 E909PB32MU1.5
36 E909PB36MU1.6
40 E909PB40MU1.6
4
44 E909PB44MU1.6
48 E909PB48MU1.6
60300GB-2016/R01

All leaflets are available on: www.asconumatics.eu


61
SEQUENCERS FOR DUST COLLECTOR SYSTEMS SERIES E909

OPTIONS (on request)


● Other voltage ratings, other housings and devices with ATEX approval

INSTALLATION
Installation/maintenance instructions are included with each sequencer

DIMENSIONS (mm), WEIGHTS


Sizes 1 and 2 Size 3

Size 4

Availability, design and specifications are subject to change without notice. All rights reserved.
60300GB-2010/R01

All leaflets are available on: www.asconumatics.eu


62
SEQUENCERS FOR DUST COLLECTOR SYSTEMS SERIES E909

WIRING DIAGRAM
SWITCH (option)

PB16 PB32 PB48


K x 5A/250 V AC
02 FUSE
01 04 See technical features
POWER

K1 EARTH
COMMON
S0 03 D1a D6/C6
OUTPUT NUMBER
01

45 15

46 16

47 17

48 18

61 31

62 32

63 33

64 34

77 47

78 48
31 1

32 2
CLAMPS 12A
+1
-2

30
12
13

14
15
3

3
4
5
250V 2,5 mm²
PE
N
L

SUPPLY VOLTAGE
1 Phase 2 Neutral 3 Earth
See technical features

EV.15

EV.16

EV.17

EV.18

EV.31

EV.32

EV.33

EV.34

EV.47

EV.48
EV.1

EV.2
CUMULATIVE ALARM RELAY

ADDITIONAL CYCLES BY CONTACT FROM FAN


(contact closed = fan ON)
NOTE: link clamps if not used with inputs from external OUTPUT VOLTAGE FOR ELECTRO-VALVES
contact enabled (F01=0) See technical features
R C
ON/OFF CLEANING CYCLE BY EXTERNAL
CONTACT/PRESSURE SWITCH R = 100÷200Ω
D6 WITH F07=1, C6 WITH F07=0 2 1 C = 100nF 400V
(contact closed = cycle enabled)
NOTE: link clamps if not used with inputs from external contact
enabled (F01=0)

ATTENTION: with output voltage 230VAC use connectors with RC


filter inside or insert RC filter on every supply line of any
electrovalves.
If filters are not used, an operating malfunction could happen.
Availability, design and specifications are subject to change without notice. All rights reserved.
60300GB-2010/R01

All leaflets are available on: www.asconumatics.eu


63
64
All leaflets are available on: www.asconumatics.eu
SEQUENCERS FOR DUST COLLECTOR SYSTEMS SERIES E909

60300GB-2010/R01
Availability, design and specifications are subject to change without notice. All rights reserved.

You might also like