TCPL - 1X63.75 MW Power Plant Gummidipoondi Doc .Ref.:LMI /OPR/ 13 Date of Issue:20/08/2002 Rev:0 Page 1 o 8
TCPL - 1X63.75 MW Power Plant Gummidipoondi Doc .Ref.:LMI /OPR/ 13 Date of Issue:20/08/2002 Rev:0 Page 1 o 8
STAND BY LOGIC : stand by pump will get start command if the following conditions are
satisfied
a. 1. PUMP SELECTOR IN REMOTE POSITION
2. STAND BY PERMISSIVE ( it will be persisting when pump started with delay time 2 sec )
3. PUMP MAIN CONTACTOR IN NOT ON POSITION (IF RUNNING PUMP TRIPS )
( OR )
b. SOLENOID VALVE ANOMALY (MISSING OPEN /MISSING CLOSE ( DELAY TIME :3 SECS)
ZERO SETTING SEQUENCE ALARM : zero setting sequence alarm will be persisting if any
one of the following conditions are satisfied. once this alarm appears, the evacuation cycle as
well as the running pump stops.
SILO DUST LEVEL IS HIGH
IN LINE FILTER DP HIGH ( PIDSH 731 )
PULSE JET FILTER DP HIGH (DELAY TIME :10 MINS) (PIDSHH 730 )
CLAPET/ EQUALISER FAULT IN THE DISCHARGE OF THE CONTINUOUS OPERATING
CYCLONE OR TWO DOOR DISCHARGE.
NOTE : the scheme is typical for all other Ash intake valves
MANUAL MODE :
Segregating valve will open in manual mode if the following conditions are satisfied
1. CYCLIC SEQUENCE SELECTOR IN MANUAL POSITION
2. HOPPER SELECTOR IN “1” POSITION (C10)
3. PERMISSIVE FOR SEQUENCE --- APH BRANCH SELECTOR IN “1 “ POSITION (C10)
(CYCLE START COMMAND IS INITIATED FOR THE
CONCERNED HOPPER )
2. MANUAL MODE :
Segregating valve will get close command with manual mode if the following conditions
are satisfied
CYCLIC SEQUENCE SELECTOR IN MANUAL POSITION
BRANCH APH CLOSING PERMISSIVE
FLUIDISING BLOWER-1 :
Fluidising blower will start if any one set of the conditions are satisfied
AUTO MODE :
1. MAN- O- AUTO SELECTOR SWITCH IN AUTO POSITION
2. LOC-O- REM SELECTOR IN REMOTE POSITION
3. SILO PRESSURE PERMISSIVE ( P <- 100 MMWCL )
4. PERMISSIVE FOR STARTING 1 ST BLOWER ( i.e BLOWER NOT ON STAND BY
MODE )
OR
2 ND BLOWER STOPS / TRIPS, AND 1 ST BLOWER SELECTED IN STAND BY MODE
MANUAL MODE :
1. MAN- O- AUTO SELECTOR SWITCH IN MANUAL POSITION
2. LOC-O- REM SELECTOR IN REMOTE POSITION
3. PRESS START P.B FROM PANEL
OR
LOCAL MODE :
1. MAN- O- AUTO SELECTOR SWITCH IN LOCAL POSITION
2. LOC-O- REM SELECTOR IN REMOTE POSITION
3. PRESS START P.B FROM LOCAL
STOP LOGIC :
1. MAN- O- AUTO SELECTOR SWITCH IN “0” POSITION
2. LOC-O- REM SELECTOR IN “ O “ POSITION
3. PRESS STOP P.B FROM LOCAL
4. ELECTRICAL PROTECTION INTERVENED
VENTING FAN 1 :
It will start if any one set of the conditions are satisfied
AUTO MODE :
1. MAN- O- AUTO SELECTOR SWITCH IN AUTO POSITION
2. LOC-O- REM SELECTOR IN REMOTE POSITION
3. DAMPER CLOSED
4. PERMISSIVE FOR STARTING 1 ST FAN ( i.e FAN NOT ON STAND BY MODE )
OR
2 ND FAN STOPS / TRIPS, AND 1 ST FAN SELECTED IN STAND BY MODE
MANUAL MODE :
1. MAN- O- AUTO SELECTOR SWITCH IN MANUAL POSITION
2. LOC-O- REM SELECTOR IN REMOTE POSITION
LOCAL MODE :
AUTO MODE :
1. CLEANING PANEL AUTO – MAN SELECTOR SWITCH IN AUTO MODE
2. CLEANING PANEL 0-1 SELECTOR SWITCH IN “ 1 “ POSITION
3. ANY FAN VENTING FAN ON
MANUAL MODE :
FLUDIZING SYSTEM :
The following sequence of operation is carried out automatically for fluidizing system
after starting 1 st or 2 nd blower
The lifting is done through a P.B as soon as the telescopic leaves its
bottom position, the rotary valve closes & consequently the discharging stops.
MANUAL MODE :
MANUAL MODE :
MANUAL MODE :
MANUAL MODE :
MANUAL MODE :
MANUAL MODE :
MANUAL MODE :
MANUAL MODE :
MANUAL MODE :
MANUAL MODE :
1 ST BLOWER :
1 ST blower will start if any one set of the conditionsn are satisfied
AUTO MODE :
5. MAN- O- AUTO SELECTOR SWITCH IN AUTO POSITION
6. LOC-O- REM SELECTOR IN REMOTE POSITION
7. SILO PRESSURE PERMISSIVE ( P <- 100 MMWCL )
8. PERMISSIVE FOR STARTING 1 ST BLOWER ( i.e BLOWER NOT ON STAND BY
MODE )
OR
2 ND BLOWER STOPS / TRIPS, AND 1 ST BLOWER SELECTED IN STAND BY
MODE
MANUAL MODE :
4. MAN- O- AUTO SELECTOR SWITCH IN MANUAL POSITION
5. LOC-O- REM SELECTOR IN REMOTE POSITION
6. PRESS START P.B FROM PANEL
OR
LOCAL MODE :
4. MAN- O- AUTO SELECTOR SWITCH IN LOCAL POSITION
5. LOC-O- REM SELECTOR IN REMOTE POSITION
6. PRESS START P.B FROM LOCAL
STOP LOGIC :
5. MAN- O- AUTO SELECTOR SWITCH IN “0” POSITION
6. LOC-O- REM SELECTOR IN “ O “ POSITION
7. PRESS STOP P.B FROM LOCAL
8. ELECTRICAL PROTECTION INTERVENED
1 ST VENTING FAN :
1 ST FAN will start if any one set of the conditionsn are satisfied
AUTO MODE :
5. MAN- O- AUTO SELECTOR SWITCH IN AUTO POSITION
6. LOC-O- REM SELECTOR IN REMOTE POSITION
7. DAMPER CLOSED
8. PERMISSIVE FOR STARTING 1 ST FAN ( i.e FAN NOT ON STAND BY MODE )
OR
MANUAL MODE :
4. MAN- O- AUTO SELECTOR SWITCH IN MANUAL POSITION
5. LOC-O- REM SELECTOR IN REMOTE POSITION
6. PRESS START P.B FROM PANEL
OR
LOCAL MODE :
AUTO MODE :
4. CLEANING PANEL AUTO – MAN SELECTOR SWITCH IN AUTO MODE
5. CLEANING PANEL 0-1 SELECTOR SWITCH IN “ 1 “ POSITION
6. ANY FAN VENTING FAN ON
MANUAL MODE :
STOP LOGIC :
FLUDIZING SYSTEM :
The foll0wing sequence of operation is carried out automatically for fluidizing system
after starting 1 st or 2 nd blower
The lifting is done throhgh a p.b as soon as the telescopic leaves its
bottom position, the rotary valve closes & consequently the discharging stops.