MOTOR SPEED L1 L2 L3 OPEN TOGETHER

CONNECTIONS
-NOMENCLATURE- SLOW T1 T2 T3 T4,T5,T6
CONSTANT HP FAST T6 T4 T5 T1,T2,T3
1M & 2M CONTACTORS MECHANICALLY SLOW T1 T2 T3 T6,T4,T5
AND ELECTRICALLY INTERLOCKED. CONSTANT TORQUE FAST T6 T4 T5 T1,T2,T3
OL-OVERLOAD RELAY. VARIABLE TORQUE SLOW T1 T2 T3 T6,T4,T5
I-INDICATING LIGHT FAST T6 T4 T5 T1,T2,T3
*-IF USED
FU-FUSE CONNECTION TABLE CONTROLLER TERMINALS
X-INDICATES CONTACT CLOSED A B C D E F
CONSTANT HP T6 T4 T5 T1 T2 T3
FOR SEPARATE CONTROL- REMOVE WIRES "A" CONSTANT TORQUE T1 T2 T3 T6 T4 T5 AUX INTLK ON
& "B" AND CONNECT CONTROL SOURCE TO NO. 9 VARIABLE TORQUE T1 T2 T3 T6 T4 T5 CIRC BKR OR DISC
ON OL AND NO. 1 ON PILOT DEVICE. L1 L2 L3 (IF USED)
BACK VIEW FRONT VIEW
TABLE A TABLE B HIGH
LOW (IF USED)
PILOT DEVICES PILOT DEVICES (IF USED)
(REAR VIEW) (REAR VIEW)
FOR CONSTANT FOR VARIABLE OR
HP MOTORS CONSTANT TORQUE MOTORS I I CIRCUIT BREAKER OR A
DISCONNECT SWITCH B
(IF USED)

OFF OFF
AUTO HAND SLOW FAST AUTO HAND SLOW FAST
X X
X 5 X 3
4 2
2 4
5 X
3 5 Y
1 1 FOR 4
CONNECTIONS 3 5
SLOW SLOW REFER TO 3 L3
8 8 TABLE "A"
L1
2 L1 L2 L3 B L2
1 2 4
REMOTE REMOTE
DEVICE DEVICE 1M Z 2M
FAST FAST
6
7
FACTORY SUPPLIED PILOT DEVICES ARE WIRED
PER TABLE "B". FOR CONSTANT HP MOTORS
INTERCHANGE WIRES 3 & 5, AND 2 & 4
IF USED WIRE PER TABLE "A".
WIRE "B" WIRE "A" 9

WIRES "A" & "B" HAS BEEN OMITTED AT FACTORY C A OVERLOAD RELAY
ON FORMS HAVING COIL VOLTAGE OF 120V OR LESS
OVERLOAD RELAY
NOTE: ADDITIONAL OVER-CURRENT PROTECTION A B C
MAY BE REQUIRED. REFER TO THE D E F
NATIONAL ELECTRICAL CODE OR LOCAL
ELECTRICAL CODE AS REQUIRED.

LINE LOAD D E F C A B
TORQUE LINE AND CR309 20 LB-IN 20 LB-IN
LOAD TERMINALS CR310 AS MARKED 20 LB-IN WIRE MOTOR TO CONTROLLER PER CONNECTION TABLE CONTROL
CIRCUIT FUSING
AS SHOWN AT CR311 35 LB-IN 20 LB-IN L1 CONTROL ELEMENTARY L2
RIGHT: CR390 AS MARKED 20 LB-IN * L1 L2

I
FAST
GROUND KIT SLOW 2M OL OL FU FU
2 3 6 9
1/2-IN CONDUIT 55-213403G001 1M
3/4-IN CONDUIT 55-213403G002 HAND
OFF
AUTO
1M
1-IN CONDUIT 55-213403G003 X
* I
1 9
1 1/4-IN CONDUIT 55-213403G004
1 1/2-IN CONDUIT 55-213403G005 X
4 5 1M
2-IN CONDUIT 55-213403G006 2M
2 1/2-IN CONDUIT 55-213403G007 2M
3-IN CONDUIT 55-213403G008

ALTERNATIVE LEGENDS FOR FAST AND SLOW


REMOTE
DEVICE
SLOW WIRING DIAGRAM
ARE HIGH AND LOW. 2 SPEED - 1 WINDING SIZE 0 & 1
FAST
THIRD ANGLE SHEET# DWG NO. DATE REV
FOR CONTROLLER WITHOUT DISCONNECT MEANS-WIRE
LINE DIRECT TO L1, L2 AND L3 ON CONTACTOR. 1 of 1 55-533840 03/21 05