Technical Leaflet Te Sys TV 7
Technical Leaflet Te Sys TV 7
Index
Index..............................................................................................................................................................1
Chapter 1. Brief Introduction of TeSys® T Motor Management System..................................................3
1.1 The Offer Provides You… ............................................................................................................................3
1.2 Overview of the Functionality ......................................................................................................................3
1.2.1 Control Functions ...................................................................................................................................................3
1.2.2 Protection Functions...............................................................................................................................................4
1.2.3 Metering and Monitoring Functions.......................................................................................................................4
Chapter 2. Components and Selection Guide ............................................................................................5
2.1 Architecture of the Offer ..............................................................................................................................5
2.2 Description of the main parts .......................................................................................................................5
2.2.1 LTM R Controller with Modbus Communication Port ..........................................................................................6
2.2.2 LTM R Controller with Other Communication Ports.............................................................................................6
2.2.3 LTM E Expansion Module .....................................................................................................................................7
2.2.4 Magelis HMI XBTN410.........................................................................................................................................7
2.3 Selection Guide ..............................................................................................................................................8
2.4 References.......................................................................................................................................................9
2.5 Technical Specification................................................................................................................................10
2.6 Dimensions and Mechanical Installation...................................................................................................12
Chapter 3. Functionality...........................................................................................................................13
3.1 Measurements and Motor Protection Functions ......................................................................................13
3.2 Monitoring Functions..................................................................................................................................14
3.2.1 Statistics................................................................................................................................................................14
3.2.2 Diagnostic Faults ..................................................................................................................................................14
3.2.3 Motor States .........................................................................................................................................................14
3.2.4 User Map ..............................................................................................................................................................14
3.3 Motor Control Functions ............................................................................................................................15
3.3.1 Control Modes and Operating States....................................................................................................................15
3.3.2 Operating Modes ..................................................................................................................................................15
3.3.3 Fault Management ................................................................................................................................................15
3.4 Commissioning.............................................................................................................................................15
Chapter 4. Application Examples .............................................................................................................16
4.1 Supported Application Segments ...............................................................................................................16
4.2 Application Examples..................................................................................................................................17
4.2.1 Overload Mode Wiring Diagrams ........................................................................................................................17
4.2.2 Independent Mode Wiring Diagrams ...................................................................................................................18
4.2.3 Reversing Mode Wiring Diagrams.......................................................................................................................18
4.2.4 Two-Step Wye-Delta Mode Wiring Diagrams .....................................................................................................19
4.2.5 Two-Step Primary Resistor Mode Wiring Diagrams............................................................................................19
4.2.6 Two-Step Autotransformer Mode Wiring Diagrams............................................................................................20
4.2.7 Two-Speed Dahlander Mode Wiring Diagrams ...................................................................................................20
4.2.8 Two-Speed Pole Changing Mode Wiring Diagrams ............................................................................................21
Control
Functions
Protection
Pre-defined Functions
Commissioning/
Control/Monitor Operating
Modes Motor Voltage
Through Thermal
Control Modes Protections
Magelis HMI PC with Custom Overload
1 to 1 PowerSuiteTM Logic Protections Power
TeSys Magelis HMI
Software Fault Current Protections
Management Protections
1 to n PLC/DCS
User
Modbus Current Measurement Fault Diagnostics
Profibus
CANOpen Wiring/Configuration Errors
DeviceNet Voltage Measurement
Internal Fault Monitoring
EtherNet
Power Measurement Sensor Fault Monitoring
Communication Thermal Overload/Current Monitoring
with PLC/DCS Statistics
Voltage/Power Monitoring
Diagnostics
User Map Communication Monitoring
Motor States
Independent X X
Predefined
mode
Reverser X X
mode
Two-step X X
Two-speed X X
Custom Logic User defined logic for operating mode X X
Manual reset X X
Fault Management Automatic reset X X
Remote reset X X
tion errors
configura-
Application for 1 to 1
Application for 1 to n
XBTN410 Cable
Magelis Operator, connected to the controller or expansion module
Cable &
PowerSuite Converter
0.04m 0.3m/1.0m
Expansion Module, connected with main controller through calbes
External CT Ground CT
External CT for upto 810A, and Ground CT for precise ground protection
* Note: Controller with EtherNet port will be launched in the middle of 2007
* Note: Controller with EtherNet port will be launched in the middle of 2007
Start
Modbus
Select the DeviceNet
relevant Select LTM R for
N communica DeviceNet
tion cable
1 to 1?
1 to 1 1 to n?
1 to n
N Select 1 to 1 Select 1 to n
application application
2.4 References
Picture Description Category Branches Part Number
FLA Range (A) Control Voltage (V)
DC 24 LTM R08MBD
0.4 ~ 8
AC 100 ~ 240 LTM R08MFM
Modbus DC 24 LTM R27MBD
1.35 ~ 27
AC 100 ~ 240 LTM R27MFM
DC 24 LTM R100MBD
5 ~ 100
AC 100 ~ 240 LTM R100MFM
DC 24 LTM R08PBD
0.4 ~ 8
AC 100 ~ 240 LTM R08PFM
DC 24 LTM R27PBD
Profibus DP 1.35 ~ 27
AC 100 ~ 240 LTM R27PFM
DC 24 LTM R100PBD
5 ~ 100
AC 100 ~ 240 LTM R100PFM
DC 24 LTM R08DBD
0.4 ~ 8
AC 100 ~ 240 LTM R08DFM
Main contoller DC 24 LTM R27DBD
DeviceNet 1.35 ~ 27
AC 100 ~ 240 LTM R27DFM
DC 24 LTM R100DBD
5 ~ 100
AC 100 ~ 240 LTM R100DFM
DC 24 LTM R08CBD
0.4 ~ 8
AC 100 ~ 240 LTM R08CFM
DC 24 LTM R27CBD
CANOpen 1.35 ~ 27
AC 100 ~ 240 LTM R27CFM
DC 24 LTM R100CBD
5 ~ 100
AC 100 ~ 240 LTM R100CFM
DC 24 LTM R08EBD
0.4 ~ 8
AC 100 ~ 240 LTM R08EFM
DC 24 LTM R27EBD
Ethernet 1.35 ~ 27
AC 100 ~ 240 LTM R27EFM
DC 24 LTM R100EBD
5 ~ 100
AC 100 ~ 240 LTM R100EFM
Inputs Control Voltage (V) Part Number
DC 24
LTM EV40BD
Expansion module
AC 100 ~ 240 LTM EV40FM
Ratio
30:1 LUTC0301
50:1 LUTC0501
®
TeSys U CT 100:1 LUTC1001
200:1 LUTC2001
External CT, support 400:1 LUTC4001
current sensing up to 800:1 LUTC8001
810A 100:1 LT6CT1001
LT6 CT 400:1 LT6CT4001
800:1 LT6CT8001
300:5 31102-085
Square D Starter Size CT 600:5 31105-049-50
900:5 31124-033
Diameter (mm)
30 TA30
Ground CT, support 50 PA50
TeSys® U CT
ground current detection 80 IA80
120 MA120
196 SA200
Length (m)
Connection cable from TeSys® T
0.04 LTMCC004
the expansion module 0.3 LU9R03
®
to main controller TeSys U
1.0 LU9R10
Connection cable to
Magelis 2.5 XBTZ938
Magelis HMI
RS232-485 converter
PowerSuite™ 1.0 VW3A8106
with connection cable
0.3 VW3A8306R03
Connection cable to
PowerSuite™ 1.0 VW3A8306R10
Modbus network
3.0 VW3A8306R30
Specific terminal for
To be defined
OKKEN panel
Chapter 3. Functionality
Over Power To signal a warning or a fault when the power factor the threshold
X X
Factor and remains above that threshold for a threshold time
Power Factor
Under Power To signal a warning or a fault when the power factor falls below the
X X
Factor threshold and remains below that threshold for a threshold time
Active Power
Consumption
Reactive Power
Consumption
Operating States
The controller responds to the state of the motor and provides control, monitoring and protection functions
appropriate to each of the motor’s operating states. A motor’s primary operating states are: Ready, Not Ready,
Start and Run. Fault and Warning Conditions may occur in any of the motor states. A fault response may change
the operating state from Ready to Not Ready.
3.4 Commissioning
Commissioning is a pre-process toward the system before using, which includes: initialization of the installed
devices, and configuration of controller parameters required to control, protect and monitor the controller,
expansion module, and other devices included in the application.
Commissioning could be implemented by 3 means:
Using the keypad of the Magelis XBTN410 HMI device
Using a PC running PowerSuite™ software
Using the network port
Supported Industries
The motor management system supports many industries and associated business sectors including the following:
Industry Sectors Application
Office buildings Control and manage the building facilities:
Shopping centers Critical HVAC systems
Industrial buildings Water
Building Ships Air
Hospitals Gas
Cultural facilities Electricity
Airports Steam
Metal, mineral, and mining: cement, glass, steel, Control and monitor pump motors
ore-extraction Ventilation
Microelectronic Control load traction and movements
Industry Petrochemical View status and communicate with machines
Chemical: pulp and paper industry Process and communicate the data captured
Pharmaceutical Remote data management for one or several
Food and beverage sites via Internet
Water treatment and transportation Control and monitor pump motors
Transportation infrastructure for people and Ventilation
Energy and
freight: airports, road tunnels, subways and Remote control of wind turbine
Infrastructure
tramways Remote data management for one or several
Power generation and transport sites via the internet
Diagram with 3-Wire Local Control Diagram with 2-Wire Local Control
Diagram with 3-Wire Local Control with Network Control Selectable Diagram with 2-Wire Local Control with Network Control Selectable
Diagram with 3-Wire Local Control Diagram with 2-Wire Local Control
with Network Control Selectable