Correctivos San Ignacio

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 4

Dicember

Inverter: 01_26_2, 06_09_1


Device out of service, Damaged DC circuit board, Replacement of device
Inverters: 06_07_1 y 06_07_2
Device out of service, Low insulation resistance in phase A, Replacement of cable and terminals
Solar panel: string 01, inverter 04_25_2
Device out of service, Hot spot on cell of solar panel, Replacement of solar panel
TCU PV05 Multiple connector
Device out of service, Multiple connector damaged, multiple connector replacement
ACBox 2.13
Device out of service, Switch Opening , Insulance resistance tests
Anemometer of PV01
Device out of service, Physical damage, Damage repair

January
Inverter: 06_09_2
Device out of service Device alarmed by internal fault Device replacement

Inverter: 06_23_2
Device out of service Device alarmed by internal fault Device replacement

Inverter: 01_25_2
Device out of service Device alarmed by internal fault Device replacement

Circuit breaker no. 24, no. 23


Sulphated terminals, Preventive detection of sulfate terminals, Replacement of wiring and terminals

Inverter: 04_19_1
Device out of service Device alarmed by internal fault Device replacement

Inverter: 03_08_2
Device out of service Device alarmed by internal fault Device replacement

Inverter: 04_21_1
Device out of service Device alarmed by internal fault Device replacement in march

Inverter: 05_02_1
Device out of service Device alarmed by internal fault Device replacement in march
Inverters: 02_18_1 & 02_18_2
Inverters: 01_24_2
Device out of service Device alarmed by internal fault Device replacement in march

Inverter: 02_12_2
Device out of service Device alarmed by internal fault Device replacement in march

Circuit breaker no. 21.3, no. 22


Device out of service, Device alarmed by internal fault, Inspection and reset device

Inverter: 04_23_2
Device out of service Device alarmed by internal fault Device replacement in march

Inverter: 03_25_1
Device out of service Device alarmed by internal fault Device replacement in march

Febraury
Inverter: 03_24_2, 06_14_1, 05_07_2, 02_23_1, 05_09_2
Device out of service Device alarmed by internal fault Device replacement in march

Inverter: 05_09_2
Device out of service Device alarmed by internal fault Device replacement in april

ACBox: 02_05
Device out of service, Damaged circuit breaker by short-circuit, Circuit breaker replacement

ACBox: 01_12
Device out of service, Devices alarmed by AC circuit breaker openning, Inspection and insulation resistance
test

Electric motor: 01_146, 06_163, 06_212 y 06_218, 04_003, 04_016, 04_168 y 06_191
Devices out of service, Damaged electric motor, Device replacement

March
Inverter: 04_24_2

Low voltage multiple connector PV 05, 03


Damaged device Device damaged by heating Device replacement

Inverter: 06_13_1
Device out of service Device alarmed by internal fault Device replacement in april

ACBox: 02_07
Device out of service, Damaged circuit breaker by short-circuit, Circuit breaker replacement

Circtuit breaker 1_26


Damaged cable, Insulation damage, Cable replacement
Inverter: 04_13_1, 03_22_1
Device out of service Device alarmed by internal fault Device replacement in may

Inverter: 3_16_01
Device out of service Device alarmed by internal fault Device replacement in april

TCU (6_063, 6_096)

TCU (2_085, 2_086, 2_094) (2_050, 6_194, 6_150, 6_169)

April

ACBox: 03_22, 01_18


Device out of service, Damaged circuit breaker, Circuit breaker replacement

ACBox: 02_17
Device out of service, Damaged cable, replacement of terminal in conductor

Inverter: 02_16_1
Device out of service, Low insulation resistance, Protection parameter setting

Photovoltaic modules PV 04
Device with internal damage, Device with internal damage, Replacement of photovoltaic module

Auxiliary services transformer


Device out of service, Device with internal damage, Replacement of transformer

Inverter: 06_07_2

Cable replacement string 03


Insulation fault, Low insulation resistance, Cable replacement

Inverter: 02_25_2

Inverter: 05_07_1

Inverter: 03_27_1
Electrical junction replacement, Electrical junction in bad conditions, Electrical junction replacement

Inverter: 01_17_1
Device out of service, Software fault, Software update

Swicth 3_26
Device out of service, Damaged cable, Cable replacement
MAY
ACBox 06_05 phase B, 06_06 phase C
Device out of service, Insulation fault on phase, Replacement of cable

Inverter 01_14_1
Device out of service, Insulation fault on phases "A" and "B", Replacement of cable

Inverter 01_02_1
Loss of communication, Loss of communication, Device reset

You might also like