GEOTECHNICAL INVESTIGATION REPORT

PROPOSED HOLY FACE OF JESUS CHURCH

SOUTH CENTRAL, POBLACION, NAMPICUAN,


NUEVA ECIJA

FR. RICHARD LAGOS

unified.geotest@gmail.com Unit C & D Ground Floor UB Building


0933-037-4628/ 0925-864-3433 (SUN) Brgy. Saguin, Mac Arthur Highway,
0917-175-3433/ 0917-307-4211 (GLOBE) City of San Fernando,
(045) 963-1644 Pampanga
GEOTECHNICAL EVALUATION REPORT FOR THE PROPOSED HOLY FACE OF JESUS CHURCH
SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
FR. RICHARD LAGOS

TABLE OF CONTENTS

1. INTRODUCTION 1
2. FIELD AND LABORATORY TESTS 1
2.1. In - Situ Tests 2
2.2. Laboratory Tests 2
3. SUBSURFACE SOIL CONDITION 5
4. GEOTECHNICAL PARAMETERS BASED ON TEST RESULTS 5
5. FINDINGS AND EVALUATION 6
5.1. Recommended Seismic Design Criteria 6
5.2. Shallow Foundation 6
5.3. Lateral Earth Pressure 7
5.4. Slab on Grade and Pavement Design 8
6. LIMITATIONS 8
7. REFERENCES 9

APPENDICES

● FINAL BORING LOG


● LABORATORY TEST RESULTS
● PICTURES
● BOREHOLE LOCATIONS PLAN
● GEOTECHNICAL ENGINEER'S PTR
GEOTECHNICAL EVALUATION REPORT
FOR THE PROPOSED HOLY FACE OF JESUS
CHURCH BUILDING

SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA

FR. RICHARD LAGOS


Geotechnical Evaluation Report for The Proposed Holy Face of Jesus Church Building
FR. RICHARD LAGOS

Table of Contents

1.  INTRODUCTION ............................................................................................................. 1 


2.  FIELD AND LABORATORY TESTS ............................................................................... 1 
2.1.  In – Situ Tests ............................................................................................................. 2 
2.2.  Laboratory Tests ........................................................................................................ 2 
3.  SUBSURFACE SOIL CONDITION ................................................................................. 5 
4.  GEOTECHNICAL PARAMETERS BASED ON TEST RESULTS .................................. 5 
5.  FINDINGS AND EVALUATION ...................................................................................... 6 
5.1.  Recommended Seismic Design Criteria .................................................................. 6 
5.2.  Shallow Foundation ................................................................................................... 6 
5.3.  Lateral Earth Pressure ............................................................................................... 7 
5.4.  Slab on Grade and Pavement Design ...................................................................... 8 
6.  LIMITATIONS .................................................................................................................. 8 
7.  REFERENCES ................................................................................................................ 9 

jbmamburam Page | 0
Geotechnical Evaluation Report for The Proposed Holy Face of Jesus Church Building
FR. RICHARD LAGOS

1. INTRODUCTION

This assessment of geotechnical conditions for The Proposed Holy Face of Jesus
Church Building at South Central, Poblacion, Nampicuan, Nueva Ecija site was
based on the findings gathered from the field and laboratory test conducted by Unified
Geotest Laboratory.

The geotechnical investigation consisted of drilling two (2) boreholes within the project
site and is shown in Table 1.1

Borehole Boring Depth Water Level Below


Structure
Number (m) Ground (m)
1
Church Building 15.0 10.0
2
Table 1.1 Summary of Borehole Location

In this report are soil properties & strength parameters, seismic design criteria of the
site, allowable bearing capacity for shallow foundation, lateral earth pressure
coefficient, and among other geotechnical information.

2. FIELD AND LABORATORY TESTS

For soil – type materials, Standard Penetration Test (SPT) are perform at regular
interval and disturbed soil samples are then retrieved after the test. Upon encountering
rock – type formation, coring will then be employ to penetrate through the hard strata
and extract rock samples.

All recovered soil and/or rock samples are taken to the soil laboratory for various
laboratory tests conforming to ASTM standards.

jbmamburam Page | 1
Geotechnical Evaluation Report for The Proposed Holy Face of Jesus Church Building
FR. RICHARD LAGOS

2.1. In – Situ Tests

Standard Test Method for Standard Penetration Test (SPT) and Split-Barrel Sampling
of Soils (ASTM D 1586)
This test method describes the procedure, generally known as the Standard
Penetration Test (SPT), for driving a split-barrel sampler to obtain a representative soil
sample and a measure of the resistance of the soil to penetration of the sampler.

The SPT is perform by driving a standard split spoon sampler into the ground by blows
from a drop hammer of mass 63.5 kg falling 760 mm (Figure 3.7). The sampler is driven
152 mm (6 in.) into the soil at the bottom of a borehole, and the number of blows (N)
required to drive it an additional 304 mm is counted. The number of blows (N) is called
the standard penetration number.

Standard Practice for Rock Core Drilling and Sampling of Rock for Site
Investigation (ASTM D 2113)
Rock cores are samples of record of the existing subsurface conditions at given
borehole locations. The samples was expected to yield significant indications about
the geological, physical, and engineering nature of the subsurface for use in the design
and construction of an engineered structure.

2.2. Laboratory Tests

Retrieved soil or cored samples at every interval are subject to the following laboratory
tests in conformance with the procedures given in the current ASTM standards as
described below:

Standard Test Method for Particle – Size Analysis of Soil (ASTM D 422)
This test method covers the quantitative determination of the distribution of particle
sizes in soils. The distribution of particle sizes larger than 75 μm (retained on the No.
200 sieve) is determined by sieving.

jbmamburam Page | 2
Geotechnical Evaluation Report for The Proposed Holy Face of Jesus Church Building
FR. RICHARD LAGOS

Standard Test Methods for Laboratory Determination of Water (Moisture) Content of


Soil and Rock by Mass (ASTM D 2216)
These test methods cover the laboratory determination of the water (moisture) content
by mass of soil, rock, and similar materials where the reduction in mass by drying is
due to loss of water except as noted in 1.4, 1.5, and 1.7 of ASTM D 2216.

Standard Test Methods for Liquid Limit, Plastic Limit, and Plasticity Index of Soils
(ASTM D 4318)
These test methods cover the determination of the liquid limit, plastic limit, and the
plasticity index of soils as defined in below.

Liquid Limit
The water content, in percent, of a soil at the arbitrarily defined boundary between the
semiliquid and plastic states.

Plastic Limit
The water content, in percent, of a soil at the boundary between the plastic and semi-
solid states.

Plasticity Index
The range of water content over which a soil behaves plastically. Numerically, it is the
difference between the liquid limit and the plastic limit.

Standard Practice for Classification of Soils for Engineering Purposes (Unified Soil
Classification System) (ASTM D 2487)
This practice describes a system for classifying mineral and organo-mineral soils for
engineering purposes based on laboratory determination of particle-size
characteristics, liquid limit, and plasticity index and shall be used when precise
classification is required.

Standard Test Method for Determining Rock Quality Designation (RQD) of Rock Core
(ASTM D 6032)
This test method covers the determination of the rock quality designation (RQD) as a
standard parameter in drill core logging.

jbmamburam Page | 3
Geotechnical Evaluation Report for The Proposed Holy Face of Jesus Church Building
FR. RICHARD LAGOS

The RQD denotes the percentage of intact and sound rock retrieved from a borehole
of any orientation. All pieces of intact and sound rock core equal to or greater than 100
mm (4 in.) long are summed and divided by the total length of the core run.

Σ length of intact and sound pieces 100 mm 4 in. 100 %


RQD
total core run length, mm

Rock Quality Classification of


Designation (RQD) Rock Quality
0 – 25 % Very Poor
25 – 50 % Poor
50 – 75 % Fair
75 – 90 % Good
90 – 100 % Excellent
Table 2.2.1 Classification of Rock Quality

Standard Test Method for Unconfined Compressive Strength of Intact Rock Core
Specimens (ASTM D 2938)
A rock core sample is cut to length and the ends are machined flat. The specimen is
placed in a loading frame and, if required, heated to the desired test temperature. Axial
load is continuously increased on the specimen until peak load and failure are
obtained.

Unconfined compressive strength of rock is used in many design formulas and is


sometimes used as an index property to select the appropriate excavation technique.

It should be noted that no UCS were performed for rock samples which did not pass
the requirement as test specimen, e.g. not intact sample to fulfill the specified
dimensioning.

jbmamburam Page | 4
Geotechnical Evaluation Report for The Proposed Holy Face of Jesus Church Building
FR. RICHARD LAGOS

3. SUBSURFACE SOIL CONDITION

The result of site specific geotechnical investigation suggests that the idealized
ground stratigraphy as shown in Table 3.1

Stratum Depth (m) Description


1 0.0 – 4.5 Medium Stiff Sandy Silt with Low Plasticity
2 4.5 – 9.0 Stiff Sandy Silt with Low Plasticity
3 9.0 – 10.5 Very Stiff Sandy Silt with Low Plasticity
4 10.5 – 15.0 Hard Sandy Silt with Low Plasticity
Table 3.1 Idealized Ground Stratigraphy for BH-1 to BH-2

Ground Water Table (GWT) was encountered at 10.0 meters below the top of the
boreholes.

4. GEOTECHNICAL PARAMETERS BASED ON TEST RESULTS

The SPT N-value are correlated to various properties and parameters of soil like; unit
weight (γwet & γsat), relative density & consistency, angle of internal friction (φ`),
undrained compressive strength (qu; c = ), and modulus of subgrade reaction (ks).

SPT N-value of cohesionless soils are correlated using Peck, Hanson, and Thornburn
to determine its internal angle of friction, while for cohesive soils correlation were made
using Terzaghi and Peck to determine the undrained cohesion. Other properties of
soils were correlated to commonly used correlations in the literature.

Values are summarized in Table 4.1.

γwet γsat φ` c ks
Stratum Depth (m) 3 3
(kN/m ) (kN/m ) (deg) (kPa) (MPa/m)
1 0.0 – 4.5 14 - - 25 3/B
2 4.5 – 9.0 16 - - 60 8/B
3 9.0 – 10.5 17 19 - 110 15/B
4 10.5 – 15.0 - 20 - 170 25/B
Table 4.1 Summary of Geotechnical Properties and Parameters for BH-1 to BH-2

jbmamburam Page | 5
Geotechnical Evaluation Report for The Proposed Holy Face of Jesus Church Building
FR. RICHARD LAGOS

For elastic deformation analysis, the Poisson’s Ratio µ=0.10 can be conservatively
used in the design.

5. FINDINGS AND EVALUATION

5.1. Recommended Seismic Design Criteria

Based on National Structural Code of the Philippines (NSCP 2015) 7th edition, the soil
underneath the project site can be classified as shown in Table 5.1.1. The Philippine
archipelago is located in a seismically active region. Thus, most of the country, except
for Palawan, can be classified as under Seismic Zone IV (Z=0.4).

Parameters Value
Soil Profile Type SD
Seismic Zone 4
Seismic Source Type A
Table 5.1.1 Recommended Seismic Design Parameters

The nearest seismic source that may directly affect the project site is Care Fault and
is approximately 29 kilometers from the site. Other seismic design parameters should
be obtained by the design engineer.

5.2. Shallow Foundation

A foundation is a structure that is built to transfer the weight and loads of the structure
to the material below. This transfer must occur such that the soil below does not
experience bearing capacity failure and/or excessive settlement to such magnitude
that the integrity of the superstructure is compromise.

The net allowable bearing capacity for shallow foundation with embedment depth (D)
to foundation least dimension (B) ratio of D/B ≤ 2.5 was calculated using Meyerhof’s
Bearing Capacity Method with a Factor of Safety of FS = 3.0.

jbmamburam Page | 6
Geotechnical Evaluation Report for The Proposed Holy Face of Jesus Church Building
FR. RICHARD LAGOS

The magnitude of elastic settlement (ρe) for shallow foundation is calculated using P.
W. Mayne & H.G. Poulos Method which approximates the displacement influence
factors by simple numerical integration of elastic stress distribution.

The net allowable bearing capacity for Spread Footing with B ≤ 2.5 meters and
ρe ≤ 25 millimeters are shown in Table 5.2.1.

Embedment Net Allowable Bearing


Depth (m) Capacity (kPa)
0.5 – 2.0 40
2.0 – 2.5 45
2.5 – 3.0 50
3.0 – 3.5 70
Table 5.2.1 Net Allowable Bearing Capacity of Spread Footing for BH-1 to BH-2
(isolated, combined, and strip footing)

It is recommended to integrate footing tie beams in the design of foundations to prevent


differential settlement.

5.3. Lateral Earth Pressure

The Coefficient of Lateral Earth Pressure (Ko, Ka and Kp) was calculated based on the
drainage characteristics of the soil. The calculated coefficients assumes a level
ground, vertical back-faced wall and the friction angle between wall and soil (δ)
δ=0.33φ.

Coefficient of Lateral Earth Pressure


Depth (m)
At Rest (K0) Active (Ka) Passive (Kp)
0.0 – 3.5 0.75 0.60 1.23
Table 5.3.1 Coefficient of Lateral Earth Pressure for BH-1 to BH-2

For cast-in-place walls, passive pressure may be neglected due to disturbance of soil
during foundation excavation. Calculated active pressure should be increased by 20%
to account for additional compaction stress during construction. At rest lateral earth

jbmamburam Page | 7
Geotechnical Evaluation Report for The Proposed Holy Face of Jesus Church Building
FR. RICHARD LAGOS

pressure coefficient (Ko) should be used when structures adjacent to the wall are
sensitive to lateral displacement.

Internal Drainage System under and behind the retaining wall should be provide to
ensure that there will be no buildup of pore water pressure and water will be drain off.

5.4. Slab on Grade and Pavement Design

Subbase or subgrade soils beneath the slab on grade and pavement should be free
from organic and unsuitable materials. It should be compacted in lift (at most 300mm)
to a minimum of 95% of MDD (Maximum Dry Density). Other necessary specifications
should conform to DPWH Manual of Standard Specification (Vol. II Highways, Bridges
and Airports, 2004).

6. LIMITATIONS

This report is based on the subsurface investigation carried out by Unified Geotest
Laboratory. Should there be any differences in the soil stratifications encountered
during the construction phase, or any differences in the understanding of the
requirements of the project, the undersigned should be reached at
jbmamburam@yahoo.com so that additional recommendations and/or corrections
can be made.

JONATHAN MAMBURAM, MSCE


Civil Engineer - Geotechnical
PRC 0107781

jbmamburam Page | 8
Geotechnical Evaluation Report for The Proposed Holy Face of Jesus Church Building
FR. RICHARD LAGOS

7. REFERENCES

American Society for Testing and Materials International (ASTM).

Association of Structural Engineers of the Philippines (2015), National Structural Code


of the Philippines (NSCP) Volume I 7th Edition.

Department of Public Works and Highways (2004), Standard Specifications for


Highways, Bridges and Airports Volume II.

http://faultfinder.phivolcs.dost.gov.ph/

Kulhawy, F. H. and Mayne, P. W. (1990), Manual on Estimating Soil Properties for


Foundation Design, Cornell University

Bowles, J.E. (1997), Foundation Analysis and Design, 5th ed., The McGraw-Hill
Companies Inc.

Mayne, P.W. and Poulos, H.G. (1999), Approximate Displacement Influence Factors
for Elastic Shallow Foundations.

jbmamburam Page | 9
Client Name: FR. RICHARD LAGOS
Project Title: PROPOSED HOLY FACE OF JESUS CHURCH
Location: SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA

FINAL BORING LOG


FINAL DEPTH: 15.00 m TEST REPORT NO.: UNI-SB-2107-996
GROUND WATER ELEV.: 10.00 m DATE STARTED: July 10, 2021
BOREHOLE: HOLE # 1 DATE FINISHED: July 11, 2021
WEATHER: Sunny Day DRILLED BY: Joefer Manalo/ Driller

DEPTH SAMPLING TYPE OF SAMPLE RECOVERY SPT BLOWS PER GROUP


RQD % N - VALUE CONSISTENCY SOIL DESCRIPTION REMARKS
(m) DEPTH SAMPLING Number (m) 15 cm CLASSIFICATION

0.00

Brown, Sandy SILT, slightly


WASH S-1 FIRM ML
1.05 BORING
plasticity
1.50 1.50 SPT 0.35 - 3 3 3 6

Brown, Sandy SILT, slightly


WASH S-2 FIRM ML
2.55 BORING
plasticity
3.00 3.00 SPT 0.35 - 3 3 3 6

Brown, Sandy SILT, slightly


WASH S-3 STIFF ML
4.05 BORING
plasticity
4.50 4.50 SPT 0.35 - 5 6 6 12

Brown, Sandy SILT, slightly


WASH S-4 STIFF ML
5.55 BORING
plasticity
6.00 6.00 SPT 0.35 - 6 7 7 14

WASH S-5 STIFF ML Gray, Sandy SILT, slightly plasticity


7.05 BORING
7.50 7.50 SPT 0.35 - 6 7 6 13

WASH S-6 VERY STIFF ML Gray, Sandy SILT, slightly plasticity


8.55 BORING
9.00 9.00 SPT 0.35 - 7 9 9 18

Dark Gray, Sandy SILT, slightly


WASH S-7 HARD ML
10.05 BORING
plasticity
10.50 10.50 SPT 0.35 - 15 14 19 33

Dark Gray, Sandy SILT, slightly


WASH S-8 HARD ML
11.55 BORING
plasticity
12.00 12.00 SPT 0.35 - 26 27 27 54

Brown, Sandy SILT, slightly


WASH S-9 HARD ML
13.05 BORING
plasticity
13.50 13.50 SPT 0.35 - 27 28 26 54

Brown, Sandy SILT, slightly


WASH S-10 HARD ML
14.55 BORING
plasticity
15.00 15.00 SPT 0.35 - 27 37 40 77

LEGEND:
STANDARD PENETRATION TEST UNDISTURBED SAMPLING

CORING GROUND WATER ELEV.

Geotest Laboratory DPWH-BRS


Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp. Accredited Laboratory
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE)
Email add.: unified.geotest@gmail.com
Project Title : PROPOSED HOLY FACE OF JESUS CHURCH
Location : SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
Client Name : FR. RICHARD LAGOS

TEST REPORT ON SIEVE ANALYSIS


ASTM D-422
Kind of Sample : Soil ( Hole 1 , Sample 1 ) Test Report No. : UNI-SB-2107-996
Sampled at : Jobsite Date Received : July 14, 2021
Sampled by : Joefer Manalo/ Driller Date Tested : July 14, 2021
Date Drilled : July 10, 2021 Tested by : R. Castillo

Spec's Item No. : Original Weight, gm. 280


Fineness Modulus : Oven Dry Weight, gm. 214
Natural Moisture Content : 30.84 Washed Oven dry Weight, gm. 55

Cumulative
Sieve Size
Wt. Retained, gm Specification
Wt. passing, gm. % Retained % Passing
In. / No. mm
1 1/2" 37.5 0.0 214 0.00 100.00
1" 25 0.0 214 0.00 100.00
3/4" 19 0.0 214 0.00 100.00
1/2" 12.5 0.0 214 0.00 100.00
3/8" 9.5 0.0 214 0.00 100.00
#4 4.75 2.0 212 0.93 99.07
#10 2 1.0 211 1.40 98.60
#40 0.425 27.0 184 14.02 85.98
#200 0.075 25.0 159 25.70 74.30
PAN 0.0
WASH LOSS 159.0
TOTAL 214.0
U.S. STANDARD SIEVE SIZE
100.00
P
90.00
E
R 80.00
C 70.00
E 60.00
N 50.00
T 40.00
F 30.00
I
20.00
N
10.00
E
R 0.00
1000.0 100.0 10.0 1.0 0.1 0.0 0.0
GRAIN SIZE IN MILLIMETERS

Sieve Size Liquid Limit 49.22


% Passing
No. mm Plastic Limit 32.40
4 4.75 99.07 Plasticity Index 16.82
10 2 98.60 Group Symbols ML
40 0.425 85.98 Soil Description Sandy SILT
200 0.075 74.30

REMARKS: Test report are based on sample taken from site.

Geotest Laboratory
Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp. DPWH-BRS
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE) Accredited Laboratory
Email add.: unified.geotest@gmail.com
Project Title : PROPOSED HOLY FACE OF JESUS CHURCH
Location : SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
Client Name : FR. RICHARD LAGOS

TEST REPORT ON SIEVE ANALYSIS


ASTM D-422
Kind of Sample : Soil ( Hole 1 , Sample 2 ) Test Report No. : UNI-SB-2107-996
Sampled at : Jobsite Date Received : July 14, 2021
Sampled by : Joefer Manalo/ Driller Date Tested : July 14, 2021
Date Drilled : July 10, 2021 Tested by : R. Castillo

Spec's Item No. : Original Weight, gm. 253


Fineness Modulus : Oven Dry Weight, gm. 200
Natural Moisture Content : 26.50 Washed Oven dry Weight, gm. 85

Cumulative
Sieve Size
Wt. Retained, gm Specification
Wt. passing, gm. % Retained % Passing
In. / No. mm
1 1/2" 37.5 0.0 200 0.00 100.00
1" 25 0.0 200 0.00 100.00
3/4" 19 21.0 179 10.50 89.50
1/2" 12.5 0.0 179 10.50 89.50
3/8" 9.5 0.0 179 10.50 89.50
#4 4.75 0.0 179 10.50 89.50
#10 2 2.0 177 11.50 88.50
#40 0.425 3.0 174 13.00 87.00
#200 0.075 59.0 115 42.50 57.50
PAN 0.0
WASH LOSS 115.0
TOTAL 200.0
U.S. STANDARD SIEVE SIZE
100.00
P
90.00
E
R 80.00
C 70.00
E 60.00
N 50.00
T 40.00
F 30.00
I
20.00
N
10.00
E
R 0.00
1000.0 100.0 10.0 1.0 0.1 0.0 0.0
GRAIN SIZE IN MILLIMETERS

Sieve Size Liquid Limit 48.97


% Passing
No. mm Plastic Limit 33.33
4 4.75 89.50 Plasticity Index 15.64
10 2 88.50 Group Symbols ML
40 0.425 87.00 Soil Description Sandy SILT
200 0.075 57.50

REMARKS: Test report are based on sample taken from site.

Geotest Laboratory
Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp. DPWH-BRS
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE) Accredited Laboratory
Email add.: unified.geotest@gmail.com
Project Title : PROPOSED HOLY FACE OF JESUS CHURCH
Location : SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
Client Name : FR. RICHARD LAGOS

TEST REPORT ON SIEVE ANALYSIS


ASTM D-422
Kind of Sample : Soil ( Hole 1 , Sample 3 ) Test Report No. : UNI-SB-2107-996
Sampled at : Jobsite Date Received : July 14, 2021
Sampled by : Joefer Manalo/ Driller Date Tested : July 14, 2021
Date Drilled : July 10, 2021 Tested by : R. Castillo

Spec's Item No. : Original Weight, gm. 221


Fineness Modulus : Oven Dry Weight, gm. 179
Natural Moisture Content : 23.46 Washed Oven dry Weight, gm. 20

Cumulative
Sieve Size
Wt. Retained, gm Specification
Wt. passing, gm. % Retained % Passing
In. / No. mm
1 1/2" 37.5 0.0 179 0.00 100.00
1" 25 0.0 179 0.00 100.00
3/4" 19 15.0 164 8.38 91.62
1/2" 12.5 0.0 164 8.38 91.62
3/8" 9.5 0.0 164 8.38 91.62
#4 4.75 0.0 164 8.38 91.62
#10 2 2.0 162 9.50 90.50
#40 0.425 2.0 160 10.61 89.39
#200 0.075 1.0 159 11.17 88.83
PAN 0.0
WASH LOSS 159.0
TOTAL 179.0
U.S. STANDARD SIEVE SIZE
100.00
P
90.00
E
R 80.00
C 70.00
E 60.00
N 50.00
T 40.00
F 30.00
I
20.00
N
10.00
E
R 0.00
1000.0 100.0 10.0 1.0 0.1 0.0 0.0
GRAIN SIZE IN MILLIMETERS

Sieve Size Liquid Limit 49.10


% Passing
No. mm Plastic Limit 32.81
4 4.75 91.62 Plasticity Index 16.29
10 2 90.50 Group Symbols ML
40 0.425 89.39 Soil Description Sandy SILT
200 0.075 88.83

REMARKS: Test report are based on sample taken from site.

Geotest Laboratory
DPWH-BRS
Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp.
Accredited Laboratory
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE)
Email add.: unified.geotest@gmail.com
Project Title : PROPOSED HOLY FACE OF JESUS CHURCH
Location : SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
Client Name : FR. RICHARD LAGOS

TEST REPORT ON SIEVE ANALYSIS


ASTM D-422
Kind of Sample : Soil ( Hole 1 , Sample 4 ) Test Report No. : UNI-SB-2107-996
Sampled at : Jobsite Date Received : July 14, 2021
Sampled by : Joefer Manalo/ Driller Date Tested : July 14, 2021
Date Drilled : July 10, 2021 Tested by : R. Castillo

Spec's Item No. : Original Weight, gm. 195


Fineness Modulus : Oven Dry Weight, gm. 152
Natural Moisture Content : 28.29 Washed Oven dry Weight, gm. 4

Cumulative
Sieve Size
Wt. Retained, gm Specification
Wt. passing, gm. % Retained % Passing
In. / No. mm
1 1/2" 37.5 0.0 152 0.00 100.00
1" 25 0.0 152 0.00 100.00
3/4" 19 0.0 152 0.00 100.00
1/2" 12.5 0.0 152 0.00 100.00
3/8" 9.5 0.0 152 0.00 100.00
#4 4.75 1.0 151 0.66 99.34
#10 2 0.0 151 0.66 99.34
#40 0.425 1.0 150 1.32 98.68
#200 0.075 2.0 148 2.63 97.37
PAN 0.0
WASH LOSS 148.0
TOTAL 152.0
U.S. STANDARD SIEVE SIZE
100.00
P
90.00
E
R 80.00
C 70.00
E 60.00
N 50.00
T 40.00
F 30.00
I
20.00
N
10.00
E
R 0.00
1000.0 100.0 10.0 1.0 0.1 0.0 0.0
GRAIN SIZE IN MILLIMETERS

Sieve Size Liquid Limit 49.58


% Passing
No. mm Plastic Limit 33.10
4 4.75 99.34 Plasticity Index 16.48
10 2 99.34 Group Symbols ML
40 0.425 98.68 Soil Description Sandy SILT
200 0.075 97.37

REMARKS: Test report are based on sample taken from site.

Geotest Laboratory
DPWH-BRS
Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp.
Accredited Laboratory
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE)
Email add.: unified.geotest@gmail.com
Project Title : PROPOSED HOLY FACE OF JESUS CHURCH
Location : SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
Client Name : FR. RICHARD LAGOS

TEST REPORT ON SIEVE ANALYSIS


ASTM D-422
Kind of Sample : Soil ( Hole 1 , Sample 5 ) Test Report No. : UNI-SB-2107-996
Sampled at : Jobsite Date Received : July 14, 2021
Sampled by : Joefer Manalo/ Driller Date Tested : July 14, 2021
Date Drilled : July 10, 2021 Tested by : R. Castillo

Spec's Item No. : Original Weight, gm. 199


Fineness Modulus : Oven Dry Weight, gm. 153
Natural Moisture Content : 30.07 Washed Oven dry Weight, gm. 3

Cumulative
Sieve Size
Wt. Retained, gm Specification
Wt. passing, gm. % Retained % Passing
In. / No. mm
1 1/2" 37.5 0.0 153 0.00 100.00
1" 25 0.0 153 0.00 100.00
3/4" 19 0.0 153 0.00 100.00
1/2" 12.5 0.0 153 0.00 100.00
3/8" 9.5 0.0 153 0.00 100.00
#4 4.75 1.0 152 0.65 99.35
#10 2 0.0 152 0.65 99.35
#40 0.425 1.0 151 1.31 98.69
#200 0.075 1.0 150 1.96 98.04
PAN 0.0
WASH LOSS 150.0
TOTAL 153.0
U.S. STANDARD SIEVE SIZE
100.00
P
90.00
E
R 80.00
C 70.00
E 60.00
N 50.00
T 40.00
F 30.00
I
20.00
N
10.00
E
R 0.00
1000.0 100.0 10.0 1.0 0.1 0.0 0.0
GRAIN SIZE IN MILLIMETERS

Sieve Size Liquid Limit 49.31


% Passing
No. mm Plastic Limit 33.64
4 4.75 99.35 Plasticity Index 15.67
10 2 99.35 Group Symbols ML
40 0.425 98.69 Soil Description Sandy SILT
200 0.075 98.04

REMARKS: Test report are based on sample taken from site.

Geotest Laboratory
DPWH-BRS
Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp.
Accredited Laboratory
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE)
Email add.: unified.geotest@gmail.com
Project Title : PROPOSED HOLY FACE OF JESUS CHURCH
Location : SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
Client Name : FR. RICHARD LAGOS

TEST REPORT ON SIEVE ANALYSIS


ASTM D-422
Kind of Sample : Soil ( Hole 1 , Sample 6 ) Test Report No. : UNI-SB-2107-996
Sampled at : Jobsite Date Received : July 14, 2021
Sampled by : Joefer Manalo/ Driller Date Tested : July 14, 2021
Date Drilled : July 10, 2021 Tested by : R. Castillo

Spec's Item No. : Original Weight, gm. 184


Fineness Modulus : Oven Dry Weight, gm. 139
Natural Moisture Content : 32.37 Washed Oven dry Weight, gm. 4

Cumulative
Sieve Size
Wt. Retained, gm Specification
Wt. passing, gm. % Retained % Passing
In. / No. mm
1 1/2" 37.5 0.0 139 0.00 100.00
1" 25 0.0 139 0.00 100.00
3/4" 19 0.0 139 0.00 100.00
1/2" 12.5 3.0 136 2.16 97.84
3/8" 9.5 0.0 136 2.16 97.84
#4 4.75 0.0 136 2.16 97.84
#10 2 0.0 136 2.16 97.84
#40 0.425 0.0 136 2.16 97.84
#200 0.075 1.0 135 2.88 97.12
PAN 0.0
WASH LOSS 135.0
TOTAL 139.0
U.S. STANDARD SIEVE SIZE
100.00
P
90.00
E
R 80.00
C 70.00
E 60.00
N 50.00
T 40.00
F 30.00
I
20.00
N
10.00
E
R 0.00
1000.0 100.0 10.0 1.0 0.1 0.0 0.0
GRAIN SIZE IN MILLIMETERS

Sieve Size Liquid Limit 49.31


% Passing
No. mm Plastic Limit 33.29
4 4.75 97.84 Plasticity Index 16.02
10 2 97.84 Group Symbols ML
40 0.425 97.84 Soil Description Sandy SILT
200 0.075 97.12

REMARKS: Test report are based on sample taken from site.

Geotest Laboratory
DPWH-BRS
Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp.
Accredited Laboratory
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE)
Email add.: unified.geotest@gmail.com
Project Title : PROPOSED HOLY FACE OF JESUS CHURCH
Location : SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
Client Name : FR. RICHARD LAGOS

TEST REPORT ON SIEVE ANALYSIS


ASTM D-422
Kind of Sample : Soil ( Hole 1 , Sample 7 ) Test Report No. : UNI-SB-2107-996
Sampled at : Jobsite Date Received : July 14, 2021
Sampled by : Joefer Manalo/ Driller Date Tested : July 14, 2021
Date Drilled : July 10, 2021 Tested by : R. Castillo

Spec's Item No. : Original Weight, gm. 190


Fineness Modulus : Oven Dry Weight, gm. 145
Natural Moisture Content : 31.03 Washed Oven dry Weight, gm. 3

Cumulative
Sieve Size
Wt. Retained, gm Specification
Wt. passing, gm. % Retained % Passing
In. / No. mm
1 1/2" 37.5 0.0 145 0.00 100.00
1" 25 0.0 145 0.00 100.00
3/4" 19 0.0 145 0.00 100.00
1/2" 12.5 0.0 145 0.00 100.00
3/8" 9.5 0.0 145 0.00 100.00
#4 4.75 0.0 145 0.00 100.00
#10 2 2.0 143 1.38 98.62
#40 0.425 0.0 143 1.38 98.62
#200 0.075 1.0 142 2.07 97.93
PAN 0.0
WASH LOSS 142.0
TOTAL 145.0
U.S. STANDARD SIEVE SIZE
100.00
P
90.00
E
R 80.00
C 70.00
E 60.00
N 50.00
T 40.00
F 30.00
I
20.00
N
10.00
E
R 0.00
1000.0 100.0 10.0 1.0 0.1 0.0 0.0
GRAIN SIZE IN MILLIMETERS

Sieve Size Liquid Limit 49.25


% Passing
No. mm Plastic Limit 32.23
4 4.75 100.00 Plasticity Index 17.02
10 2 98.62 Group Symbols ML
40 0.425 98.62 Soil Description Sandy SILT
200 0.075 97.93

REMARKS: Test report are based on sample taken from site.

Geotest Laboratory
DPWH-BRS
Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp.
Accredited Laboratory
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE)
Email add.: unified.geotest@gmail.com
Project Title : PROPOSED HOLY FACE OF JESUS CHURCH
Location : SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
Client Name : FR. RICHARD LAGOS

TEST REPORT ON SIEVE ANALYSIS


ASTM D-422
Kind of Sample : Soil ( Hole 1 , Sample 8 ) Test Report No. : UNI-SB-2107-996
Sampled at : Jobsite Date Received : July 14, 2021
Sampled by : Joefer Manalo/ Driller Date Tested : July 14, 2021
Date Drilled : July 10, 2021 Tested by : R. Castillo

Spec's Item No. : Original Weight, gm. 178


Fineness Modulus : Oven Dry Weight, gm. 133
Natural Moisture Content : 33.83 Washed Oven dry Weight, gm. 3

Cumulative
Sieve Size
Wt. Retained, gm Specification
Wt. passing, gm. % Retained % Passing
In. / No. mm
1 1/2" 37.5 0.0 133 0.00 100.00
1" 25 0.0 133 0.00 100.00
3/4" 19 0.0 133 0.00 100.00
1/2" 12.5 0.0 133 0.00 100.00
3/8" 9.5 0.0 133 0.00 100.00
#4 4.75 0.0 133 0.00 100.00
#10 2 0.0 133 0.00 100.00
#40 0.425 1.0 132 0.75 99.25
#200 0.075 2.0 130 2.26 97.74
PAN 0.0
WASH LOSS 130.0
TOTAL 133.0
U.S. STANDARD SIEVE SIZE
100.00
P
90.00
E
R 80.00
C 70.00
E 60.00
N 50.00
T 40.00
F 30.00
I
20.00
N
10.00
E
R 0.00
1000.0 100.0 10.0 1.0 0.1 0.0 0.0
GRAIN SIZE IN MILLIMETERS

Sieve Size Liquid Limit 49.37


% Passing
No. mm Plastic Limit 33.15
4 4.75 100.00 Plasticity Index 16.22
10 2 100.00 Group Symbols ML
40 0.425 99.25 Soil Description Sandy SILT
200 0.075 97.74

REMARKS: Test report are based on sample taken from site.

Geotest Laboratory
DPWH-BRS
Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp.
Accredited Laboratory
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE)
Email add.: unified.geotest@gmail.com
Project Title : PROPOSED HOLY FACE OF JESUS CHURCH
Location : SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
Client Name : FR. RICHARD LAGOS

TEST REPORT ON SIEVE ANALYSIS


ASTM D-422
Kind of Sample : Soil ( Hole 1 , Sample 9 ) Test Report No. : UNI-SB-2107-996
Sampled at : Jobsite Date Received : July 14, 2021
Sampled by : Joefer Manalo/ Driller Date Tested : July 14, 2021
Date Drilled : July 10, 2021 Tested by : R. Castillo

Spec's Item No. : Original Weight, gm. 163


Fineness Modulus : Oven Dry Weight, gm. 126
Natural Moisture Content : 29.37 Washed Oven dry Weight, gm. 4

Cumulative
Sieve Size
Wt. Retained, gm Specification
Wt. passing, gm. % Retained % Passing
In. / No. mm
1 1/2" 37.5 0.0 126 0.00 100.00
1" 25 0.0 126 0.00 100.00
3/4" 19 0.0 126 0.00 100.00
1/2" 12.5 0.0 126 0.00 100.00
3/8" 9.5 2.0 124 1.59 98.41
#4 4.75 0.0 124 1.59 98.41
#10 2 0.0 124 1.59 98.41
#40 0.425 0.0 124 1.59 98.41
#200 0.075 2.0 122 3.17 96.83
PAN 0.0
WASH LOSS 122.0
TOTAL 126.0
U.S. STANDARD SIEVE SIZE
100.00
P
90.00
E
R 80.00
C 70.00
E 60.00
N 50.00
T 40.00
F 30.00
I
20.00
N
10.00
E
R 0.00
1000.0 100.0 10.0 1.0 0.1 0.0 0.0
GRAIN SIZE IN MILLIMETERS

Sieve Size Liquid Limit 49.25


% Passing
No. mm Plastic Limit 32.66
4 4.75 98.41 Plasticity Index 16.59
10 2 98.41 Group Symbols ML
40 0.425 98.41 Soil Description Sandy SILT
200 0.075 96.83

REMARKS: Test report are based on sample taken from site.

Geotest Laboratory
DPWH-BRS
Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp.
Accredited Laboratory
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE)
Email add.: unified.geotest@gmail.com
Project Title : PROPOSED HOLY FACE OF JESUS CHURCH
Location : SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
Client Name : FR. RICHARD LAGOS

TEST REPORT ON SIEVE ANALYSIS


ASTM D-422
Kind of Sample : Soil ( Hole 1 , Sample 10 ) Test Report No. : UNI-SB-2107-996
Sampled at : Jobsite Date Received : July 14, 2021
Sampled by : Joefer Manalo/ Driller Date Tested : July 14, 2021
Date Drilled : July 10, 2021 Tested by : R. Castillo

Spec's Item No. : Original Weight, gm. 226


Fineness Modulus : Oven Dry Weight, gm. 180
Natural Moisture Content : 25.56 Washed Oven dry Weight, gm. 6

Cumulative
Sieve Size
Wt. Retained, gm Specification
Wt. passing, gm. % Retained % Passing
In. / No. mm
1 1/2" 37.5 0.0 180 0.00 100.00
1" 25 0.0 180 0.00 100.00
3/4" 19 0.0 180 0.00 100.00
1/2" 12.5 0.0 180 0.00 100.00
3/8" 9.5 0.0 180 0.00 100.00
#4 4.75 0.0 180 0.00 100.00
#10 2 0.0 180 0.00 100.00
#40 0.425 0.0 180 0.00 100.00
#200 0.075 6.0 174 3.33 96.67
PAN 0.0
WASH LOSS 174.0
TOTAL 180.0
U.S. STANDARD SIEVE SIZE
100.00
P
90.00
E
R 80.00
C 70.00
E 60.00
N 50.00
T 40.00
F 30.00
I
20.00
N
10.00
E
R 0.00
1000.0 100.0 10.0 1.0 0.1 0.0 0.0
GRAIN SIZE IN MILLIMETERS

Sieve Size Liquid Limit 49.25


% Passing
No. mm Plastic Limit 33.56
4 4.75 100.00 Plasticity Index 15.69
10 2 100.00 Group Symbols ML
40 0.425 100.00 Soil Description Sandy SILT
200 0.075 96.67

REMARKS: Test report are based on sample taken from site.

Geotest Laboratory
DPWH-BRS
Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp.
Accredited Laboratory
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE)
Email add.: unified.geotest@gmail.com
Client Name: FR. RICHARD LAGOS
Project Title: PROPOSED HOLY FACE OF JESUS CHURCH
Location: SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA

FINAL BORING LOG


FINAL DEPTH: 15.00 m TEST REPORT NO.: UNI-SB-2107-996
GROUND WATER ELEV.: 10.00 m DATE STARTED: July 12, 2021
BOREHOLE: HOLE # 2 DATE FINISHED: July 12, 2021
WEATHER: Sunny Day DRILLED BY: Joefer Manalo/ Driller

DEPTH SAMPLING TYPE OF SAMPLE RECOVERY SPT BLOWS PER GROUP


RQD % N - VALUE CONSISTENCY SOIL DESCRIPTION REMARKS
(m) DEPTH SAMPLING Number (m) 15 cm CLASSIFICATION

0.00

Brown, Sandy SILT, slightly


WASH S-1 FIRM ML
1.05 BORING
plasticity
1.50 1.50 SPT 0.35 - 3 4 4 8

Brown, Sandy SILT, slightly


WASH S-2 FIRM ML
2.55 BORING
plasticity
3.00 3.00 SPT 0.35 - 4 4 4 8

Brown, Sandy SILT, slightly


WASH S-3 FIRM ML
4.05 BORING
plasticity
4.50 4.50 SPT 0.35 - 4 4 4 8

Brown, Sandy SILT, slightly


WASH S-4 VERY STIFF ML
5.55 BORING
plasticity
6.00 6.00 SPT 0.35 - 5 8 10 18

Brown, Sandy SILT, slightly


WASH S-5 STIFF ML
7.05 BORING
plasticity
7.50 7.50 SPT 0.35 - 7 8 7 15

WASH S-6 VERY STIFF ML Gray, Sandy SILT, slightly plasticity


8.55 BORING
9.00 9.00 SPT 0.35 - 9 10 10 20

Dark Gray, Sandy SILT, slightly


WASH S-7 HARD ML
10.05 BORING
plasticity
10.50 10.50 SPT 0.35 - 16 18 16 34

WASH S-8 HARD ML Gray, Sandy SILT, slightly plasticity


11.55 BORING
12.00 12.00 SPT 0.30 - 23 26 29 55

WASH S-9 HARD ML Gray, Sandy SILT, slightly plasticity


13.05 BORING
13.50 13.50 SPT 0.30 - 30 29 30 59

Light Gray, Sandy SILT, slightly


WASH S-10 HARD ML
14.55 BORING
plasticity
15.00 15.00 SPT 0.30 - 33 35 36 71

LEGEND:
STANDARD PENETRATION TEST UNDISTURBED SAMPLING

CORING GROUND WATER ELEV.

Geotest Laboratory DPWH-BRS


Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp. Accredited Laboratory
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE)
Email add.: unified.geotest@gmail.com
Project Title : PROPOSED HOLY FACE OF JESUS CHURCH
Location : SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
Client Name : FR. RICHARD LAGOS

TEST REPORT ON SIEVE ANALYSIS


ASTM D-422
Kind of Sample : Soil ( Hole 2 , Sample 1 ) Test Report No. : UNI-SB-2107-996
Sampled at : Jobsite Date Received : July 14, 2021
Sampled by : Joefer Manalo/ Driller Date Tested : July 14, 2021
Date Drilled : July 12, 2021 Tested by : R. Castillo

Spec's Item No. : Original Weight, gm. 277


Fineness Modulus : Oven Dry Weight, gm. 219
Natural Moisture Content : 26.48 Washed Oven dry Weight, gm. 71

Cumulative
Sieve Size
Wt. Retained, gm Specification
Wt. passing, gm. % Retained % Passing
In. / No. mm
1 1/2" 37.5 0.0 219 0.00 100.00
1" 25 0.0 219 0.00 100.00
3/4" 19 0.0 219 0.00 100.00
1/2" 12.5 0.0 219 0.00 100.00
3/8" 9.5 0.0 219 0.00 100.00
#4 4.75 0.0 219 0.00 100.00
#10 2 0.0 219 0.00 100.00
#40 0.425 1.0 218 0.46 99.54
#200 0.075 69.0 149 31.96 68.04
PAN 1.0
WASH LOSS 148.0
TOTAL 219.0
U.S. STANDARD SIEVE SIZE
100.00
P
90.00
E
R 80.00
C 70.00
E 60.00
N 50.00
T 40.00
F 30.00
I
20.00
N
10.00
E
R 0.00
1000.0 100.0 10.0 1.0 0.1 0.0 0.0
GRAIN SIZE IN MILLIMETERS

Sieve Size Liquid Limit 49.21


% Passing
No. mm Plastic Limit 31.97
4 4.75 100.00 Plasticity Index 17.24
10 2 100.00 Group Symbols ML
40 0.425 99.54 Soil Description Sandy SILT
200 0.075 68.04

REMARKS: Test report are based on sample taken from site.

Geotest Laboratory
Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp. DPWH-BRS
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE) Accredited Laboratory
Email add.: unified.geotest@gmail.com
Project Title : PROPOSED HOLY FACE OF JESUS CHURCH
Location : SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
Client Name : FR. RICHARD LAGOS

TEST REPORT ON SIEVE ANALYSIS


ASTM D-422
Kind of Sample : Soil ( Hole 2 , Sample 2 ) Test Report No. : UNI-SB-2107-996
Sampled at : Jobsite Date Received : July 14, 2021
Sampled by : Joefer Manalo/ Driller Date Tested : July 14, 2021
Date Drilled : July 12, 2021 Tested by : R. Castillo

Spec's Item No. : Original Weight, gm. 245


Fineness Modulus : Oven Dry Weight, gm. 197
Natural Moisture Content : 24.37 Washed Oven dry Weight, gm. 34

Cumulative
Sieve Size
Wt. Retained, gm Specification
Wt. passing, gm. % Retained % Passing
In. / No. mm
1 1/2" 37.5 0.0 197 0.00 100.00
1" 25 0.0 197 0.00 100.00
3/4" 19 0.0 197 0.00 100.00
1/2" 12.5 0.0 197 0.00 100.00
3/8" 9.5 0.0 197 0.00 100.00
#4 4.75 0.0 197 0.00 100.00
#10 2 0.0 197 0.00 100.00
#40 0.425 0.0 197 0.00 100.00
#200 0.075 34.0 163 17.26 82.74
PAN 0.0
WASH LOSS 163.0
TOTAL 197.0
U.S. STANDARD SIEVE SIZE
100.00
P
90.00
E
R 80.00
C 70.00
E 60.00
N 50.00
T 40.00
F 30.00
I
20.00
N
10.00
E
R 0.00
1000.0 100.0 10.0 1.0 0.1 0.0 0.0
GRAIN SIZE IN MILLIMETERS

Sieve Size Liquid Limit 49.67


% Passing
No. mm Plastic Limit 33.43
4 4.75 100.00 Plasticity Index 16.24
10 2 100.00 Group Symbols ML
40 0.425 100.00 Soil Description Sandy SILT
200 0.075 82.74

REMARKS: Test report are based on sample taken from site.

Geotest Laboratory
Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp. DPWH-BRS
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE) Accredited Laboratory
Email add.: unified.geotest@gmail.com
Project Title : PROPOSED HOLY FACE OF JESUS CHURCH
Location : SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
Client Name : FR. RICHARD LAGOS

TEST REPORT ON SIEVE ANALYSIS


ASTM D-422
Kind of Sample : Soil ( Hole 2 , Sample 3 ) Test Report No. : UNI-SB-2107-996
Sampled at : Jobsite Date Received : July 14, 2021
Sampled by : Joefer Manalo/ Driller Date Tested : July 14, 2021
Date Drilled : July 12, 2021 Tested by : R. Castillo

Spec's Item No. : Original Weight, gm. 266


Fineness Modulus : Oven Dry Weight, gm. 141
Natural Moisture Content : 88.65 Washed Oven dry Weight, gm. 4

Cumulative
Sieve Size
Wt. Retained, gm Specification
Wt. passing, gm. % Retained % Passing
In. / No. mm
1 1/2" 37.5 0.0 141 0.00 100.00
1" 25 0.0 141 0.00 100.00
3/4" 19 0.0 141 0.00 100.00
1/2" 12.5 0.0 141 0.00 100.00
3/8" 9.5 0.0 141 0.00 100.00
#4 4.75 0.0 141 0.00 100.00
#10 2 1.0 140 0.71 99.29
#40 0.425 1.0 139 1.42 98.58
#200 0.075 2.0 137 2.84 97.16
PAN 0.0
WASH LOSS 137.0
TOTAL 141.0
U.S. STANDARD SIEVE SIZE
100.00
P
90.00
E
R 80.00
C 70.00
E 60.00
N 50.00
T 40.00
F 30.00
I
20.00
N
10.00
E
R 0.00
1000.0 100.0 10.0 1.0 0.1 0.0 0.0
GRAIN SIZE IN MILLIMETERS

Sieve Size Liquid Limit 49.67


% Passing
No. mm Plastic Limit 33.09
4 4.75 100.00 Plasticity Index 16.58
10 2 99.29 Group Symbols ML
40 0.425 98.58 Soil Description Sandy SILT
200 0.075 97.16

REMARKS: Test report are based on sample taken from site.

Geotest Laboratory
DPWH-BRS
Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp.
Accredited Laboratory
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE)
Email add.: unified.geotest@gmail.com
Project Title : PROPOSED HOLY FACE OF JESUS CHURCH
Location : SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
Client Name : FR. RICHARD LAGOS

TEST REPORT ON SIEVE ANALYSIS


ASTM D-422
Kind of Sample : Soil ( Hole 2 , Sample 4 ) Test Report No. : UNI-SB-2107-996
Sampled at : Jobsite Date Received : July 14, 2021
Sampled by : Joefer Manalo/ Driller Date Tested : July 14, 2021
Date Drilled : July 12, 2021 Tested by : R. Castillo

Spec's Item No. : Original Weight, gm. 270


Fineness Modulus : Oven Dry Weight, gm. 214
Natural Moisture Content : 26.17 Washed Oven dry Weight, gm. 6

Cumulative
Sieve Size
Wt. Retained, gm Specification
Wt. passing, gm. % Retained % Passing
In. / No. mm
1 1/2" 37.5 0.0 214 0.00 100.00
1" 25 0.0 214 0.00 100.00
3/4" 19 0.0 214 0.00 100.00
1/2" 12.5 0.0 214 0.00 100.00
3/8" 9.5 0.0 214 0.00 100.00
#4 4.75 0.0 214 0.00 100.00
#10 2 2.0 212 0.93 99.07
#40 0.425 2.0 210 1.87 98.13
#200 0.075 2.0 208 2.80 97.20
PAN 0.0
WASH LOSS 208.0
TOTAL 214.0
U.S. STANDARD SIEVE SIZE
100.00
P
90.00
E
R 80.00
C 70.00
E 60.00
N 50.00
T 40.00
F 30.00
I
20.00
N
10.00
E
R 0.00
1000.0 100.0 10.0 1.0 0.1 0.0 0.0
GRAIN SIZE IN MILLIMETERS

Sieve Size Liquid Limit 49.25


% Passing
No. mm Plastic Limit 32.23
4 4.75 100.00 Plasticity Index 17.02
10 2 99.07 Group Symbols ML
40 0.425 98.13 Soil Description Sandy SILT
200 0.075 97.20

REMARKS: Test report are based on sample taken from site.

Geotest Laboratory
DPWH-BRS
Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp.
Accredited Laboratory
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE)
Email add.: unified.geotest@gmail.com
Project Title : PROPOSED HOLY FACE OF JESUS CHURCH
Location : SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
Client Name : FR. RICHARD LAGOS

TEST REPORT ON SIEVE ANALYSIS


ASTM D-422
Kind of Sample : Soil ( Hole 2 , Sample 5 ) Test Report No. : UNI-SB-2107-996
Sampled at : Jobsite Date Received : July 14, 2021
Sampled by : Joefer Manalo/ Driller Date Tested : July 14, 2021
Date Drilled : July 12, 2021 Tested by : R. Castillo

Spec's Item No. : Original Weight, gm. 198


Fineness Modulus : Oven Dry Weight, gm. 152
Natural Moisture Content : 30.26 Washed Oven dry Weight, gm. 5

Cumulative
Sieve Size
Wt. Retained, gm Specification
Wt. passing, gm. % Retained % Passing
In. / No. mm
1 1/2" 37.5 0.0 152 0.00 100.00
1" 25 0.0 152 0.00 100.00
3/4" 19 0.0 152 0.00 100.00
1/2" 12.5 0.0 152 0.00 100.00
3/8" 9.5 0.0 152 0.00 100.00
#4 4.75 0.0 152 0.00 100.00
#10 2 2.0 150 1.32 98.68
#40 0.425 0.0 150 1.32 98.68
#200 0.075 3.0 147 3.29 96.71
PAN 0.0
WASH LOSS 147.0
TOTAL 152.0
U.S. STANDARD SIEVE SIZE
100.00
P
90.00
E
R 80.00
C 70.00
E 60.00
N 50.00
T 40.00
F 30.00
I
20.00
N
10.00
E
R 0.00
1000.0 100.0 10.0 1.0 0.1 0.0 0.0
GRAIN SIZE IN MILLIMETERS

Sieve Size Liquid Limit 49.17


% Passing
No. mm Plastic Limit 32.93
4 4.75 100.00 Plasticity Index 16.24
10 2 98.68 Group Symbols ML
40 0.425 98.68 Soil Description Sandy SILT
200 0.075 96.71

REMARKS: Test report are based on sample taken from site.

Geotest Laboratory
DPWH-BRS
Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp.
Accredited Laboratory
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE)
Email add.: unified.geotest@gmail.com
Project Title : PROPOSED HOLY FACE OF JESUS CHURCH
Location : SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
Client Name : FR. RICHARD LAGOS

TEST REPORT ON SIEVE ANALYSIS


ASTM D-422
Kind of Sample : Soil ( Hole 2 , Sample 6 ) Test Report No. : UNI-SB-2107-996
Sampled at : Jobsite Date Received : July 14, 2021
Sampled by : Joefer Manalo/ Driller Date Tested : July 14, 2021
Date Drilled : July 12, 2021 Tested by : R. Castillo

Spec's Item No. : Original Weight, gm. 270


Fineness Modulus : Oven Dry Weight, gm. 212
Natural Moisture Content : 27.36 Washed Oven dry Weight, gm. 3

Cumulative
Sieve Size
Wt. Retained, gm Specification
Wt. passing, gm. % Retained % Passing
In. / No. mm
1 1/2" 37.5 0.0 212 0.00 100.00
1" 25 0.0 212 0.00 100.00
3/4" 19 0.0 212 0.00 100.00
1/2" 12.5 0.0 212 0.00 100.00
3/8" 9.5 1.0 211 0.47 99.53
#4 4.75 1.0 210 0.94 99.06
#10 2 0.0 210 0.94 99.06
#40 0.425 0.0 210 0.94 99.06
#200 0.075 1.0 209 1.42 98.58
PAN 0.0
WASH LOSS 209.0
TOTAL 212.0
U.S. STANDARD SIEVE SIZE
100.00
P
90.00
E
R 80.00
C 70.00
E 60.00
N 50.00
T 40.00
F 30.00
I
20.00
N
10.00
E
R 0.00
1000.0 100.0 10.0 1.0 0.1 0.0 0.0
GRAIN SIZE IN MILLIMETERS

Sieve Size Liquid Limit 49.65


% Passing
No. mm Plastic Limit 33.96
4 4.75 99.06 Plasticity Index 15.69
10 2 99.06 Group Symbols ML
40 0.425 99.06 Soil Description Sandy SILT
200 0.075 98.58

REMARKS: Test report are based on sample taken from site.

Geotest Laboratory
DPWH-BRS
Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp.
Accredited Laboratory
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE)
Email add.: unified.geotest@gmail.com
Project Title : PROPOSED HOLY FACE OF JESUS CHURCH
Location : SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
Client Name : FR. RICHARD LAGOS

TEST REPORT ON SIEVE ANALYSIS


ASTM D-422
Kind of Sample : Soil ( Hole 2 , Sample 7 ) Test Report No. : UNI-SB-2107-996
Sampled at : Jobsite Date Received : July 14, 2021
Sampled by : Joefer Manalo/ Driller Date Tested : July 14, 2021
Date Drilled : July 12, 2021 Tested by : R. Castillo

Spec's Item No. : Original Weight, gm. 217


Fineness Modulus : Oven Dry Weight, gm. 164
Natural Moisture Content : 32.32 Washed Oven dry Weight, gm. 1

Cumulative
Sieve Size
Wt. Retained, gm Specification
Wt. passing, gm. % Retained % Passing
In. / No. mm
1 1/2" 37.5 0.0 164 0.00 100.00
1" 25 0.0 164 0.00 100.00
3/4" 19 0.0 164 0.00 100.00
1/2" 12.5 0.0 164 0.00 100.00
3/8" 9.5 0.0 164 0.00 100.00
#4 4.75 0.0 164 0.00 100.00
#10 2 0.0 164 0.00 100.00
#40 0.425 0.0 164 0.00 100.00
#200 0.075 1.0 163 0.61 99.39
PAN 0.0
WASH LOSS 163.0
TOTAL 164.0
U.S. STANDARD SIEVE SIZE
100.00
P
90.00
E
R 80.00
C 70.00
E 60.00
N 50.00
T 40.00
F 30.00
I
20.00
N
10.00
E
R 0.00
1000.0 100.0 10.0 1.0 0.1 0.0 0.0
GRAIN SIZE IN MILLIMETERS

Sieve Size Liquid Limit 49.66


% Passing
No. mm Plastic Limit 33.37
4 4.75 100.00 Plasticity Index 16.29
10 2 100.00 Group Symbols ML
40 0.425 100.00 Soil Description Sandy SILT
200 0.075 99.39

REMARKS: Test report are based on sample taken from site.

Geotest Laboratory
DPWH-BRS
Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp.
Accredited Laboratory
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE)
Email add.: unified.geotest@gmail.com
Project Title : PROPOSED HOLY FACE OF JESUS CHURCH
Location : SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
Client Name : FR. RICHARD LAGOS

TEST REPORT ON SIEVE ANALYSIS


ASTM D-422
Kind of Sample : Soil ( Hole 2 , Sample 8 ) Test Report No. : UNI-SB-2107-996
Sampled at : Jobsite Date Received : July 14, 2021
Sampled by : Joefer Manalo/ Driller Date Tested : July 14, 2021
Date Drilled : July 12, 2021 Tested by : R. Castillo

Spec's Item No. : Original Weight, gm. 235


Fineness Modulus : Oven Dry Weight, gm. 186
Natural Moisture Content : 26.34 Washed Oven dry Weight, gm. 11

Cumulative
Sieve Size
Wt. Retained, gm Specification
Wt. passing, gm. % Retained % Passing
In. / No. mm
1 1/2" 37.5 0.0 186 0.00 100.00
1" 25 0.0 186 0.00 100.00
3/4" 19 0.0 186 0.00 100.00
1/2" 12.5 5.0 181 2.69 97.31
3/8" 9.5 0.0 181 2.69 97.31
#4 4.75 0.0 181 2.69 97.31
#10 2 1.0 180 3.23 96.77
#40 0.425 2.0 178 4.30 95.70
#200 0.075 3.0 175 5.91 94.09
PAN 0.0
WASH LOSS 175.0
TOTAL 186.0
U.S. STANDARD SIEVE SIZE
100.00
P
90.00
E
R 80.00
C 70.00
E 60.00
N 50.00
T 40.00
F 30.00
I
20.00
N
10.00
E
R 0.00
1000.0 100.0 10.0 1.0 0.1 0.0 0.0
GRAIN SIZE IN MILLIMETERS

Sieve Size Liquid Limit 49.29


% Passing
No. mm Plastic Limit 33.62
4 4.75 97.31 Plasticity Index 15.67
10 2 96.77 Group Symbols ML
40 0.425 95.70 Soil Description Sandy SILT
200 0.075 94.09

REMARKS: Test report are based on sample taken from site.

Geotest Laboratory
DPWH-BRS
Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp.
Accredited Laboratory
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE)
Email add.: unified.geotest@gmail.com
Project Title : PROPOSED HOLY FACE OF JESUS CHURCH
Location : SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
Client Name : FR. RICHARD LAGOS

TEST REPORT ON SIEVE ANALYSIS


ASTM D-422
Kind of Sample : Soil ( Hole 2 , Sample 9 ) Test Report No. : UNI-SB-2107-996
Sampled at : Jobsite Date Received : July 14, 2021
Sampled by : Joefer Manalo/ Driller Date Tested : July 14, 2021
Date Drilled : July 12, 2021 Tested by : R. Castillo

Spec's Item No. : Original Weight, gm. 279


Fineness Modulus : Oven Dry Weight, gm. 210
Natural Moisture Content : 32.86 Washed Oven dry Weight, gm. 1

Cumulative
Sieve Size
Wt. Retained, gm Specification
Wt. passing, gm. % Retained % Passing
In. / No. mm
1 1/2" 37.5 0.0 210 0.00 100.00
1" 25 0.0 210 0.00 100.00
3/4" 19 0.0 210 0.00 100.00
1/2" 12.5 0.0 210 0.00 100.00
3/8" 9.5 0.0 210 0.00 100.00
#4 4.75 0.0 210 0.00 100.00
#10 2 0.0 210 0.00 100.00
#40 0.425 0.0 210 0.00 100.00
#200 0.075 1.0 209 0.48 99.52
PAN 0.0
WASH LOSS 209.0
TOTAL 210.0
U.S. STANDARD SIEVE SIZE
100.00
P
90.00
E
R 80.00
C 70.00
E 60.00
N 50.00
T 40.00
F 30.00
I
20.00
N
10.00
E
R 0.00
1000.0 100.0 10.0 1.0 0.1 0.0 0.0
GRAIN SIZE IN MILLIMETERS

Sieve Size Liquid Limit 49.57


% Passing
No. mm Plastic Limit 33.20
4 4.75 100.00 Plasticity Index 16.37
10 2 100.00 Group Symbols ML
40 0.425 100.00 Soil Description Sandy SILT
200 0.075 99.52

REMARKS: Test report are based on sample taken from site.

Geotest Laboratory
DPWH-BRS
Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp.
Accredited Laboratory
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE)
Email add.: unified.geotest@gmail.com
Project Title : PROPOSED HOLY FACE OF JESUS CHURCH
Location : SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
Client Name : FR. RICHARD LAGOS

TEST REPORT ON SIEVE ANALYSIS


ASTM D-422
Kind of Sample : Soil ( Hole 2 , Sample 10 ) Test Report No. : UNI-SB-2107-996
Sampled at : Jobsite Date Received : July 14, 2021
Sampled by : Joefer Manalo/ Driller Date Tested : July 14, 2021
Date Drilled : July 12, 2021 Tested by : R. Castillo

Spec's Item No. : Original Weight, gm. 199


Fineness Modulus : Oven Dry Weight, gm. 164
Natural Moisture Content : 21.34 Washed Oven dry Weight, gm. 7

Cumulative
Sieve Size
Wt. Retained, gm Specification
Wt. passing, gm. % Retained % Passing
In. / No. mm
1 1/2" 37.5 0.0 164 0.00 100.00
1" 25 0.0 164 0.00 100.00
3/4" 19 0.0 164 0.00 100.00
1/2" 12.5 3.0 161 1.83 98.17
3/8" 9.5 0.0 161 1.83 98.17
#4 4.75 2.0 159 3.05 96.95
#10 2 0.0 159 3.05 96.95
#40 0.425 1.0 158 3.66 96.34
#200 0.075 1.0 157 4.27 95.73
PAN 0.0
WASH LOSS 157.0
TOTAL 164.0
U.S. STANDARD SIEVE SIZE
100.00
P
90.00
E
R 80.00
C 70.00
E 60.00
N 50.00
T 40.00
F 30.00
I
20.00
N
10.00
E
R 0.00
1000.0 100.0 10.0 1.0 0.1 0.0 0.0
GRAIN SIZE IN MILLIMETERS

Sieve Size Liquid Limit 49.15


% Passing
No. mm Plastic Limit 32.28
4 4.75 96.95 Plasticity Index 16.87
10 2 96.95 Group Symbols ML
40 0.425 96.34 Soil Description Sandy SILT
200 0.075 95.73

REMARKS: Test report are based on sample taken from site.

Geotest Laboratory
DPWH-BRS
Unit C & D Ground Floor UB Building Brgy. Saguin Mac Arthur Hiway City of San Fernando Pamp.
Accredited Laboratory
Mobile Nos. : 0933-037-4628/ 0925-864-3433 (SUN)/ 0917-175-3433 / 0917-307-4211 (GLOBE)
Email add.: unified.geotest@gmail.com
PROPOSED HOLY FACE OF JESUS CHURCH
SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
FR. RICHARD LAGOS

BORE HOLE 1
.
PROPOSED HOLY FACE OF JESUS CHURCH
SOUTH CENTRAL, POBLACION, NAMPICUAN, NUEVA ECIJA
FR. RICHARD LAGOS

BORE HOLE 2
Un
ifie
d Ge
otest
Lab
ora