Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 1

West Bay Lagoon Villas

Q9971-1 Hot Water


V1

Project No. Date


DAR A L-HANDASAH DESIGN CALCULATION L9960 03-Dec-01
Shair & Partners
Mechanical & Industrial Department SHEET Sheet No. Computed by
BEIRUT - LEBANON

Subject Hot Water Demand For Tower Checked by Approved by


Building 4 Seasons Hotel - Beirut

1- Tower

HW Demand Storage
Fixture type Occup NO Total Flow Storage Heater
Demand Factor Factor

lph / fix lph lph liter kW


Toilet
Lavatory Private 300 7.6 2280
Bath Tub Private 300 76 22800
Bidet Private 300 11 3300
Shower Private 300 284 85200
Dishwasher Private 0 57 0
Washing MachinPrivate 0 76 0
Kitchen Sink Private 0 38 0

Sub-Total 113,580 0.25 0.8 28,395 22,716 1,154


Total Possible max demand 113580 28,395 22,716 1,154

Probable max. demand = 28395 lit/h


Required storage capacity = 22716 lit
Required heater capacity = 1154 kW

NB: Probable max demand = lph * Demand Factor


Required Storage Capacity = Probable max. demand* Storage Factor
Heater Capacity = (Storage capacity/3600)* 4.18*(60-25)

Q9971-1-CLC-ME-01-Rev A 1 of 1

You might also like