High Voltage Tester

PU2.5/5-10kV

agea-kull ag
Meisenweg 1
CH-4552 Derendingen
Switzerland
Application
agea-kull PU2.5/5-10kV tester provide a step-
less adjustable AC high voltage of 0-10kV and
max.0.5A for on-site testing of mainly capacitive
test objects such as motors, generators, cables,
switchgears and instrument transformers. They
are suitable for potential tests, C-tanϑ and PD
measurements.

Design
The system is designed for easy handling and
transportation. It is divided into a low voltage
and a high voltage part and allows the operator
to stand in a safe distance from the high
voltage. The reduced weight enables handling
by two or even only one person.

Control Unit
The control unit is built into a robust case with
castors and handle. A storage compartment
houses the auxiliary devices and cables re-
quired for connecting the test transformer and
the test objet. The controls are self-explaining
and very easy to operate. The unit provides all
safety devices according standard EN50191

Test Transformer
Mains Input Output Current On-Duty
230V 11A 0- 10kV 300mA 15min
50Hz or 60Hz 500mA 5min

The transformer is oil insulated to ensure a low


pd level of typical <5pC and compensates 50%
of the testing power. Internal measuring
resistors deliver the voltage and current signals
to the control unit.
Features
-Handwheel for stepless voltage adjustment
-Illuminated On/Off push buttons
-Timer with acoustical signalisation
-Voltage and current measurement, current trip
-Zero start interlock and emergency stop
-Socket for safety interlock and warning lamps
-50% internal power compensation (inductive)
-Handles and lifting eyes on HV transformer
Auxiliaries
Following devices are part of the delivery:
-2m mains and connection cables
-5m grounding cable with clamp
-1 manual grounding rod (L=385mm)
-3 red warning lamps with magnetic socket
-5m shielded and pd free high voltage cable
with clamp

Options
Available options are:
-Transport housing for the test transformer
-Castors on the test transformer
-HV-adaptors with M6-M12 tread for contacting
of motor or generator terminal screws
-Interlock chains and chain supports
-Motorized voltage adjustment
-Filtering

Customized Solutions
Systems with other specifications can be
delivered as well, for example
-with higher output voltages
-with more power
-with external high voltage compensation
-with cast resign transformers

Please contact us for your specific case


Load Diagram

Dimensions

Contact

agea-kull ag
High Voltage and High Current Test Equipment
Meisenweg 1, CH-4552 Derendingen / Switzerland
Tel: ++41 32 681 54 24 Web: www.agea.kull.ch Mail: info@agea-kull.ch

PU2-5-10kV LeafE1 07/2021