Guideline for choosing products 2007, edition 1

Cable terminations type Kabeldon SOT


for XLPE-cables 7.2-36 kV
• 1-core with Cu-tape screen
• 3-core with Cu-tape screen
and armouring
Prefabricated cable termination Kabeldon SOT
made of rubber with integrated Kits for 1-core cables with
field control and top sealing.
The outdoor variant has Cu-tape screen
permanent sheds which give
Instructions:
a prolonged creepage distance.
The indoor termination can also Choose cable size and voltage level in the upper
be installed in a humid indoor table depending on the quantity of cable cores.
environment. The number gives the second part of
The kits includes copper braids the Article No. for the correct type of accessory
and constant force springs for for the choice made.
connection of the copper tape
Accessories are specified in the lower table.
screen to earth.
One kit includes material for
three single core ends. Example:
Cable lugs have to be 1 x 240 mm² 17.5 kV cable, outdoor termination,
ordered separately. gives number 1121 which stands for:
Article No. 6234, 1121 = SOT 244-3 T

Cable 7.2 kV 12 kV 17.5 kV 24 kV 36 kV


A B
size
Indoor Outdoor Indoor Outdoor Indoor Outdoor Indoor Outdoor In- Outdoor
mm²
16 1100 – 1114 1119 – – – – –
25 1100 1119 1114 1119 1112 1117 – – –
35 1100 1119 1114 1119 1112 1117 1113 1118 –
50 1100 1119 1112 1117 1112 1117 1113 1118 –
70 1101 1117 1112 1117 1112 1117 1113 1118 1123
95 1101 1117 1112 1117 1112 1117 1113 1120 1123
120 1101 1117 1112 1117 1113 1117 1113 1120 1123
150 1101 1117 1113 1117 1113 1120 1116 1121 1123
185 1101 1117 1113 1120 1113 1120 1116 1121 1123
240 1109 1120 1115 1120 1116 1121 1116 1121 1124
300 1109 1120 1116 1121 1116 1121 1116 1122 1124
400 1109 1120 1116 1121 1116 1122 1116 1122 –
500 1115 1122 1116 1122 1116 1122 – – –
630 1115 1122 1116 1122 – – – – –

D
Type Article Designation Diameter Size of Picture
No. over insulation copper braid
6234, Ø mm mm²
C
Indoor 1100 SOT 101-3 R 10.5 - 15 10 A
Indoor 1101 SOT 102-3 R 12.9 - 25.8 10 A
Indoor 1109 SOT 103-3 S 21.5 - 34.9 22 A
Indoor 1112 SOT 241-3 R 15 - 28 10 B
Indoor 1113 SOT 241-3 S 15 - 28 22 B
Indoor 1114 SOT 241A-3 R 11 - 15 10 B
Indoor 1115 SOT 242-3 S 25 - 39 22 B
Indoor 1116 SOT 242-3 T 25 - 39 22 B
Outdoor 1117 SOT 243-3 R 15 - 24 10 C
Outdoor 1118 SOT 243-3 S 15 - 24 22 C
Outdoor 1119 SOT 243A-3 R 11 - 15 10 C
Outdoor 1120 SOT 244-3 S 22 - 33 22 C
Outdoor 1121 SOT 244-3 T 22 - 33 22 C
Outdoor 1122 SOT 245-3 T 31 - 40 22 C
In/outdoor 1123 SOT 361-3 T 26 - 39 22 D
In/outdoor 1124 SOT 361-3 U 26 - 39 35 D
Kabeldon SOT Prefabricated cable termination
E

Kits for 3-core cables with Cu-tape made of rubber with integrated
ield control and top sealing.
screen and armouring The outdoor variant has
permanent sheds which give
Instructions:
a prolonged creepage distance. L
Choose cable size and voltage level in the upper The indoor termination can also
table depending on the quantity of cable cores. be installed in a humid indoor
The number gives the second part of the environment.
Article No. for the correct type of accessory for The kits includes copper braids
the choice made. and constant force springs for
connection of the copper tape
Accessories are specified in the lower table.
screen to earth.
The kits also include crutch seal
Example: and protective hoses of heat shrink
3 x 240 mm² 17.5 kV cable, outdoor termination, type.
gives number 1095 which stands for: Cable lugs have to be ordered
F
Article No. 6234, 1095 = SOT 244-3 TB separately.

Cable size 7.2 kV 12 kV 17.5 kV 24 kV 36 kV


mm²
Indoor Outdoor Indoor Outdoor Indoor Outdoor Indoor Outdoor In- Outdoor
16 1081 – 1089 1085 – – – – –
25 1081 1085 1089 1085 1090 1086 – – –
L
35 1081 1085 1089 1085 1090 1086 1092 1096 –
50 1081 1085 1090 1086 1091 1087 1092 1096 –
70 1082 1086 1091 1087 1091 1087 1092 1096 1098
95 1083 1087 1091 1087 1091 1087 1092 1088 1098
120 1083 1087 1091 1087 1092 1087 1092 1088 1098
150 1083 1087 1092 1087 1092 1088 1094 1095 1098
185 1083 1087 1092 1088 1093 1088 1094 1095 1098
240 1084 1088 1093 1088 1094 1095 1094 1095 1099 G
300 1084 1088 1094 1095 1094 1095 1094 1097 1099
400 1084 1088 1094 1095 1094 1095 1094 1097 –

Type Article Designation Diameter Diameter Maximum Size of Pic-


No. over over outer length* copper ture
6234, insulation jacket L braid
L
Ø Ø mm mm²
Indoor 1081 SOT 101-3 RA 10.5 - 15 24 - 60 500 3 x 10 E
Indoor 1082 SOT 102-3 RA 12.9 - 25.8 24 - 60 500 3 x 10 E
Indoor 1083 SOT 102-3 RB 12.9 - 25.8 48 - 110 500 3 x 10 E
Indoor 1084 SOT 103-3 SB 21.4 - 34.9 48 - 110 500 3 x 22 E
Outdoor 1085 SOT 243A-3 RA 11 - 15 24 - 60 1450 3 x 10 G
Outdoor 1086 SOT 243-3 RA 15 - 24 24 - 60 1450 3 x 10 G
Outdoor 1087 SOT 243-3 RB 15 - 24 48 - 110 1450 3 x 10 G
Outdoor 1088 SOT 244-3 SB 22 - 33 48 - 110 1450 3 x 22 G H
Indoor 1089 SOT 241A-3 RC 11 - 15 24 - 60 550 3 x 10 F
Indoor 1090 SOT 241-3 RC 15 - 28 24 - 60 550 3 x 10 F
Indoor 1091 SOT 241-3 RD 15 - 28 48 - 110 550 3 x 10 F
Indoor 1092 SOT 241-3 SD 15 - 28 48 - 110 550 3 x 22 F
Indoor 1093 SOT 242-3 SD 25 - 39 48 - 110 550 3 x 22 F
Indoor 1094 SOT 242-3 TD 25 - 39 48 - 110 550 3 x 22 F L
Outdoor 1095 SOT 244-3 TB 25 - 33 48 - 110 1450 3 x 22 G
Outdoor 1096 SOT 243-3 SB 15 - 24 48 - 110 1450 3 x 22 G
Outdoor 1097 SOT 245-3 TB 31 - 40 48 - 110 1450 3 x 22 G
In/outdoor 1098 SOT 361-3 TB 26 - 39 48 - 110 1510 3 x 22 H
In/outdoor 1099 SOT 361-3 UB 26 - 39 48 - 110 1510 3 x 35 H

* Maximum length including termination measured from the crutch of the cable to the end of the XLPE-insulation.
© Copyright 2007 ABB. All rights reserved.

ABB Kabeldon
ABB Automation Technologies AB
Box 531
SE-441 15 Alingsås, Sweden
Tel: +46 322 770 00
Fax: +46 322 770 01
www.abb.se/kabeldon

You might also like