Bmz1Kas 1,8/3 KV - Medium Voltage Power Cable: Description

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

BMz1Kas 1,8/3 kV - Medium voltage power cable

Article number: 44415 24-03-2017

Description
1 x 630 rs + as70

Single-core, rubber (EPR) insulated, medium-voltage cable. The cable


is intended for permanent installation in tram and metro installations
and forms the connection between the transformer, rectifier and the
direct-current distribution system and the third rail.

Trading information
Product group Medium voltage power cable

Series Various installation

Type BMz1Kas 1,8/3 kV

Net. Weight 7,267 kg/m

Sheath marking TKF - BMz1Kas 1,8/3kV- 1X630rs+as70 {Year} {Length} {Batch}

Trade lengths
Reel à 1 (44415 / 8713182060763)

Reel à 500 (44415H X 500/20 / 8713182060787)

Reel à 1000 (44415H X 1000/50 / 8713182060770)

Subject to technical modifications | No rights can be derived from this information

Spinnerstraat 15 | P.O. Box 6 | 7481 KJ Haaksbergen | Nederland | Phone: +31 (0)53 573 22 55 | E-mail: info@tkf.nl Page 1 of 3 24-03-2017
BMz1Kas 1,8/3 kV - Medium voltage power cable
Article number: 44415 24-03-2017

Construction characteristics
Standardization IEC 60502-1

Flame retardant In accordance with IEC 60332-1 / IEC 60332-3-24 Cat. C

Low smoke (acc. EN 61034-2) Yes

Longitudinal water blocking conductors No

Longitudinal water blocking screen Yes

Armouring No

Number of cores 1

Nominal cross section conductor 630 mm²

Conductor material Cu

Shape of conductor Round

Conductor category Class 2 = stranded

Nominal earthscreen cross section 70 mm²

Earthscreen construction Copper round wire + copper tape counter spiral

Core insulation Rubber (HEPR)

Material outer sheath Flame Retardant Halogen Free Polyolefin Compound

Colour outer sheath Red

Properties
Halogen free IEC 60754-1 / IEC 60754-2

Low smoke IEC 61034-1 & IEC 61034-2

Conductor diameter 32.6 mm

Insulation thickness 2.4 mm

Diameter over insulation 39.2 mm

Diameter shield wires 1.15 mm

Diameter over shield 42.1 mm

Outer sheath thickness 2.6 mm

Outer diameter approx. 48.1 mm

Min. bending radius during installation 0.72 m

Min. bending radius after installation 0.58 m

Tensile force with pullingsleeve 6900 N

Subject to technical modifications | No rights can be derived from this information

Spinnerstraat 15 | P.O. Box 6 | 7481 KJ Haaksbergen | Nederland | Phone: +31 (0)53 573 22 55 | E-mail: info@tkf.nl Page 2 of 3 24-03-2017
BMz1Kas 1,8/3 kV - Medium voltage power cable
Article number: 44415 24-03-2017

Technical characteristics
Nominal voltage U0 1.8 kV

Nominal voltage U 3 kV

Nominal voltage Umax 3.6 kV

Conductor DC resistance @ 20°C 0.0283 Ohm/km

Max. conductor temperature 90 °C

Shield DC resistance 0.27 Ohm/km

Mutual capacitance (Nominal) 0.94 µF/km

Operating reactance trefoil arrangement 0.08 Ohm/km

Operating reactance flat arrangement 0.15 Ohm/km

Conductor AC resistance @ max. cont. Conductor 0.0405 Ohm/km


temp.

Frequency 50 Hz

max. thermal short-circuit current conductor 1 sec 90.1 kA

max. short-circuit temperature conductor 250 °C

max. thermal short-circuit current shield 1 sec 10.4 kA

max. short-circuit temperature shield 250 °C

Minimum installation temperature 0 °C

Max. operation temperature 70 °C

Subject to technical modifications | No rights can be derived from this information

Spinnerstraat 15 | P.O. Box 6 | 7481 KJ Haaksbergen | Nederland | Phone: +31 (0)53 573 22 55 | E-mail: info@tkf.nl Page 3 of 3 24-03-2017