change centrally in a library. You can use a faceplate in several projects as required. The
faceplates are stored in the project library.
You use faceplates to create individually configured display and operating objects. You can use
faceplates several times in the project or in different projects. All instances of a faceplate in the
project are changed centrally. This reduces the configuration effort.
Faceplates are based on a type-instance model to support the central changeability. You
create central properties for an object in types. The instances represent local points of use of
the types.
● Faceplate type
You create a display and operating object according to your requirements and store it in the
project library. The instances are bound to the respective faceplate type. If you change a
property of a faceplate type, the property is saved centrally and also changed in all
instances. In the faceplate type, you define the properties that can be changed on the
faceplate. You edit a faceplate type in the "Faceplates" editor.
● Faceplate
The faceplate is an instance of the faceplate type. You use a faceplate in screens as a
display and operating object. You configure the variable properties of the faceplate type on
the instance. You assign the tags of your project to the faceplate, for example. If you
configure properties on the faceplate, you overwrite the properties of the faceplate type. The
changes on the faceplate are saved at the point of use and have no effect on the faceplate
type. To reset the variable properties at the faceplate to the properties of the faceplate type,
select "Reset instance" in the shortcut menu.
The figure below shows the relationships between the faceplate type and the faceplate. The
background color of the I/O field is configured in the faceplate type in such a way that every
instance can change the property. Blue is used as the background color in the faceplate type.
You use yellow as the background color in the faceplate.
Visualizing processes
System Manual, 11/2019, Online help printout 265
When you change the background color in the faceplate type, this has no effect on the faceplate
because the "Background color" property is assigned on an instance-specific basis.
Not all HMI devices support every display and operating object. The screen objects that are not
available in the respective HMI device are not displayed when using the faceplate.
Independent of the device, all properties are offered for the configuration during the generation
of faceplates. When using a faceplate in a screen, only the properties supported by the
configured device are available.
The following devices support faceplates:
● KTP 400
● KP 400
● TP 700
● KP 700
● TP 900
Visualizing processes
266 System Manual, 11/2019, Online help printout
● KP 900
● TP 1200
● KP 1200
● TP 1500
● KP 1500
● TP 1900
● TP 2200
Visualizing processes
System Manual, 11/2019, Online help printout 267
The library view for faceplate types consists of several editors, e.g. "Screens" and "Tags" which
are arranged in the work area and the configuration area.
In the work area, place the objects contained in the faceplate type as you usually do in the
"Screens" editor. You can remove objects, or use the "Toolbox" task card to add new objects.
Visualizing processes
268 System Manual, 11/2019, Online help printout
● Properties
The static and dynamic properties are identified as follows:
– The symbol identifies a dynamic property. Dynamic implementation of this property,
using tags or text and graphic lists.
– The symbol identifies a static property. You change only the values of a static
property.
● Text lists
You can also create and edit texts lists for the faceplate type in the "Text lists" tab. These text
lists are only available within the faceplate type. You can interconnect the text lists of the
faceplate type directly with an object contained in the faceplate type, such as a symbolic I/
O field.
Visualizing processes
System Manual, 11/2019, Online help printout 269
● Graphic lists
If necessary, you can also create graphics lists for the faceplate type in the "Graphics lists"
tab. These graphic lists are only available within the faceplate type. You can interconnect
the graphic lists of the faceplate type directly with an object contained in the faceplate type,
e.g. a graphic I/O field.
● User texts
The "User text" tab shows the contained user text of the opened faceplate type, for example
entries from text lists. You can enter the compilations for the individual project languages
directly in the "User text" tab.
Faceplate types are display and operating objects which are made up of several objects, e.g.
controller modules.
1. Select all the objects that you need for the faceplate type.
2. Select the "Create faceplate type" command in the shortcut menu of the multiple selection.
A dialog opens.
3. Enter a name for the faceplate.
4. If necessary, add a comment or change the version number.
The library view opens. Two versions of the type are displayed in the "types" folder. Version
0.0.1 has been released and contains the currently selected objects.
The 0.0.2 version has the status "in progress". Edit the faceplate type in version 0.0.2 as
required.
Visualizing processes
270 System Manual, 11/2019, Online help printout
1. The library view is open.
2. Select the "Add new type" command in the shortcut menu of the project library. A dialog
opens.
3. Select the runtime for which the faceplate type is to be available. An empty faceplate type
is created.
4. Drag-and-drop the objects from the "Toolbox" task card to the work area of the faceplate
type.
The new faceplate type is created and displayed under the selected name in the project library.
The faceplate type is assigned the status "in progress" and the version 0.0.1.
Visualizing processes
System Manual, 11/2019, Online help printout 271
In the configuration area of the "Faceplates" editor you define which properties and process
values of the objects contained in the faceplate can be configured in the "Properties" tab.
For tooltip texts configured for objects in the faceplate to be displayed in Runtime, insert the
property "Tooltip text" as faceplate property.
Independent of the device, all properties are offered for the configuration during the generation
of faceplates. When using a faceplate in a screen, only the properties supported by the
configured device are available.
The use of user-defined PLC data types (UDTs) of PLCs S7-300 and S7-400 is not supported.
These PLC data types cannot be selected as a faceplate property.
1. To create a new property, click the "Add property" button in the interface list.
A new property is displayed in the "Interface" list.
2. To create a new category, click the "Add category" button in the interface list.
A new category including a new property is displayed in the "Interface" list.
Visualizing processes
272 System Manual, 11/2019, Online help printout
3. Click the name of the property and assign a name, for example, "Color".
4. Select the data type.
Note the following rules when entering property names of the faceplates:
● The name must start with a letter.
● The name can contain alphanumeric characters and the underscore.
● The name may not contain more than 255 characters.
● Do not use any UNICODE characters (for example, Chinese characters).
If an element of a faceplate is assigned as data type of the user data type (UDT), the
following rule applies:
The length of the name of a property of the faceplate together with the length of the name
of the lower-level element of the "User Data Type" (UDT) data type must not exceed
126 characters.
Visualizing processes
System Manual, 11/2019, Online help printout 273
You have created a new property.
1. Click an object in the "Contained objects" list.
2. Select a property, e.g. "Appearance > Background color".
3. Move the property from the "Contained objects" list to the desired property in the "Interface"
list by drag&drop.
The connection is displayed as a colored line.
The system assigns the same data type to the property in the "Interface" list as that of the
property in the "Contained objects" list.
To change the data type, select the data type from the data types of the connected property.
4. Repeat step 3 to connect other properties of the contained properties with the interface.
The property from the "Contained objects" list must be in concordance with the data type of
the already connected property of the "Interface" list.
As of V13 SP1, you can use the HMI user data types and the PLC user data types as properties
of the faceplates.
Visualizing processes
274 System Manual, 11/2019, Online help printout
You interconnect the HMI user data types and the PLC user data types with the faceplates
using interface properties by connecting the faceplates with the structural elements of the
interface properties.
To set the HMI user data types and the PLC user data types as properties of the faceplates,
follow these steps:
1. Select the user data type in the selection list under "Type".
2. In the Inspector window under "Properties > Properties > General", select the interface
property of the faceplate in the "Tag" selection list.
Visualizing processes
System Manual, 11/2019, Online help printout 275
You have created a new property or a new category with a property. You have connected the
property of the interface with a property of the contained objects. If you use an instance of the
faceplate type in a screen, you configure the properties of the faceplate which you have created
in the "Interface" list.
Static properties are only available for panels and RT Advanced. You work with dynamic
properties in RT Professional.
1. Select "Edit faceplate" in the shortcut menu. The "Faceplates" editor is open.
2. Select the property which you want to delete in the "Interface" list.
3. Select "Delete" in the shortcut menu.
The property is deleted from the "Interface" list. Existing connections to the contained objects
are deleted. All linked faceplates lose their instance-specific property.
1. Select "Edit faceplate" in the shortcut menu. The "Faceplates" editor is open.
2. Select the category which you want to delete in the "Interface" list.
3. Select "Delete" in the shortcut menu.
The category including the properties is deleted from the "Interface" list. Existing connections
to the contained objects are deleted. All linked faceplates lose their instance-specific properties.
Visualizing processes
276 System Manual, 11/2019, Online help printout
You have moved the property to a new category.
You connect a tag in the faceplate type directly with the properties of the objects contained in
the faceplate type. The tags in the faceplate type are a central means of defining dynamic
properties in the faceplate type.
The tags of a faceplate type have limited functionality. The "Tags" tab of the configuration area
has the same structure as the "Tags" editor.
Use of the "." or "@" character in names of tags in faceplate types is not permitted. Do not use
the special characters in the tag names in faceplates.
In the following situations, you may not assign an array element or a multiplex tag that is
interconnected with a faceplate to a property of a screen object:
● The property is configured in a faceplate as parameter of a system function.
● System functions or scripts are assigned in the faceplate to events of the property.
Visualizing processes
System Manual, 11/2019, Online help printout 277
1. Click "Add" in the "HMI tags" table. A new tag is created in the faceplate type.
2. Open "Properties > Events" in the inspector window if necessary. You configure the "Value
change" event on the tag for example.
3. In the work area, select the object to which you want to assign this tag, e.g. an I/O field.
4. Select the tag in the inspector window of the I/O field "Properties > Properties > General >
Process > Tag".
Only tags of the faceplate type are displayed in the object list in the "Faceplates" editor.
You have created a tag in the faceplate type. You are using the tag in the faceplate for scripting,
for example.
In the configuration area of the "Faceplates" editor you create scripts which you only use within
a faceplate type. You can only refer to tags of the faceplate type or properties of the contained
objects within the script. The script is used as a copy in the instance of the faceplate type.
Visualizing processes
278 System Manual, 11/2019, Online help printout
5. Click "HMI tags".
All tags of the faceplate type are displayed in the object list.
6. Select a tag and confirm the selection.
7. Press the shortcut keys <CTRL+J> to use properties of the faceplate type in the script. The
object list opens.
8. Click "Properties".
All dynamic properties of the "Interface" list for the faceplate type are displayed in the object
list.
You have created a script in the faceplate type. The instance of the faceplate type uses a copy
of the script. The script is executed in runtime depending on the configuration.
In the configuration area of the "Faceplates" editor you define which events of the objects
contained in the faceplate can be configured in the "Events" tab. You configure a function list
on the events of the faceplate in the "Screens" editor.
Visualizing processes
System Manual, 11/2019, Online help printout 279
3. Move the event from the "Contained objects" list to a new category in the "Interface" list.
The new event is displayed in the "Interface" list.
The connection appears as a colored line.
4. Double-click the event and, if required, change the name of the event.
You have created an event in the faceplate type. if you use an instance of the faceplate type,
you will only be offered the configured events in the inspector window. You configure a function
list on the event in the faceplate.
Visualizing processes
280 System Manual, 11/2019, Online help printout
In the configuration area of the "Faceplates" editor you define which events of the objects
contained in the faceplate can be configured in the "Events" tab. You configure a function list
on the events of the faceplate in the "Screens" editor.
4. Double-click the event and, if required, change the name of the event.
Visualizing processes
System Manual, 11/2019, Online help printout 281
You have created an event in the faceplate type. If you use an instance of the faceplate type,
you will only be offered all default settings for events in the inspector window. In the faceplate
you configure a function list or a VB-script or C-script on the event.
In a faceplate type, you connect a text list with an object included in the faceplate type. Text is
assigned to the values of a tag in a text list. The text list is used, for example, to display a
selection list in a symbolic I/O field contained in the faceplate type. The interface between the
text list and a tag of the faceplate type is configured at the object that uses the text list.
1. Click "Add" in the "Text lists" table. A new text list is created in the faceplate type.
2. Assign a name to the text list that indicates its function.
Visualizing processes
282 System Manual, 11/2019, Online help printout
3. Select the text list type, e.g. "Value/Range" under "Select".
4. Click "Add" in the "Text list entries" table.
5. Define the values or range of values for the text list.
6. Enter a text for every value range which is displayed in Runtime when the tag is within the
specified value range.
7. Select an object, e.g. a symbolic I/O field, in the work area of the faceplate type.
8. In the Inspector window of the object, enable "Properties > Properties > General > Label >
Text list".
9. Select the "Text list" from the selection list.
10.Select a tag of the faceplate type under "Process > Tag".
You have created a text list in the faceplate type. This text list is linked to an object contained
in the faceplate type. You have configured a faceplate type tag at the object.
In a graphics list, specific graphics are assigned to possible values of a tag. In a faceplate type,
you connect a graphics list with an object included in the faceplate type. Graphics are assigned
to the values of a tag in a graphics list. For example, the graphics list is used to display a
selection list in a graphic I/O field contained in the faceplate type. The interface between the
graphics list and a tag of the faceplate type is configured at the object that uses the graphics list.
Visualizing processes
System Manual, 11/2019, Online help printout 283
1. Click "Add" in the "Graphics lists" table. A new graphics list is created in the faceplate type.
2. Assign a functional name to the graphics list.
3. Select a graphics list type, e.g. "Range (... - ...)", under "Selection".
4. Click "Add" in the "Graphics list entries" table. A new entry is created in the list.
5. Define the values or range of values for the graphics list.
6. Select a graphic for every value or value range which is displayed in runtime when the tag
is within the specified value range.
7. Select an object, e.g. a graphic I/O field, in the work area of the faceplate type.
8. Activate "Properties > Properties > General > Contents > Graphics list" in the object's
Inspector window.
9. Select the "Graphics list" from the selection list.
10.Select a tag of the faceplate type in "Process > Tag".
You have created a graphics list in the faceplate type. This graphics list is linked to an object
contained in the faceplate type. You have configured a faceplate type tag at the object.
If you use several languages in your project, you can translate individual texts directly. As soon
as you change the language of the software user interface, the translated texts are available in
the selected language.
When you create a faceplate in the "Text" tab, alarm class texts and alarm texts are
automatically created in the tab. These texts are required for the WinCC alarm logging.
Visualizing processes
284 System Manual, 11/2019, Online help printout
● A project is open.
● You have opened the "Faceplates" editor.
● You have created a faceplate type.
● The faceplate type contains at least one object with text, e.g. a text field.
You have translated individual texts in the "Texts" tab of the faceplate type. The texts will then
be displayed in the runtime language.
Visualizing processes
System Manual, 11/2019, Online help printout 285
You have the option to export the texts of the faceplates for translation and then to import them
back again. An OpenOffice XML file is created for the export that can be edited with Microsoft
Excel and other spreadsheet programs. You set the languages available for the export and
import in the "Languages" tab. You export and import the text of a faceplate type using the
buttons "Export project texts" and "Import project texts" in the toolbar.
Alternatively, you can export and import the texts of the faceplates using the commands "Export
texts" and "Import texts" in the "Library" task card. In this case, the project languages defined
for this project are used for the export and import.
● A project is open.
● You have opened the "Faceplates" editor.
● You have created a faceplate type.
● The faceplate type contains at least one object with text, e.g. a text field.
Visualizing processes
286 System Manual, 11/2019, Online help printout
6. Enter the name and path for the export file.
7. Click "Export".
Once the export is successfully concluded, the export file is stored under the specified path.
To import the text back into the TIA Portal after editing or translation, follow these steps:
1. Open the faceplate type in the project library.
2. Open the "Texts" tab in the "Faceplates" editor.
3. Click "Import project texts" in the toolbar.
The "Import" dialog box opens.
4. Select the path and name of the import file in the "Select file for import" box.
If you have made changes to the source language in the export file and would like to
overwrite the entries in the project with the changes, select the "Import source language"
check box.
5. Click on "Import".
You have exported the text of a faceplate for translation and imported it back into the TIA Portal
after translation.
All faceplate types in the project library have a status. You create a faceplate type in the "in
progress" status. You can edit the faceplate types as required in this status. When editing is
complete, release the faceplate type.
Visualizing processes
System Manual, 11/2019, Online help printout 287
1. Select, for example, the released version 0.0.1 of a faceplate type in the project library.
2. Select "Edit faceplate type" in the shortcut menu.
The library view opens. The new version 0.0.2 of the faceplate type has been created.
The faceplate type has the "In progress" status.
In the faceplate type, specify the response of the faceplate when it is resized.
1. Activate "Properties > Properties > Layout > Fit to size > Auto-size".
2. Select the "Fixed aspect ratio" setting, for example.
This setting retains the aspect ratio when you resize the faceplate.
3. Click the faceplate in the "Libraries" task card.
4. Select "Release version" in the shortcut menu.
Visualizing processes
288 System Manual, 11/2019, Online help printout
You have specified how the faceplate responds when its size in a screen is changed. You can
change the response for a particular faceplate.
Select a faceplate in the screen. Select the required setting in "Properties > Properties > Layout
> Characteristics" in the Inspector window.
In the faceplate type, specify the response of the faceplate when it is resized.
1. Activate "Properties > Properties > Layout > Fit to size > Auto-size."
2. Select one of the following options for "Response to resizing":
– Fixed size
Specifies that the size of the faceplate is unchangeable.
– Proportional
The faceplate is scaled proportionally. The rectangle surrounding the object is not scaled.
– None
No restriction on resizing of the faceplate.
– Original size
Specifies that the size of the faceplate is unchangeable, but the size of the rectangle
surrounding the object can be adapted.
– Keep aspect ratio
The size of the faceplate is changeable. The aspect ratio is kept during resizing.
3. Click the faceplate in the "Libraries" task card.
4. Select "Enable faceplate type" in the shortcut menu.
You have specified how the faceplate responds when its size in a screen is changed. You can
change the response for a particular faceplate.
Select a faceplate in the screen. Select the required setting in "Properties > Properties > Layout
> Characteristics" in the Inspector window.
Visualizing processes
System Manual, 11/2019, Online help printout 289
The faceplate type is stored in the project library. If you use the faceplate type in a screen, you
create an instance of the faceplate type.
Note that a faceplate is always configured for a particular class of HMI devices. For example,
you cannot use a faceplate type that is configured for "RT Professional" in a screen on an "RT
Advanced" HMI device.
The number of faceplate instances per screen is not limited. However, you should be aware of
the fact that the number of faceplate instances used, or the use of scripts in the faceplate
instances, will have an impact on performance.
If you would like to copy a faceplate instance from one project to another project, first copy the
faceplate type to the target project, followed by the faceplate instance.
● A screen is open.
● The "Libraries" task card is opened.
● The project library is open and it contains at least one faceplate type.
Faceplate types are also stored in global libraries. When you add a faceplate type from the
global library to the screen, the system automatically saves a copy of it to the project library.
1. Move the desired faceplate type from a library to the screen by drag&drop.
Visualizing processes
290 System Manual, 11/2019, Online help printout
You have created an instance of the faceplate type. The instance is given the version number
of the most recently released type.
Configure the properties of the faceplate in the Inspector window as required. To dynamize the
faceplate, open the interface in the Inspector window.
Cancel application, to remove specified instances from the update of the faceplate type.
The faceplate is converted into a group that is independent of the faceplate type. Modifications
of the faceplate type have no effect on this group.
Visualizing processes
System Manual, 11/2019, Online help printout 291
You can dynamically control events and properties of faceplates in two ways:
● Dynamically controlling faceplates
You configure the events or dynamic properties individually for the application point on the
faceplate. To do this, define in the "Faceplates" editor that these properties and events are
configurable in the faceplate. To dynamize the faceplates in the "Screens" editor, use the
scripts and tags that are created in the project.
● Dynamizing the faceplate type
You dynamize the objects which are contained in the faceplate type in the "Faceplates"
editor. You configure the individual objects as in the "Screens" editor. Tags and scripts are
available in the "Faceplates" editor to dynamize properties and events. You do not have
access to the tags and scripts of the project within the faceplate.
Every faceplate created with the faceplate type has the same preconfigured dynamization.
You can edit this dynamic control only in the "Faceplates" editor.
You are using the instance of a faceplate type in an object group. The properties of the
instance are also displayed as properties of the group. Any dynamization with tags, scripts
or animations of the group is not displayed in Runtime.
If you automatically calculate the trigger for scripts on the faceplate type with the "Calculate
trigger automatically (recommended)" option, the update cycle of the instances is about 2
seconds and is independent of the picture update cycle configured in the pictures.
WinCC provides preconfigured dynamic control in the "Animations" task card. You use
animations to dynamize faceplates and faceplate types.
Visualizing processes
292 System Manual, 11/2019, Online help printout
You dynamize a faceplate in exactly the same way as you dynamize an object from the "Tools"
task card.
You connect the dynamic properties of the faceplate in the "Screens" editior with a tag or a
script which supplies values to the property in runtime.
You Include tags and scripts which you have created in the project for the faceplate.
In Runtime, the object moves in response to every change in value of the tag that is used to
control the movement. The direction of movement corresponds to the configured type of
movement "horizontal".
Visualizing processes
System Manual, 11/2019, Online help printout 293
In this example you create a faceplate in which you can convert the value of a length measuring
system from kilometers into meters. The length in meters is displayed in an output field.
● A screen is open.
● The toolbox window is displayed.
Visualizing processes
294 System Manual, 11/2019, Online help printout
For the example you require objects with the following settings:
1. In the toolbox, click the individual objects and drag&drop the objects into the screen.
2. Set the properties as shown above.
3. Select all objects.
4. Select the "Create faceplate type" command in the shortcut menu of the multiple selection.
The "Add type" window opens.
5. Enter "KMtoMeter" as type name.
The faceplate type appears in the project library under the name "KMtoMeter". The faceplate
type is assigned the "in progress" status.
You create the dynamic property and tag of the faceplate type.
Visualizing processes
System Manual, 11/2019, Online help printout 295
3. Double click the name of the property and enter "KMToMeter".
4. Click the selection list and select the data type "Int".
The "KMToMeter" property is displayed in the "Interface" list. The symbol identifies the dynamic
property. The property will be linked to a tag in the next step.
The "KMToMeter" property and the "BB_Tag" of the faceplate type are created in the
configuration area of the "Faceplates" editor.
You create a script that converts the value of a length measuring system from kilometers to
meters.
Visualizing processes
296 System Manual, 11/2019, Online help printout
1. Click "Scripts > Faceplate scripts" in the configuration area.
2. Double click "Add VB script".
3. Press the shortcut keys <CTRL+J>.
The object list opens.
4. Click "HMI tags".
The faceplate tag "BB_Tag" is displayed in the object list.
Visualizing processes
System Manual, 11/2019, Online help printout 297
10.Enter "*1000" at the end of the code. This corresponds to the conversion factor from
kilometers to meters.
11.Enter the name "Script_1" under "Properties > Properties > General >Setting > Name" in the
Inspector window.
The script has been created in the faceplate type. If you use the "KMtoMeter" faceplate type in
a screen, you assign a tag to the "KMtoMeter" property. The value of this tag is multiplied by
factor 1000 and assigned to the tag of the faceplate type "BB_Tag" as a new value. In this way
you supply values to the tags of the faceplate type.
You insert the faceplate type "KMtoMeter" in a screen and assign a tag to the dynamic property
"KMtoMeter".
For the example you require a tag with the following settings:
Kilometer No ULong
Visualizing processes
298 System Manual, 11/2019, Online help printout
1. Create the HMI tag "Kilometer" with the settings named above.
2. Open the "project library" in the "Libraries" task card.
3. Move the "KMtoMeter" faceplate type into the screen by drag&drop.
4. Click "Properties > Properties > Interface" in the Inspector window.
The table shows all the properties which you can dynamize in the faceplate.
The dynamic property "KMtoMeter" is linked with the "Kilometer" tag. During runtime the
dynamic property is supplied with values of the "Kilometer" tag. The values are multiplied by
factor 1000 in the script of the faceplate type and assigned to the tag in the faceplate as a new
value.
Visualizing processes
System Manual, 11/2019, Online help printout 299
You connect the included objects in the faceplate "KMtoMeter" to a faceplate tag and a
faceplate script.
You connect the I/O field with the "BB_Var" tag of the faceplate type. You connect the "Click"
event for a button to the script "Script_1".
The I/O field is connected with the tag of the faceplate type. The button is connected with the
script of the faceplate type.
If you click the button of the faceplate during runtime, the script is executed. The value of the
tag of the faceplate is output in the I/O field.
Visualizing processes
300 System Manual, 11/2019, Online help printout