Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

21, rue d'Artois, F-75008 Paris Session 2000

http://www.cigre.org 12-205 © CIGRÉ

CURRENT LIMITATION IN HIGH TEMPERATURE SUPERCONDUCTING


TRANSFORMERS AND IMPACT ON THE GRID

E. Serres (*), M. Lakner S. Fleshler


C. Levillain J. Rhyner A. Otto
F.X.Camescasse M. Chen R. Diehl
J.-F. Picard W. Paul C. Christopherson
FRANCE H. Zueger R.Mason
SWITZERLAND K. de Moranville
J. Backes J. Daniel
D. Bonmann USA
GERMANY

ABSTRACT: KEY WORDS:


Superconductivity, transformer, current-limitation,
After the manufacturing, short-circuit and dielectric system benefits.
tests and one year operation of a 630 kVA -
18720 V/ 420 V High Temperature Superconducting
1. CURRENT LIMITATION : THEORY
Transformer in Geneva (Switzerland), new perspectives
were opened for the development of transformers with The successful manufacturing, testing and one year
new functionalities. Current limitation appears to be operation of a 630 kVA - 18720 V/ 420 V High
one of the most promising advantages for future Temperature Superconducting (HTS) transformer in
networks. Geneva had demonstrated the feasibility of integrating
such a transformer into an existing network in principle
The first part of this document describes the capability [1].
of a High Temperature Superconductor (HTS) wire to While for this demonstrator the major potential
limit high prospective fault currents to very low values. advantages were low load losses, the elimination of oil
Simulations and measurements prove this new and compactness, it was recognised that these features
functionality under various conditions. The wire is a do not take full advantage of the specific properties of
bismuth, strontium, calcium, copper oxide power-in- superconductors. Especially the exploitation of the
tube wire, with a critical temperature of around 110 K. transition from the superconducting to the normal-
conducting, resistive state for the limitation of fault
Moreover, right after the fault current limiting event, if currents, would add a very promising new functionality
the critical temperature is not exceeded, the wire is able to a mature product like a transformer.
to recover its superconducting characteristics even if 1.1. System requirements for a fault current limiting
the rated current is flowing. This « operational transformer
recovery » offers good opportunities for network
operation. A series connected device may be considered The network environment of the transformer includes
as a low impedance during normal operation, high the protection system, which shall detect, locate and
resistance during short-circuit and low impedance some interrupt fault currents as fast as possible in order to
periods after the fault, without disconnection. avoid or limit damage caused by the energy released. On
the other hand the protection system, together with an
The second part of this document deals with the added intelligent network layout, shall ensure a minimum of
value of such a capability on transformers, taking full voltage fluctuations and interruptions seen by the
advantage of the reduced peak and r.m.s. values of the customers.
short-circuit current. Different application examples are
given, from step-up transformers to HV/MV It is believed that the economic breakeven of HTS
transformers leading to different benefits for the system, power transformers will be in excess of several tens of
such as reduced stresses on downstream devices, MVA, such that in most cases the insertion of a current
reduced load losses, more compact transformers, limiting HTS transformer would impact several voltage
increased voltage stability, reduced generator ratings… and protection levels. Even in simple schemes like the

(*) EDF – Division Recherche & Développement –1 Avenue du général de Gaulle – 92141 Clamart Cedex
-2-

one shown in Fig. 1, the time needed to detect, localise log (current)
and interrupt selectively the faulty feeder adds up to at
least 250 ms for conventional protection equipment. In
case of a main breaker failure, the delay and breaker
opening time of the next higher voltage level result in a
total fault duration that easily exceeds 1 s. In overhead
line networks it is common practice to apply automatic T1

log (voltage)
N=2 T2>T1
reclosure patterns. For short “open” periods the time T3>T2
integral of the “closed” periods represents a good T4>T3
approximation of the thermal load on the equipment.
Ic2
Normal transients, like the starting of large electric Ic3
motors, may reach amplitudes of an order of 2 p.u. Such
transients are not allowed to trip the protection system. Ic4 Ic1

IEC 354 allows emergency overload periods of up to


150% rated load for large power transformers, at the Fig. 1: Typical I-V-curves of a BSCCO HTS conductor
expense of accelerated thermal ageing of the electrical with High Resistive Sheath for 4 different temperatures
insulation.
For the first few cycles of a fault, one can assume
Ideally a fault current limiting device should have zero adiabatic heating of the conductor, since heat diffusion
impedance for currents up to about 2 p.u. Higher over the metallic and HTS cross section is dominating.
prospective currents should be limited to 5 p.u. for This heating reduces the critical current of the HTS
periods up to 2 s. After the fault current is cut, the material, which leads to a further increase of resistance.
device should immediately and automatically recover its
full loadability. Preferably such a device should work At later stages of the fault and during recovery of the
without the need for an active control in order to be fail- superconducting state after clearing the fault, the heat
safe. transfer to the coolant, either in direct contact with
metallic surfaces or through electrical insulation,
becomes effective.
1.2. Impact of network requirements on HTS
conductor design For an HTS conductor in good thermal and electrical
In the resistive current limiting state, heat is dissipated at contact to a continuous metallic bypass, the two
a very high rate into the current limiting device. The conditions to be met for fast recovery can be
challenge is to limit the temperature increase, to provide approximated as: The temperature of the HTS material
sufficient cooling for automatic recovery and to release may not exceed the critical temperature at the end of the
the dissipated fault energy in a controlled manner. fault.

In an electrical grid, where the feeding voltage is C p ⋅ density ⋅ (Tc − Top ) ⋅ ρ el / V 2 > t fault (1)
constant to a good approximation, the maximum fault where
current flowing in the conductor is determined by the I- tfault duration of the fault
V-curve of the HTS material. In parallel to the HTS Cp average specific heat of HTS material and
material a bypass conductor in good electrical contact is metallic bypass in contact with it.
needed to spread out the effect of local inhomogeneities density average density of HTS material and metallic
in the HTS material, as to avoid hot spots. The parallel bypass
resistances of HTS material and electrical bypass Tc critical temperature of the HTS at rated current
determine the rate and power density at which heat is and the related magnetic field
generated. Top rated operating temperature of the HTS
V voltage gradient along the conductor
Fig. 1 gives an example of typical Current - Voltage
ρel current dependent, overall combined resistivity
(I-V) curves of an HTS conductor for different
of HTS conductor and electrical bypass,
temperatures. HTS conductors exhibit a rather wide flux
averaged over the fault duration.
flow regime extending significantly above the critical
current Ic, where superconductivity noticeably enhances
The second condition for recovery under rated current is
the conductivity.
that the heat flux at the surface of conductor and bypass
be smaller than the steady state heat transfer available at
that instant.
jop ⋅ ρ el ⋅ d < h ⋅ (Tc − Top ) ⋅ (α + 1) / α
2 *
(2)
-3-

where Time (s)

jop is the rated operating current density, averaged 200


0 0,2 0,4 0,6 0,8 1 1,2
25

over HTS conductor and bypass 150

ρel*
20
is the current dependent average resistivity of 100
critical current 16-18 A DC
imposed current : 20 A peak
the conductor with its electrical bypass at the 15
50
end of the fault current limiting event, averaged 10

over time 0

Current (A)

Voltage (V)
h is the effective heat transfer coefficient -50 current 5

α is the aspect ratio width/thickness d of the -100


0

conductor cross section -150 voltage

d is the overall thickness of the conductor


-5
-200

-10
-250

It is essential to note that due to the wide flux flow -300 -15
region, in HTS conductors ρel assumes very small
instantaneous values during the off-peak moments of the Fig. 2: Current and voltage traces of a 1 m section of
ac cycle, resulting in the low average resistivity allowing composite conductor during and after a fault of 150 ms
fast recovery.
1.3. Accessibility by conductor design and physical Fig. 2 shows current and voltage traces of a 1 m section
limits of this composite conductor during and after a fault of
150 ms. The critical current of this sample was 16 – 18
The amplitude of the first fault current peak is A. The conductor was insulated with about 0.2 mm thick
dominated by the flux flow resistance of the HTS polymer. The peak voltage gradient during the fault was
material. As the conductor heats up, the resistance of the 0.15 V/cm. It is recognised that the voltage decreases
bypass determines the short circuit current. Common slowly after the fault, under more than critical current.
alloys have resistivities of up to 100 µΩ.cm. The heat Once the current drops back to its operational level
capacity effective during the short term current limiting (after the fault clears), the voltage is significantly
event is limited by the low thermal conductivity of high reduced and is observed to decay slowly with time. This
resistivity materials. Handling and manufacturing behaviour confirms the possibility of fast operational
constraints put a lower limit on the thickness of BSCCO recovery. The behaviour is consistent with numerical
HTS conductors. Therefore the specific surface area for simulations using the IV curves of Fig. 1 which imply a
heat exchange cannot be increased infinitely. There is no temperature rise in the wire remaining below the
physical lower limit to overall operational r.m.s. current superconducting critical temperature. The time until
density; however economic considerations suggests a complete restoration of superconductivity at the
target of 10 A/mm2 or higher. The thermal conductivity operational temperature, i.e. the ability to take overloads
of electrical insulation will limit the available cooling. without going normal-conducting, was about two
Reducing the voltage gradient (electric field) can reduce seconds. Measurements on improved samples of up to
the energy deposition per unit mass, however mass and 60 meters in length have since confirmed the feasibility
cost of the transformer will increase inversely with of fast operational recovery.
gradient.
No refrigeration machine will be able to remove heat at
the rate it is generated during a fault. Therefore an 2.2. Input to the transformer design
interim heat sink in the form of solid material or liquid When designing a current limiting device, one first
coolant being heated or evaporated has to be provided. selects the desired operating current and the desired
max. fault current. Assuming no electrical bypass the I-
2. SELF LIMITING WIRE V-curve yields the maximum voltage gradient along the
conductor. For a given operating voltage this determines
2.1. Proof of the self limiting effect the conductor length. In order to maintain a good current
limitation and long fault holding times one selects an
We designed an HTS conductor, capable of limiting a electrical bypass with high heat capacity and resistivity;
fault current to about 10 times critical current in the first equ. 1 can be used as a coarse check whether the desired
peak and to return to the superconducting state while fault holding time can be reached with the materials to
carrying a current of Ic after fault durations of several be used. Since the heat transfer is usually limited, equ. 2
100 ms. To achieve basic current limiting capability, can be used to adjust the overall operating current
silver was alloyed with a base metal to increase the density and the thickness of the conductor.
matrix resistivity of the BSCCO tape to the order of
several µΩ.cm. To achieve operational recovery
capability, this modified HTS tape was then soldered
between two metallic tapes of about ten times the
superconductor thickness.
-4-

3. IMPACT ON THE GRID current will be stopped (fault at Q).


Condition 2: The transformer must withstand a
3.1. Study of a HV/MV design short duration short-circuit but after the clearing of the
fault, it must be able to cool down although current from
Once the design is made, one of the most important
the non faulty feeders still flows. (fault at R).
tasks is to check whether the transformer is or may be
It appears from our study that the second condition
compatible with the existing protection scheme, in
seems the most difficult to fulfill.
particular in case of short circuit. From the above
chapters it appeared clearly that current limitation
The thermal behaviour of the transformer in case of
induces temperature increase in the wires.
short-circuit was studied using a dedicated simulation
tool. The calculations proved that in order to “recover”
Operational constraints, especially for HV/MV
its superconducting properties, the temperatures of the
transformers derive from network configuration (Fig. 3).
wires must not exceed the critical temperature (Tc
approx. = 110 K). This appears to be the criterion to
fulfil condition 2. Results of the simulations on a 10
MVA, uSC = 7,2 % (short circuit impedance) are given
in Fig. 5.

HV line
HV/M V

Circuit
Breaker Q
Q

CB R R
Feeders
Fig. 3: Standard HV/MV configuration

Two types of fault can be considered: busbar faults, i.e.


faults between Circuit-Breaker Q and Circuit-Breakers
R (cleared by CB Q) and feeder faults, that is faults
downstream CB R (cleared by CB R). According to the
state-of-the-art protection philosophy, CB Q is also
designed as the back-up protection for CB R. Currents
flowing in the transformer therefore are very different as
shown in Fig. 4:

I (A)

Short-circuit current
Fault atQ

Rated current Fault atR Fig. 5: Short circuit currents and temperature in the
windings
0
The main result from these calculations is that the first
peak is reduced to less than 9 p.u. and then 2.5 p.u. r.m.s
Fault 2 cleared Fault 1 cleared Time after 700 ms. A conventional transformer with uSC = 7.2
by CB 2 by CB 1
% would lead to a 13.9 p.u. r.m.s. short-circuit current
Fig. 4: Main and back-up protection principles
and to 34.8 p.u. (full asymmetry factor = 2.5) for the
first peak, to be compared to 9 p.u. Fault current
As a consequence, two conditions are necessary:
limitation is instantaneously efficient and leads to
Condition 1: The transformer must thermally reduced stresses on downstream devices during faults.
withstand a long duration short-circuit after which the
-5-

It was then found that the critical temperature (ca. 110 heavily loaded areas.
K) is reached in 580 ms. CB R must clear a fault in less
than 580 ms (condition 2). Condition 1 is reached if the The second example deals with a generation application.
short-circuit is cleared by CB Q in about 1s. The first part of this study showed the advantage in
terms of voltage stability for HTS FCL step-up
These maximum short-circuit durations are compatible transformers (uSC = 6 %) compared to conventional ones
with some protection scheme, but may appear as too (uSC = 14 %). Simulations were made in order to see the
short for other applications or other designs. These influence of the step-up transformer. Three faults were
durations are very design sensitive and may vary simulated: Case 1.1 and 1.2 close to the generator and
significantly, but our goal is to optimise the transformer case 2 a little bit further away, as shown in Fig. 6.
design to match the operational constraints. However,
technical progress toward numerical protection and
increased communication between circuit-breakers are
likely to make it possible to reduce the time needed for
protection to clear a fault. Moreover, Power Quality is case 2
becoming a very strong requirement from customers and Step-up
transformer
utilities and reducing fault duration is a part of the
answer to that problem. case 1.1 case 1.2
~
From a utility point of view, this current limitation
capability is one of the main interests for High 110 kV

Temperature Superconducting Transformer technology


because of the potential savings on downstream devices,
lines, cables... Other benefits are:
Fig. 6: Fault location
• Intrinsic characteristics of superconductivity:
environmentally friendly (no oil leak or fire The basic idea of the simulations is to determine the
hazard), more compact design. critical fault clearing time, that is the maximum allowed
• Reduced load losses. fault clearing time before the generator must be
• System benefits such as those described in § 3.2. disconnected from the network before losing stability.
The mechanical and electrical data of the machines as
3.2. System benefits well as the generator control have been set according to
real data. The course of the simulation is as follows: The
HTS fault current limiting transformers seem very machine initially operates at its rated power. At the
attractive from a utility point of view, in addition to the beginning of the simulation T0, a short circuit on the
above mentioned advantages. lines considered in each case is assumed, leading to a
voltage collapse close to the generator. After T1, the
A first study was performed for a real 110 kV circuit breaker of the line is triggered, so that the fault is
subtransmission network. It is given by a 110 kV loop removed. Critical clearing times are shown in table I.
fed by 4 transformers from the interconnected EHV
grid. Due to increased load demand in the network, Table I. Critical clearing times for the different faults
additional transformer power has to be installed. (ms) case 1.1 case 1.2 case 2
However even in the present system configuration, the Conventional 230 280 570
short-circuit fault currents are close to the substation transformer
HTS transformer 940 (∞) (∞)
ratings. A study was made, replacing one out of four
conventional transformers (uSC = 12-20 %, short circuit The main observation is that the resistive behaviour of
impedance) with a HTS fault current limiting the HTS step up transformer allows active power to be
transformer (uSC = 6 %) of the same rating. As a result, absorbed by the transformer during faults, thus
an additional gain of 10-30 % in short circuit power stabilizing the generator. The fault current limitation
(under normal load current) is achieved, without function in a step up transformer improves the transient
exceeding the admissible short-circuit current ratings, stability of the network.
thanks to the resistive limitation. If all of the four
transformers are replaced, a 50% short-circuit power
increase is expected in this loop and the short-circuit
current will be dramatically reduced (25 to 35 % at each
node). As a conclusion of this study, it appeared that
HTS fault current limiting transformers can be used to
increase the short circuit power in a loop without
increasing the short-circuit current. This is of interest for
-6-

4. CONCLUSION
G ~ Current limitation in High Temperature
Generator step-up transformer load Superconducting Transformers appears to be achievable,
120 MVA
using a self limiting and recovering HTS conductor.
Xd
RT
XT
Experimental proof of this effect was achieved on
several lengths. This capability is fully used in a
~ E U
Q
U
L
R L
X
L transformer and will lead to numerous advantages,
especially if protections are quick enough to clear faults
Fig. 7: Model network for step-up transformer study rapidly, avoiding overheating of the transformer.
Numerical protection and increased communication
An extra added value to the step-up HTS transformer between circuit-breakers will improve this situation very
application is related to power generation savings. The soon.
data of the generator are taken from an existing
generator and the network is described in Fig.7. The This paper illustrates examples of system benefits
impedance values during normal operation for the step- derived from this technology, such as reduced stresses
up transformers are : conventional [0.5% + j⋅14%], HTS on downstream devices, reduced load losses, more
[0.02% + j⋅6.0%]. The values assumed for normal compact transformers, increased voltage stability,
operation refer to all HTS transformer types with HRS reduced generator ratings … These benefits are already
wire and therefore reduced impedance in normal of common interests for both utilities and transformer
operation. manufacturers.

The comparison is based on the (conventional) rated 5. REFERENCES


operation point of generator for the conventional
[1] P.G. Thérond, C.Levillain, J.-F. Picard, B. Bugnon, H.
transformer, that is a rated power of 120 MVA at a Zueger, S. Hörnfeldt, T. Fogelberg, G. Papst, D.
power factor cosϕ of 0.8 (inductive). The values for the Bonmann, High Temperature 630 kVA Superconducting
active and reactive power behind the transformer for Transformer, CIGRE 1998, Paris, session paper 12-302
both types are given in table II:

Table II. Active and reactive power for both


transformers at generator and load locations
Conventional HTS
transformer transformer
location generator load generator load
Sr 120 111.2 115.5 111.2
(MVA)
Cos ϕ 0.80 0.86 0.83 0.86
P 96 95.5 95.5 95.5
(MW)
Q 72 57 65 57
(MVAR)

These results show, for the same power injection at the


PCC (Point of Common Coupling), a rated generator
(apparent) power of only 96.25 %. Alternatively, more
active power can be drawn from a given generator.
When operating the generator with the same (maximum)
voltage in both cases, this reduces the stator current by
the same percentage. This means a reduction of the
stator losses of 7.4 %. Alternatively, the reduced stator
currents can also be used for reduced cross-sections, but
the saved investments will be in the same order of
magnitude as the saved losses.

These two examples show the benefits for transmission


as well as generation applications of intrinsic current
limiting function of High Temperature Superconducting
transformers.

You might also like