FIELD CONNECTIONS DIAGRAM


FOR YMC2 MODEL A CHILLER
WITH M1 COMPRESSOR
WIRING DIAGRAMS
CONTRACTOR ________________________ PURCHASER _____________________________________________
ORDER NO. ___________________________ JOB NAME _______________________________________________
YORK CONTRACT NO. __________________ LOCATION _______________________________________________
YORK ORDER NO. _____________________ ENGINEER ______________________________________________

REFERENCE DATE _______ APPROVAL DATE________ CONSTRUCTION DATE ________

JOB DATA:

CHILLER MODEL NO. YMC2____________________ NO. OF UNITS_______________________________

MOTOR/VARIABLE SPEED DRIVE POWER: 460V, 60Hz; 380V, 60Hz; 415V, 50Hz or 400V, 50Hz

Issue Date:
July 31, 2018
FORM 160.78-PW1
ISSUE DATE: 7/31/2018

IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or
During rigging, installation, operation, maintenance, death to themselves and people at the site.
or service, individuals may be exposed to certain com-
ponents or conditions including, but not limited to: This document is intended for use by owner-authorized
heavy objects, refrigerants, materials under pressure, rigging, installation, and operating/service personnel. It
rotating components, and both high and low voltage. is expected that these individuals possess independent
Each of these items has the potential, if misused or training that will enable them to perform their assigned
handled improperly, to cause bodily injury or death. It tasks properly and safely. It is essential that, prior to
is the obligation and responsibility of rigging, instal- performing any task on this equipment, this individual
lation, and operating/service personnel to identify and shall have read and understood the on-product labels,
recognize these inherent hazards, protect themselves, this document and any referenced materials. This in-
and proceed safely in completing their tasks. Failure dividual shall also be familiar with and comply with
to comply with any of these requirements could result all applicable industry and governmental standards and
in serious damage to the equipment and the property in regulations pertaining to the task in question.

SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to areas of potential hazard:

DANGER indicates an imminently CAUTION identifies a hazard which


hazardous situation which, if not could lead to damage to the machine,
avoided, will result in death or seri- damage to other equipment and/or
ous injury. environmental pollution. Usually an
instruction will be given, together with
a brief explanation.

WARNING indicates a potentially NOTE is used to highlight additional


hazardous situation which, if not information which may be helpful to
avoided, could result in death or seri- you.
ous injury.

External wiring, unless specified as an optional connection in the manufacturer’s product


line, is NOT to be connected inside the equipments cabinet. Devices such as relays, switches,
transducers and controls may NOT be installed inside the equipments panel. NO external
wiring is allowed to be run through the panel. All wiring must be in accordance with YORK/
Johnson Controls published specifications and must be performed ONLY by qualified YORK/
Johnson Controls personnel. Johnson Controls will not be responsible for damages/problems
resulting from improper connections to the controls or application of improper control sig-
nals. Failure to follow this will void the manufacturer’s warranty and cause serious damage
to property or injury to persons.

2 JOHNSON CONTROLS
FORM 160.78-PW1
ISSUE DATE: 7/31/2018

CHANGEABILITY OF THIS DOCUMENT


In complying with Johnson Controls’ policy for con- regarding the applicability of these documents, rig-
tinuous product improvement, the information con- ging, lifting, and operating/service personnel should
tained in this document is subject to change without verify whether the equipment has been modified and
notice. Johnson Controls makes no commitment to if current literature is available from the owner of the
update or provide current information automatically equipment prior to performing any work on the chiller.
to the manual or product owner. Updated manuals, if
applicable, can be obtained by contacting the nearest
CHANGE BARS
Johnson Controls Service office or accessing the John-
Revisions made to this document are indicated with
son Controls QuickLIT website at http://cgproducts.
a line along the left or right hand column in the area
johnsoncontrols.com.
the revision was made. These revisions are to technical
It is the responsibility of rigging, lifting, and operating/ information and any other changes in spelling, gram-
service personnel to verify the applicability of these mar or formatting are not included.
documents to the equipment. If there is any question

TABLE OF CONTENTS

FIGURE 1 - Grounding VSD (490A)��������������������������������������������������������������������������������������������������������������������������4


FIGURE 2 - Grounding VSD (744A)��������������������������������������������������������������������������������������������������������������������������6
FIGURE 3 - Variable Speed Drive (490A)�����������������������������������������������������������������������������������������������������������������8
FIGURE 4 - Variable Speed Drive (744A)�����������������������������������������������������������������������������������������������������������������9
FIGURE 5 - Field Connections��������������������������������������������������������������������������������������������������������������������������������10

JOHNSON CONTROLS 3
FORM 160.78-PW1
ISSUE DATE: 7/31/2018

VARIABLE SPEED DRIVE (490A)


NOTES:
1. All field wiring shall be done in accordance with the 4. Items marked * furnished by Johnson Controls.
NEC codes listed within this manual. NEC articles 5. Items marked ** available from Johnson Controls at
and paragraphs cited are for reference only and may additional cost.
not be current NEC code. 6. Control power supply 115V - 50/60 Hz, 2.0 KVA
2. capacity for control center only, is supplied by (1)-2.0
PROPER GROUNDING IS REQUIRED: KVA control power transformers (1T) mounted Inside
the VSD, they are factory wired.
7. A removable cover plate with pilot knockouts is sup-

plied for connection of power supply conduits. VSD
• Variable Speed Drive (VSD) shall be grounded in ac-
power conduit connection removable cover plate (cut
cordance with the 2017 NEC (Paragraph 250.118).
holes to suit) locations per Figure 3 on page 8.
• Ground wires must be copper only and sized per Flexible conduit must be used for final connections
the NEC See Table 250.122. to VSD. Multiple conduits shall contain an equal
• A separate grounding conductor shall be run in each number of wires from each phase in each conduit
conduit or for each 3 phase bundle within a cable to prevent overheating per the 2017 NEC (Para-
tray. See Figure 1 on page 4. graph 300-20(a)). Use copper conductors only;
• Each ground wire shall be connected directly be- DO NOT USE aluminum conductors. See Table 1
tween the supply transformer’s secondary ground on page 4 for factory furnished VSD terminal lug
and the VSD ground lug. wire ranges and conduit connection provisions.
8. The following terminal lugs are factory furnished for
• Flexible conduit is required for final connection to
field wiring supply connections. All lugs are rated
the VSD for vibration isolation.
AL9CU.
• Conduit is not an acceptable grounding means. 9. Condenser water pump motor starter (3M) holding
• See Table 1 on page 4 for VSD ground lug siz- coil to be furnished for 115V - 50/60 Hz. The power
ing. require­ments for the water pump starter (3M) must be
3. Wiring, electrical conduit, junction boxes, fused dis- a max. of 1 Amp holding and 10 Amps inrush. If power
connect switches (FDS), or circuit breakers, starters requirements exceed this value, furnish coil for line
(M), pushbutton stations (PB), manual-off-automatic voltage, and control relay with 115V coil (see Note 20).
switch (S), flow switch (FLS), and control relays fur-
nished by others unless otherwise specified.

Table 1 - LUG DETAILS


Input Voltage/ Line Side Lugs Grounding Lug
Option Wire Range
Frequency BBL Per Terminal Wire Range, Qty.
380/460 60 Hz
Circuit Breaker 2 2/0 - 350 mcm #14-2/0, 2 bbl
400/415 50 Hz
380/460 60 Hz
Disconnect 2 2/0 - 350 mcm #14-2/0, 2 bbl
400/415 50 Hz

Phase A* A
Conduit
B
C
Transformer VSD Ground
Terminal Phase B* Terminal
Conduit
Each conduit shall contain a copper conductor
Block Block of each phase and a copper ground wire.
Phase C*
Neutral (if applicable)
C G C G C G C G
A B A B A B A B

Ground Ground
Wire tray shall contain bundles of copper wire with
*See Note 7. one conductor per phase and a copper ground
wire in each bundle.

LD27401

Figure 1 - GROUNDING VSD (490A)

4 JOHNSON CONTROLS
FORM 160.78-PW1
ISSUE DATE: 7/31/2018

VARIABLE SPEED DRIVE (490A)


10. Automatic control of the chilled water pump by the 18.The minimum value of line impedance shall be
control center is shown. Chilled water pump motor determined by the case in which the VSD is fed from
starter (5M) holding coil to be furnished for 115V a transformer whose kVA rating is equal to 5 times
– 50/60 Hz. The power requirements for the water rated power of the VSD. The transformer shall be
pump starter (5M) must be a maximum of 1 Amp specified to have 3% impedance. The supply volt-
holding and 8 Amps inrush. If power requirements age, at VSD input terminals, during start-up must
exceed this value, furnish coil for line voltage, and be maintained above 391 volts for 440V/460V/480V
control relay with 115V coil (see Note 20). 60 Hz units, above 323 volts for 380V/400V 50/60
• The pumps operate during com­pressor operation Hz units, above 353 volts for 415V 50 Hz units. The
& during cycling shutdown. following Table provides allowable supply voltage
range during normal operation.
• For manual chilled water pump control, connect
a manual start/stop switch as shown in the Field Table 3 - VOLTAGE RANGES
Connections diagram for 115VAC coils only.
Input Voltage Voltage Range
Table 2 - CONDUIT DETAILS 380/400V 50/60 Hz 342-423
Input Voltage/ Chiller Motor Max. No. of 415V 50 Hz 374-456
Frequency Code Conduits 440/460V 60 Hz 414-508
380/460 60 Hz 19.Maximum line voltage imbalance (calculated as
M1 (2) 3 in.
400/415 50 Hz the difference between any of the three line volt-
11. Units shipped knocked down require field connection ages and the average of the three line voltages,
of harnesses to control center, power wiring between and multiplied by 100%) will be 5%. Maximum line
compressor motor and VSD. These harnesses and voltage total harmonic distortion (THD) will be 5%
power wiring are furnished by Johnson Controls for per phase (from n=2nd to n=50th harmonic) when
field assembly and consist of proper lengths of flex- line impedance is specified as follows:
ible conduit with necessary con­nectors, and contain • Minimum value of line impedance will be deter-
the wires (shown in Note 12) prop­erly terminated mined by the case in which the VSD is fed from a
and marked. transformer whose kVA rating is equal to 5 times
12. Wire #14 AWG copper for one way distance of less the rated power of the VSD. The transformer will
than 175 feet. Wire #12 AWG copper for one way be specified to have 3% impedance.
distance of more than 175 feet, but less than 300 • Maximum value of line impedance will be deter-
feet. mined by the case in which the VSD is fed from a
13. Wiring diagram for YORK control center and Field transformer whose kVA rating is equal to the rated
Control Modifications Form 160.78-PW2. power of the VSD. The transformer will be specified
15.The branch circuit overcurrent protection device for to have 7% impedance.
the YORK VSD must be a time delay type with a The VSD will comply with IEEE Std. 519-1992 sec-
rating which is the standard fuse/circuit breaker size tion 10.3.
required to pro­tect the field supply wiring conduc- 20. Each 115VAC field-connected inductive load, i.e. relay
tors per the N.E.C. coil, motor starter coil, etc. will have a transient
16. The YORK Variable Speed Drive power supply wiring suppressor wired (by others) in parallel with its coil,
ampacity shall be calculated as follows. physically located at the coil. Spare transient sup-
Model YMC2 minimum circuit ampacity: pressors are factory sup­plied in a bag attached to the
keypad cable clamp in the OptiView Control Center.
Ampacity = 1.25 (Job FLA)
21. All switches and circuit breakers used as switches
Where 125% factor per 2008 N.E.C. (Para. 440-33).
will be located so they may be operated from a read-
17. The VSD is equipped with a U.L. Listed rotary discon- ily accessible place. They will be installed per 2008
nect switch or optional circuit breaker. In both cases, N.E.C. (Para. 404.8).Switches and circuit breakers
fast acting semiconductor fuses, downstream of installed adjacent (close-coupled) to motors, appli-
the disconnecting device, to provide additional ances, or other equipment that they supply shall be
protection to the VSD. Ground fault is employed on permitted to be located higher than 6'-7" (2m) and
both circuit breaker and disconnect switch models to be accessible by portable means per 2008 N.E.C.
via the VSD logic control board using a hall effect (Para. 404.8 Exception No. 2).
current sensor one per phase. Ground fault protec-
tion is also provided as part of the circuit breaker
protection.

JOHNSON CONTROLS 5
FORM 160.78-PW1
ISSUE DATE: 7/31/2018
VARIABLE SPEED DRIVE (744A)
NOTES:
1. All field wiring shall be done in accordance with the 4. Items marked * furnished by Johnson Controls.
NEC codes listed within this manual. NEC articles 5. Items marked ** available from Johnson Controls at
and paragraphs cited are for reference only and may additional cost.
not be current NEC code. 6. Control power supply 115V - 50/60 Hz, 4.0 KVA
2. capacity for control center only, is supplied by (2)-2.0
PROPER GROUNDING IS REQUIRED: KVA control power transformers (1T)/(2T) mounted
outside the VSD, they are factory wired.
7. A removable cover plate with pilot knockouts is sup-

plied for connection of power supply conduits. VSD
• Variable Speed Drive (VSD) shall be grounded in ac-
power conduit connection removable cover plate (cut
cordance with the 2017 NEC (Paragraph 250.118).
holes to suit) locations per Figure 4 on page 9.
• Ground wires must be copper only and sized per Flexible conduit must be used for final connections
the NEC See Table 250.122. to VSD. Multiple conduits shall contain an equal
• A separate grounding conductor shall be run in each number of wires from each phase in each conduit
conduit or for each 3 phase bundle within a cable to prevent overheating per the 2017 NEC (Para-
tray. See Figure 2 on page 6. graph 300-20(a)). Use copper conductors only;
• Each ground wire shall be connected directly be- DO NOT USE aluminum conductors. See Table 4
tween the supply transformer’s secondary ground on page 6 for factory furnished VSD terminal lug
and the VSD ground lug. wire ranges and conduit connection provisions.
8. The following terminal lugs are factory furnished for
• Flexible conduit is required for final connection to
field wiring supply connections. All lugs are rated
the VSD for vibration isolation.
AL9CU.
• Conduit is not an acceptable grounding means. 9. Condenser water pump motor starter (3M) holding
• See Table 4 on page 6 for VSD ground lug siz- coil to be furnished for 115V - 50/60 Hz. The power
ing. require­ments for the water pump starter (3M) must be
3. Wiring, electrical conduit, junction boxes, fused dis- a max. of 1 Amp holding and 10 Amps inrush. If power
connect switches (FDS), or circuit breakers, starters requirements exceed this value, furnish coil for line
(M), pushbutton stations (PB), manual-off-automatic voltage, and control relay with 115V coil (see Note 20).
switch (S), flow switch (FLS), and control relays fur-
nished by others unless otherwise specified.

Table 4 - LUG DETAILS


Input Voltage/ Line Side Lugs Grounding Lug
Option Wire Range
Frequency BBL Per Terminal Wire Range, Qty.
380/460 60 Hz
Circuit Breaker 4 4/0 - 500 mcm #4-500 mcm, 4 bbl
400/415 50 Hz
380/460 60 Hz
Disconnect 4 #2 - 600 mcm #4-500 mcm, 4 bbl
400/415 50 Hz

Phase A* A
Conduit
B
C
Transformer VSD Ground
Terminal Phase B* Terminal
Conduit
Each conduit shall contain a copper conductor
Block Block of each phase and a copper ground wire.
Phase C*
Neutral (if applicable)
C G C G C G C G
A B A B A B A B

Ground Ground
Wire tray shall contain bundles of copper wire with
*See Note 7. one conductor per phase and a copper ground
wire in each bundle.

LD27401

Figure 2 - GROUNDING VSD (744A)

6 JOHNSON CONTROLS
FORM 160.78-PW1
ISSUE DATE: 7/31/2018
VARIABLE SPEED DRIVE (744A)

10. Automatic control of the chilled water pump by the determined by the case in which the VSD is fed from
control center is shown. Chilled water pump motor a transformer whose kVA rating is equal to 5 times
starter (5M) holding coil to be furnished for 115V rated power of the VSD. The transformer shall be
– 50/60 Hz. The power requirements for the water specified to have 3% impedance. The supply volt-
pump starter (5M) must be a maximum of 1 Amp age, at VSD input terminals, during start-up must
holding and 8 Amps inrush. If power requirements be maintained above 391 volts for 440V/460V/480V
exceed this value, furnish coil for line voltage, and 60 Hz units, above 323 volts for 380V/400V 50/60
control relay with 115V coil (see Note 20). Hz units, above 353 volts for 415V 50 Hz units. The
• The pumps operate during com­pressor operation following Table provides allowable supply voltage
& during cycling shutdown. range during normal operation.
• For manual chilled water pump control, connect Table 6 - VOLTAGE RANGES
a manual start/stop switch as shown in the Field
Input Voltage Voltage Range
Connections diagram for 115VAC coils only.
380/400V 50/60 Hz 342-423
Table 5 - CONDUIT DETAILS 415V 50 Hz 374-456
Input Voltage/ Chiller Motor Max. No. of 440/460V 60 Hz 414-508
Frequency Code Conduits 19.Maximum line voltage imbalance (calculated as
380/460 60 Hz the difference between any of the three line volt-
M1 (4) 3 in.
400/415 50 Hz ages and the average of the three line voltages,
11. Units shipped knocked down require field connection and multiplied by 100%) will be 5%. Maximum line
of harnesses to control center, power wiring between voltage total harmonic distortion (THD) will be 5%
compressor motor and VSD. These harnesses and per phase (from n=2nd to n=50th harmonic) when
power wiring are furnished by Johnson Controls for line impedance is specified as follows:
field assembly and consist of proper lengths of flex- • Minimum value of line impedance will be deter-
ible conduit with necessary con­nectors, and contain mined by the case in which the VSD is fed from a
the wires (shown in Note 12) prop­erly terminated transformer whose kVA rating is equal to 5 times
and marked. the rated power of the VSD. The transformer will
12. Wire #14 AWG copper for one way distance of less be specified to have 3% impedance.
than 175 feet. Wire #12 AWG copper for one way • Maximum value of line impedance will be deter-
distance of more than 175 feet, but less than 300 mined by the case in which the VSD is fed from a
feet. transformer whose kVA rating is equal to the rated
13. Wiring diagram for YORK control center and Field power of the VSD. The transformer will be specified
Control Modifications Form 160.78-PW2. to have 7% impedance.
15.The branch circuit overcurrent protection device for The VSD will comply with IEEE Std. 519-1992 sec-
the YORK VSD must be a time delay type with a tion 10.3.
rating which is the standard fuse/circuit breaker size 20. Each 115VAC field-connected inductive load, i.e. relay
required to pro­tect the field supply wiring conduc- coil, motor starter coil, etc. will have a transient
tors per the N.E.C. suppressor wired (by others) in parallel with its coil,
16. The YORK Variable Speed Drive power supply wiring physically located at the coil. Spare transient sup-
ampacity shall be calculated as follows. pressors are factory sup­plied in a bag attached to the
Model YMC2 minimum circuit ampacity: keypad cable clamp in the OptiView Control Center.
Ampacity = 1.25 (Job FLA) 21. All switches and circuit breakers used as switches
will be located so they may be operated from a read-
Where 125% factor per 2008 N.E.C. (Para. 440-33).
ily accessible place. They will be installed per 2008
17. The VSD is equipped with a U.L. Listed rotary discon- N.E.C. (Para. 404.8).Switches and circuit breakers
nect switch or optional circuit breaker. In both cases, installed adjacent (close-coupled) to motors, appli-
fast acting semiconductor fuses, downstream of the ances, or other equipment that they supply shall be
disconnecting device, to provide additional protec- permitted to be located higher than 6'-7" (2m) and
tion to the VSD. Ground fault is employed on both to be accessible by portable means per 2008 N.E.C.
circuit breaker and disconnect switch models via the (Para. 404.8 Exception No. 2).
VSD logic control board using a hall effect current
sensor one per phase. Ground fault protection is
also as part of the circuit breaker protection.
18.The minimum value of line impedance shall be

JOHNSON CONTROLS 7
FORM 160.78-PW1
ISSUE DATE: 7/31/2018
VARIABLE SPEED DRIVE (490A)
VSD Circuit Breaker Semiconductor
Input Voltage/ Chiller Rating @ 480VAC, 60 Hz Fuse Rating Ground
Frequency Motor Code or 400VAC, 50 Hz (Amps) @ 660 Fault Trip
Trip Withstand VAC
380/460 60 Hz
M1 450A 100,000*† 550A 40A
400/415 50 Hz
* Per U.L. Listing of VSD
† RMS Symmetrical Amperes

TOP VIEW

25-1/4"
(638mm)

26-3/8" 24-1/4" 9"


(670mm) (616mm) (229mm)
4-1/2"
INPUT (112mm)

APPROX. OVERALL OF DOOR APPROX. OVERALL OF DOOR


1-1/8"
(28.5mm) 21-1/2" 31"
(546mm) (787mm)
55-1/4"
(1403mm)

FRONT VIEW

CIRCUIT
BREAKER
38-1/8" (OPTIONAL)
(968mm)

SEE
NOTE
15-1/8" 21
(384mm)

14-1/4" DISCONNECT
(363mm) SWITCH

LD14634

Figure 3 - VARIABLE SPEED DRIVE (490A)

8 JOHNSON CONTROLS
FORM 160.78-PW1
ISSUE DATE: 7/31/2018
VARIABLE SPEED DRIVE (744A)
VSD Circuit Breaker Semiconductor
Input Voltage/ Chiller Rating @ 480VAC, 60 Hz Fuse Rating Ground
Frequency Motor Code or 400VAC, 50 Hz (Amps) @ 660 Fault Trip
Trip Withstand VAC
380/460 60 Hz
M1 800A 100,000*† 800A 80A
400/415 50 Hz
* Per U.L. Listing of VSD
† RMS Symmetrical Amperes

TOP VIEW

25-1/4"
(638mm)
16-1/4"
26-3/8" 24-1/4" (412mm)
(670mm) (616mm)

INPUT 8"
(203)

APPROX. OVERALL OF DOOR APPROX. OVERALL OF DOOR


1-1/8"
(28.5mm) 25" 33-1/2"
(635mm) (851mm)
61-1/4"
(1555mm)

FRONT VIEW

CIRCUIT
BREAKER
(OPTIONAL)
51"
(1295mm)

SEE
NOTE
18-3/8"
21
(466mm)

14-1/8" DISCONNECT
(466mm) SWITCH

LD14634

Figure 4 - VARIABLE SPEED DRIVE (744A)

JOHNSON CONTROLS 9
FORM 160.78-PW1
ISSUE DATE: 7/31/2018

FIELD CONNECTIONS

FIELD SUPPLIED

FDS5 FDS3

3LL2
3LL1

3LL3
5LL3
5LL2
5LL1
5M 3M S
SEE AUTO
NOTE

OFF
SUPR 21 MAN

SUPR
SEE
NOTE
NOTE 21
SEE 9
5T3
5T2
5T1

3T2
3T1

3T3
NOTE
20

CHILLED
WATER
PUMP
MOTOR
WIRE # 14 AWG CONDENSER WATER
COPPER PUMP MOTOR
NOTES 11 & 18

WIRE
# 14 AWG TB4* TB2*
COPPER 1 95 1 82 11 1 31 9 1 13 12 1 20 19 1 8 7 1 44 45 55 56 26 27 42 43 40 41 150 151

NOTE 11
1
1

OPTIVIEW CONTROL CENTER *

GRD. SCREWS*

LD14566

Figure 5 - FIELD CONNECTIONS

10 JOHNSON CONTROLS
FORM 160.78-PW1
ISSUE DATE: 7/31/2018

FIELD CONNECTIONS (CONT'D)

POWER SUPPLY (NOTE 19)


L1 VOLT
L2 PHASE 3
L3 HERTZ
FIELD SUPPLIED
FDS4 FDS2**
NOTES 5 & 15
4LL2

2LL2
4LL1

4LL3

2LL1

2LL3
4M
4T2
4T1

4T3

NOTE 7, 16
COPPER CONDUCTORS ONLY
DO NOT USE ALUMINUM
COOLING TOWER
CONDUCTORS.
FAN MOTOR

NOTE 8
GRD L1 L2 L3
TB2* TB6*
152 153 154 155 156 157 164 36 35 5 3 4 15 16 24 25 53 1 1 1 1 L L L 2 2 2 2 NOTES 2 & 8

1
1
2M
2 YORK VSD
1T* CHILLER MOTOR
2

WIRE #14 AWG


COPPER, NOTE 11
OPTIVIEW CONTROL CENTER * NOTES 4 & 6

T1 T2 T3

T1* T2* T3*

COMPRESSOR MOTOR*
LD14567

FIGURE 5 - FIELD CONNECTIONS (CONT'D)

JOHNSON CONTROLS 11
5000 Renaissance Drive, New Freedom, Pennsylvania USA 17349 800-861-1001 Subject to change without notice. Printed in USA
Copyright © by Johnson Controls 2018 www.johnsoncontrols.com ALL RIGHTS RESERVED
Form 160.78-PW1 (718)
Issue Date: July 31, 2018
Supersedes: 160.78-PW1 (615)