Nature Test Item Process

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

H5161.11-1.0.

2 Communication system combined with equipments installation


1.0.1 The installation quality acceptance of a combined capacitor, a radiotona, a combination filter is used.
1.0.2 Mi-switched capacitors, cibo device, and bay wave device for cold assembly acceptance shall comply with the provisions of Table 1.0.2

Project Number Table Number

Installation location

Quality standard
Quality standard
Process Test item Nature Single conclusion
Results
A B C

Model Meet the design document requirements

Serial number

Visual Inspection No damage

Sealed chair Master No leakage


Precision
Flange bolt connection Master Tighten
capacitor
The ratio of the three main related fish < 5%
Master
to the average

Lead connection Good

ground Good

Meet the requirements of design


Model
documents

Serial number
visual inspection No damage
Stop wave
Level check Basically

Post insulator appearance Intact and evenly stressed


Internal capacitor Good contact, fixed
1 offline connection Good contact, fixed firmly
6 south Meet the design document requirements

By factory abbreviation

Combine Visual inspection No damage


filter
Fixed installation Firm and upright

set up connection Good contact, fixed firmly

Acceptance Conclusion:

Acceptance unit Signature

Construction unit

Supervision unit
H5161.11Form-2Microwave antenna installation
2.0.1 This chapter applies to the installation quality acceptance of microwave antennas
2.0.2 Microwave antenna installation quality acceptance should met the requirements of Table 2.0.2
Single item
Process Test Item Nature Quality Standard Quality acceptance
result

Antenna Mounting The location is coorect, install the jail


installation
Antenna and base connection Fixed prison garden, not relative to swing
Antenna azimuth, elevation
Master Meet the requirements of design documents
angle adjustment
Main Reflection and assembly
Seams are flush and even
of assembled antenna
Antenna Horn radiator Bonding park
Adjustment
Protective cover for main
Installed correctly, with even force
reflecting surface
Polarization direction of
Master Meet the requirements of design documents
antenna inertia
Antenna feed and waveguide
Meet the feeder trend requirements
interface
Reasonable reinforment, free from external
Antenna feed installation
force
Connecting surface of each
Clean, good contact
component of antenan feed

Antenna focal length Correct

Antenna receiving field


Meet the requirements of design documents
emphasis
Acceptance Conclusion:

Acceptance signature unit

Construction unit

Supervision unit
H5161.11-Form-3 Microwave feeder installation
3.0.1 This chapter applies to the Installation quality acceptance of ding Microwave performance line.
3.0.2 The installation quality acceptance of the microwave performance line shall meet the requirements of table

Test Item single item


Process Nature Quality standard Quality standard
result

straight without distortion or


Feeder inspection
cracks
Neat and beautiful, no
Hungry line laying appearance
crossover
Feeder reinforcement force point
On the waveguide flange
announcement

Feeder laying Rectangular hard waveguide


2m
feeder
Change line
reinforcement Round hard waveguide feeder 3m
spacing
Elliptical flexible Waveguide
1m~1.5m
feeder
Meet the requirements of
Slow wire bending radius and torsion inspection Master
product techincal documents
Adjustable Length error
waveguide
section Welding inspection
Feeder gas closed test
Cutting, cutting and flanging inspection of RF
coaxial cable
Hungry wire grounding inspection
Acceptance Conclusion:

Acceptance signature unit

Construction unit

Supervision unit
H5161.11-Form 4 Communication equipment installation
4.0.1 This chapter applies to the installation quality acceptance of communication equipment
4.0.2 The installation quality acceptance of communication equipment shall meet the requirements of Table
Single item
Process Test Item Nature Quality standard Quality acceptance
conclusion
Meet the requirements of
Subrack panel has
design documents
The position is correct, the
Subrack installation
hanging column is neat
Subrack delivery
Plug in for inspection Good contact

Network management equipment Meet the requirements of design


installation documents
Corresponding to the cypress on
Main distribution frame installation the end of the cable, because it
is stable and reliable

The location meets the


Distrinution Patch panel wiring board installation requirements of the design
frame documents and the sign are complete

Neatly, with moderate lashing


Digital distribtion frame jumper
tightness
Protection audio interface installation Good contact
Correct deployment, beautiful
Cable routing between sockets
craftsmanship
Cable routing Power Cable Deploy separately

Cable channel Horizontal and straight

Optical fiber cable bending radius Master >40mm

Fiber optic Straight muscles, no ancestral


Optical fiber braided wiring
connection hair
Binding withsoft material, no
Fiber binding
indentation

Coaxial cable layer size Compatibel with cable plug

Core wire welding Master Upright and firm

Complete accessories and firm


Coaxial cable plug assembly
Cable termination assembly
and protection
The length of the split head is
Shielded wire end treatment
consistent and the contact is good

The length of the heat shrinkable


Heat shrinkage treatment tube is moderate, and the shrinks
evenly
Indentification
Signs, labels Accurate, clear and neat
label
Acceptance Conclusion:

Acceptance signature unit

Construction unit

Supervision unit
H5161.11-Form5 Communication system Free maintenance cover battery installation
5.0.1 This chapter applies to the installation quality acceptance of the communication system
5.0.2 This chapter applies the system exchanger installation quality inspection meets the provisions of Table

Single item
Process Test Item Nature Quality Standard Quality acceptance
conclusion

Screen(set) multiplication
<1.5mm/m
Straightness error

Listed item level is said to be


<3mm
World phase poor
installation
Discord <2mm

Check value of disc gap <2mm

disk inspection Smooth, no rusty paint

New battery pack model Meet the requiements of design


Master
specifications documents
Battery visual inspection Elimination without leakage

Saftey valve inspection Intact without falling off

Channel steel fixing Firm

Bottom battery installation Correct polarrity connection


Battery pack
installation Top layer installaiton Correct polarity connection
inspection
Conductive connection surface
Coating power compound grease
treatment
Positive and negative screw
Tight, good contact
connection

Leading line color Positive ladder color, negative blue

Battery number correct, neat handwriting

Battery change and


Battery Charge and discharge
discharge test Master Complete
test record documents
record
Acceptance Conclusion:

Acceptance signature unit

Construction unit

Supervision unit
H5161.11-Form.6 Rack mount
6.0.1 This chapter applies to the installation quality acceptance of the rack
6.0.2 The quality acceptance of rack installation shall meet the requirements of Table

Installation location

Single
Construciton project Nature Quality standard Quality acceptance result
conclusion

Meet the requirements of design


Rack model verification
documents

Frame vertical error <3mm

Inter-rack team <3mm

Error between rows <5mm

Frame ground Master Reliable connection

Rack inspection Good appearance, conplete parts

Rack mount Fasten

Rack identification Accurate and neat

Machine installation Correctly located and neat

Alignmnet of the trip, all sign,


Terminal equipmnet installation Master
correct

Acceptance Conclusion:

Acceptance signature unit

Construction unit

Supervision unit
H5161.11-Form7 Communication optical cable installation in the station
7.0.1 This chapter applies to the quality acceptance of linen installation of communication optical cables in the station
7.0.2 The Installation quality acceptance of the communication optical cablein the station shall meet the requirements of Table

Installation location

Quality Single
Process Test Item Nature Quality acceptance
standard conclusion

Lead down cable fixed Take a beautiful, uniform card


OPGW(Fiber composite Cable ground Master Reliably
overhead floor)
Band radius >40 Betal cable diameter

Width cable stand Fixed reliability


Width cbale stand
Keeper Neat and orderly, bundling point>4

The material meets the design


Plug Master document requirements, which is
sealed
Guide cable
An all protection and fixed Designed to design files

Bend radius >25 diameter

pickup the box Parking and sealing Garden is a strong park

Sign Standard Clear, half garden


Acceptance Conclusion:

Acceptance signature unit

Construction unit

Supervision unit
H5161.11-Form8 Lightning protection grounding installation of communication station (system)
8.0.1 This suitable for the acceptance of the installation quality of lightning protection grounding of communication stations(system)
8.0.2 The acceptance of the lightning protection grounding installation quality of the communication station(system)

Single item
Process Test Item Nature Quality standard Quality acceptance
result

Lightning rod(band) is conencted


Master Reliable, good contact
to the down conductor
Down conductor and pressure
Reliable, good contact
equalizing belt connection
Lightning protection Communication station ground Meet the requirements of design
grouding bus specifications documents

Ground resistance Qualified

Anti-corrosion measures for Galvanized, anti-corrosion treatment after


grounding bus welding

2 Points and aboev, the grounding bus


Number of connection points
and the grounding body are welded firmly,
between ground bus and Master
and the welding seam is treated with
grounding grid
anti-corrosion
The grounding bus bar is closed into aring,
the crosssection of the copper bar is 90mm,
Grounding device in communication
and the cross section of the galvanized flat
steel is 120mm

At least two points are grounded, and the


Cable support ground
distance between the ground points is 30m

Negative DC power supply positive


Directly grounded
power supply side ground

Negative DC power supply positve


communication equipmnet side Directly grounded
grounding
Working and
protective DC lock wire shielding layer in
Directly grounded
grounding computer roon
Cable shield Ground at both ends

Before the armored cable enters the


Ground simultaneously
computer room, install an dshield

Switch, dispactching switchboard


Good grounding
metal rack
Main distribution frame, security
Good grounding
wiring registation
Communication AC and DC screen and
Good grounding
rectifier metal frame
Each device and ground bus Singe direct connection
Microwave station grounding bus and
Separate connection nearby
grounding grid
Grounding bus and grounding grid of
Separate connection nearby
communication station
Each line of audio cable Findground on the patch panel
Acceptance Conclusion:

Acceptance signature unit


Construction unit
Supervision unit

You might also like