Calculation of Design Moment Storey: 1
Calculation of Design Moment Storey: 1
Storey: 1
For column C26 (B1)
Unsupported Length(L) = 2.803 m
Depth of column: D= 450 mm
Width of column: B= 450 mm
Pu= 2404.5995 KN
End
moment
eminx= 𝑙/500+ End moment Minimum
Initial moment Mi Design moment
Bottom Top Mu2 moment
𝐷/30= (KNm) Mu (KNm)
Mu1 (KNm) Mmin (KNm)
eminy= 𝑙/500+
(KNm)
𝐵/30=
M uy -383.0218 143.1711 49.5492 -172.54464 -383.0218
Mux -91.1238 51.4239 49.5492 -36.44952 -91.1238
20.606 mm >20 OK
20.606 mm >20 OK
Also,
0.05*D = 22.5 mm >eminx
0.05*B = 22.5 mm >eminy
Mminx= Pu*eminx
= 49.5492 KN-m
Mminy= Pu*eminy
= 49.5492 KN-m
Design Moment(Mu)
max min
57.26844 -172.54464
20.56956 -36.44952
-172.54464
-36.44952
Mix =
Design of Column
FLEXURAL ANALYSIS OF COLUMN
91.1238KNm
450mm
383.022KNm
450mm
Calculated previously
Muy= -383.0218 KN-m
Mux= -91.1238 KN-m
So,
" )/𝑙
=l =
effx 2.034 m
leffy=
1.950 m
IS 456 : 2000 cl.25.1.2
λx="leffx " 4.52 <12 Short Column
/𝑙 =
λx="leffy " 4.33 <12 Short Column
/𝑙=
l= Least lateral dimension
Now,
d'
0.1
D
D d'
0.1
B
p
0.154
f ck
Pu 0.47
f ck BD
Assume reinforcement is uniformly distributed on four sides,
SP16, chart 48
"Mux,1 0.185
" /"fckB
"M
D2 "uy,1= 0.185
" /"fckDB
Thus,
2
" =
Mux,1 = 421.4531 KN-m
Muy,1 = 421.4531 KN-m
"Pu 0.470
" /"P
" =CL 39.6
IS 456 :uz2000
For,
Pu/Puz αn
<= 0.2 1
>= 0.8 2
0.470 1.450
Now,
n n
M ux M
uy 0.979 OK
M
M uxl uy1
From Etabs
Area of Steel (Asc)= 7785 mm2
360.574 246.577
KN KN
C26 426.708 KN
C26
426.708 KN
End moment of the beams along X andY-axis adjoining the column is tabulated below
Vc = τcd * Acv
where,
τcd = Design shear strength of concrete
= k*δ*τc
for,
Ast provided = 3925 mm2
p=("Ast "
∗100)/(𝐵
∗𝑑)
p= 2.15% and M25 concrete
τc = 0.83
IS 456: 2000, table 19
k= 1
IS 456: 2000, Cl 40.2.2
δ= 1 + "3∗ Pu
" /"Ag ∗ Fck "
δ= 2.42 >1.5
so,
δx= 1.5
δy= 1.5
we get,
τcdx = 1.243827 N/mm2
τcdy = 1.243827 N/mm2
τvx = "Vex
" /"Acv "
= 1.030 N/mm2
τvy = "Vey
" /"Acv "
= 0.826 N/mm2
In X-direction,
Space between end bars = 360 mm < 48*φt(384)
Space between bars = 90 mm >75mm
In Y-direction,
Space between end bars = 360 mm < 48*φt(384)
Space between bars = 90 mm >75mm
Since, longitudinal bar are spaced more than 75mm on either side so transverse
reinforcement should go around corner bars as well as alternate bars with open type
Special confining reinforcement has to be provided over a length lo from each joint
face towards mid span, and on either side of any section, where flexural yielding may
occur under the effect of earthquake.
Lo should be more than
1) 450 mm larger lateral dimension
2) 467.17 mm (clear span of member)/6
3) 450 mm 450mm
so,
Provide Lo as 500mm
Development Length:
IS 456-2000 cl.26.2.1
s
Ld 1132.813 mm for compression
4 x bd
Thus,
For special confining region i.e. 500 mm adopting 8mm diameter bars
at 100 mm spacing
For other regions provide 8mm diameter bars at 150 mm spacing.