Professional Documents
Culture Documents
A Technical Guide To The Effective Use of Steam in Plate Heat Exchangers
A Technical Guide To The Effective Use of Steam in Plate Heat Exchangers
a technical guide to
the effective use of
steam in plate
heat exchangers
a collaboration
between Spirax Sarco
and Alfa Laval
Introduction
Both Spirax Sarco and Alfa Laval are the acknowledged experts and
world-leaders in the control of steam and heat exchange. Our customers
rely on our technical knowledge and high quality products in all
industries around the world.
This reference manual has been jointly written by Spirax Sarco and
Alfa Laval to ensure that we all have the knowledge necessary to offer
the best technical advice available to our customers.
Steam and Plate Heat Exchangers
Index
1. Steam fundamentals
- What is steam? 7
- Why use steam? 7
- The formation of steam 7
- Terminology and units 8
- Steam quality 9
- Steam tables 10
- Mollier diagram 10
3. System design
- Steam system elements 19
- Steam generation 19
- Steam line sizing 20
- Draining steam lines 24
- Air venting 27
- Pressure reduction 28
- Flash steam 30
- Condensate return system 32
Appendices
- Appendix 1. Steam Tables 66
- Appendix 2. Stall Chart 70
Illustrations, Formulae and Tables
Illustrations
Fig. 1 Saturated steam - temperature vs pressure 8
Fig. 2 Saturated steam - specific volume vs pressure 9
Fig. 3 Mollier diagram 11
Fig. 4 Mollier diagram example 12
Fig. 5 Simplified Mollier diagram 13
Fig. 6 Heat exchange 17
Fig. 7 Packaged boiler 19
Fig. 8 Steam and condensate system 20 -21
Fig. 9 Pressure drop in steam lines 23
Fig. 10 Heat loss from a steam pipe 24
Fig. 11 The cause of waterhammer 24
Fig. 12 Steam line drainage point 25
Fig. 13 Steam trap types 26
Fig. 14 Steam trap set 27
Fig. 15 Steam line air venting 27
Fig. 16 Steam pressure reducing valves 28
Fig. 17 Steam pressure reducing station - with pilot operated valve 29
Fig. 18 Steam separator 30
Fig. 19 Pressure reducing valves fitted in parallel 30
Fig. 20 Pressure reducing valves fitted in series 31
Fig. 21 Flash steam per kg of condensate 31
Fig. 22 Flash vessel 32
Fig. 23 Condensate systems 33
Fig. 24 Condensate line sizing 34
Fig. 25 Multiple condensate line sizing 35
Fig. 26 Long pumped delivery line 36
Fig. 27 Electric condensate pumping unit 37
Fig. 28 Automatic pump operation 38
Fig. 29 Automatic pump packaged unit 38
Fig. 30 Stall chart 43
Fig. 31 Use stall chart to establish flow rate at stall point 44
Fig. 32 Use stall chart to establish secondary inlet temperature at stall point 45
Fig. 33 Primary steam two-port control 46
Fig. 34 Primary steam two-port control + active condensate drainage 47
Fig. 35 Exit temperature required to provide a blended temperature of... 48
Fig. 36 Primary steam two-port control + secondary by-pass 49
Fig. 37 Primary steam two-port control + secondary three-port control 50
Fig. 38 Primary condensate two-port control 51
Fig. 39 Elements of a simple closed loop automatic temperature control system 52
Fig. 40 Performance limits for plate heat exchangers 55
Fig. 41 Flow principle in a plate heat exchanger 55
Fig. 42 The gasket plate heat exchanger 56
Fig. 43 A channel plate with herringbone pattern 56
Fig. 44 A Clip-on gasket 57
Steam and Plate Heat Exchangers
Formulae
Formula 1 Specific enthalpy calculation 10
Formula 2a Heat required to produce a rise in temperature 15
Formula 2b Steam flow rate required to produce a rise in temperature 16
Formula 3a Heat required to balance heat losses 16
Formula 3b Steam flow rate required to balance heat losses 17
Formula 4 Calculating steam load on a heat exchanger from secondary flow rate 17
Formula 5 Calculating steam load on a heat exchanger from kW... 18
Formula 6 Calculating steam load on a heat exchanger from MW energy rate... 18
Formula 7 Calculate flash steam quantity 32
Formula 8 Calculate common line size for non pumped condensate 35
Formula 9 Calculate heat exchange area 39
Formula 10 Calculate arithmetic mean temperature difference 39
Formula 11 Simplified calculation for arithmetic mean temperature difference 39
Formula 12 Calculate heat load (full load) 40
Formula 13 Calculate actual arithmetic mean temperature required 41
Formula 14 Calculate actual primary temperature 41
Formula 15 Calculate stall fraction for variable flow condition 42
Formula 16 Calculate stall fraction for variable DT condition 42
Tables
Table 1 Relative density and specific heat of various liquids 16
Table 2 Overall heat transfer coefficient for steam to various liquids 17
Table 3 Pipeline steam capacities at specific velocities 22
Table 4 Warm up and running condensate loads for steam lines 26
Steam and Plate Heat Exchangers
1. Steam fundamentals
7
in the gas phase. Since one joule represents a very small amount
If the pressure on the liquid increases, the of energy, it is usual to multiply it by a thousand
molecules find it more difficult to leave. More and use kilojoules (kJ).
energy needs to be added before the molecules
can break free and enter the gas phase. Specific enthalpy
Therefore the temperature of the water increases Is the enthalpy (total energy) of a unit mass
to over 100ºC before boiling occurs. For any (usually 1 kg). Therefore the usual unit of
given pressure there is a corresponding measurement is kJ/kg.
temperature above which water cannot exist as a
liquid. Specific heat capacity
Equally, if the pressure on the water is below A measure of the ability of a substance to
normal atmospheric pressure, then it is easier absorb heat. It is the amount of energy (joules)
for the molecules to break free. Lower energy required to raise 1 kg by 1ºC. Therefore specific
levels are required, and boiling will occur at a heat capacity is expressed in kJ/kg ºC.
temperature below 100ºC. The specific heat capacity of water is
This relationship between pressure and approximately 4.19 kJ/kg ºC. This means that an
temperature is constant for saturated steam, and increase in enthalpy of 4.19 kJ will raise the
is shown in Fig. 1 and the 'Steam Tables' in temperature of 1 kg of water by 1ºC.
Appendix I.
Entropy
Entropy is a measure of molecular order. A
Fig. 1 Saturated steam - temperature vs change in entropy corresponds to a change in
pressure the molecular order, or organisation of a system.
250 As entropy increases, molecules move more
freely, e.g. entropy increases when a solid melts
Steam temperature °C
8
Steam and Plate Heat Exchangers
Absolute pressure and gauge pressure Fig. 2 Saturated steam - specific volume vs
The theoretical pressureless state of a perfect pressure
vacuum is 'absolute zero'. Absolute pressure is 1.8
therefore a pressure above absolute zero. The
1.6
pressure exerted by the atmosphere is 1 013 bar
1.4
9
Formula 1.
Steam tables
Specific enthalpy calculation
It has already been explained that a
(
hg = hf + 0.95 × hfg ) relationship exists between steam pressure and
saturation temperature: that enthalpies of
= 721.4 + (0.95 × 2 047.7 ) saturated water, evaporation and saturated steam
= 2 667 kJ / kg vary with pressure and that specific volume
changes with pressure.
For saturated steam these relationships are
fixed and recorded in 'Steam Tables' as set out in
tables in Appendix I. Clearly, 'wet' steam has a
Appendix I.
heat content substantially lower than that of dry
saturated steam at the same pressure.
The droplets of water in the steam have
weight but occupy negligible space and Mollier diagram
therefore have little effect on the overall
volume. A steam Mollier diagram is another means of
Pure dry saturated steam is a colourless gas. recording the properties of steam and
It is water droplets suspended in the steam that condensate under various conditions. It shows
give it a white cloudy appearance. the properties of steam and condensate under
any specific condition, or state. If the initial and
Superheated steam final state point of a process are known, a line
If heat continues to be added after all the joining these state points can represent that part
water has evaporated, the steam temperature of the process itself.
will again rise. The steam is then called A steam Mollier diagram will contain the
'superheated', and this superheated steam can be following features:
at any temperature above that of saturated steam
at the corresponding pressure. ■ Specific enthalpy (h) and Specific entropy (s)
Saturated steam will condense readily on any values plotted on the axes of the diagram.
surface which is at a lower temperature,
immediately giving up its enthalpy of ■ A steam saturation line dividing the
evaporation. chart into a superheated steam region and
When superheated steam gives up some of its a wet steam region. The line itself denotes
enthalpy, it initially does so by virtue of a fall in dry saturated steam.
temperature. No condensation will occur until
its temperature has fallen to its saturation ■ Dryness fraction (x) in the wet area of the
temperature, and the rate at which energy flows diagram.
from superheated steam is often less than that
achieved with saturated steam, even though its ■ Constant pressure (p) lines in both the wet
temperature is higher. area and dry area of the diagram.
Superheated steam, because of its properties,
is usually the first choice for power generation ■ Constant temperature line (t) in the
requirements, whilst saturated steam is ideal for superheat region. In the wet area the
heating applications. pressure and temperature lines are parallel.
10
Steam and Plate Heat Exchangers
Superheat
Area
nt
sta
Specific enthalpy, h kJ/kg
on
pc
t constant
ta nt Sa
ons tur
atio
t, tc n li
ne
tan dr
o ns yn
pc es
sf
ra
ct
io
n
x
Wet Area
The use of a steam Mollier diagram can be ■ The steam is now reduced in pressure from
explained by giving an example of how the 15 bar abs to 4 bar abs through a pressure
various states of steam and condensate can be reducing valve. It is now at 4 bar abs,
plotted when it is used in a heat exchanger. For superheated to 167ºC. The specific
the sake of clarity, only the lines necessary to enthalpy remains constant at 2 790 kJ/kg
illustrate the example are shown in Fig. 4. - Point C
11
up its specific enthalpy of evaporation, it condensate system. The final condition
must cool until it reaches its saturation will depend on the condensate removal
temperature of 120ºC arrangements and the pressure within the
- Point E condensate return system
- Point G
■ The steam then condenses at constant
pressure and temperature, giving up all of It is not practicable to reproduce a full Mollier
its specific enthalpy of evaporation. diagram in a publication such as this, because of
It is then condensate at 120ºC its large size and complexity. Full diagrams are
- Point F available in both hard copy and electronic format
from technical publishers.
■ Some sub-cooling of the condensate may
occur within the heat exchanger and A simplified Mollier diagram is reproduced in
cooling and some re-evaporation will Figure 5. showing sufficient detail to be able to
occur when the condensate passes through plot state points around the saturated steam line in
the heat exchanger steam trap into the the pressure range used by plate heat exchangers.
bs
bs
bs
ar a
ar a
ar a
2b
4b
15 b
Superheat
Area
198°C
B C D 144°C
Specific enthalpy, h kJ/
2790
A 120°C
2595
8°C
19
b s 4°C E
a r a s 14 °C
b ab 20
15 bar bs 1 Sat
ura
4 ar a tion
2b line
kg
506 x=
F G 0.9
Wet Area
12
Steam and Plate Heat Exchangers
bs
bs bs s
ra
a a ab
ar ar r
ba
5b 2b ba
0.5
1
3000
s
r ab
ba
200°C 0.2
2800
150°C s
ab
Specific enthalpy (h) kJ/kg
r
ba
0.1
100°C
Satur
ation
Line
2600 ar abs
4b
0.0
ar abs
x=0.95 1b
2400 0.0
x=0.90
2200
7.0 7.5 8.0 8.5
13
14
Steam and Plate Heat Exchangers
■ Calculation.
The specific heat of a material is the amount
Measurement of heat required to raise a unit mass (1 kg)
Obviously, steam flow cannot be measured at through 1ºC. A table of the specific heats and
the design stage of an installation. Measurement specific gravities of various liquids is set out in
of steam flow can only be used to establish the Table 1.
steam flow rate on an existing installation.
Two methods of measurement are available;
15
Table 1. Relative density and specific heat of
various liquids Formula 2b
Steam flow rate required to produce a rise in
Relative Specific heat temperature
Liquid
density kJ/kg °C
Acetone 0.79 2.13 M × Cp × ∆t
Alcohol, ethyl, 0°C 0.79 2.30 Ws =
Alcohol, ethyl, 40°C 0.79 2.72
hfg × h
Alcohol, methyl, 4 - 10°C 0.80 2.46
Alcohol, methyl, 15 - 21°C 0.80 2.51 where:
Ammonia, 0°C 0.62 4.60 Ws = steam flow rate, kg/h
Ammonia, 40°C 4.85 M = weight of material, kg
Ammonia, 80°C 5.39
Ammonia, 100°C 6.19
Cp = specific heat, kJ/kg°C
Ammonia, 114°C 6.73 ∆t = temperature rise, °C
Anilin 1.02 2.17 hfg = enthalpy of evaporation of steam, kJ/kg
Benzol 1.75 h = time available, hours
Calcium chloride 1.20 3.05
Castor oil 1.79
Citron oil 1.84
Diphenylamine 1.16 1.92
Ethyl ether 2.21 Where heat is required to balance heat losses,
Ethylene glycol 2.21 the heat flow rate can be calculated using
Fuel oil 0.96 1.67 Formula 3a.
Fuel oil 0.91 1.84
Fuel oil 0.86 2.09
Gasoline 2.21
Glycerine 1.26 2.42
Kerosene 2.00 Formula 3a
Mercury 19.60 1.38 Heat required to balance heat losses
Naphthalene 1.14 1.71
Nitrobenzene 1.50 Qr =k × A × ∆t × 3.6
Olive oil 0.91 - 0.94 1.96
Petroleum 2.13 where:
Potassium hydrate 1.24 3.68 Qr = heat flow rate, kJ/h
Sea water 1.02 3.93 k = heat transfer coefficient, W/m2 °C
Sesame oil 1.63
Sodium chloride 1.19 3.30
A = heating area, m2
Sodium hydrate 1.27 3.93 ∆t = temperature difference, °C
Soybean oil 1.96
Toluol 0.87 1.50
Turpentine 0.87 1.71
Water 1.00 4.19
The 'k' value, or heat transfer coefficient, is a
Xylene 0.87 - 0.88 1.71
value giving the expected overall rate at which
heat energy will travel from a hot medium to a
As the actual flow rate of steam is usually cooler medium through a barrier separating
required, Formula 2b will normally be more them. Some typical 'k' values, expressed in
useful. Watts /m2 ºC, for the flow of energy from steam
through stainless steel to various liquids in plate
heat exchangers are listed in Table 2.
16
Steam and Plate Heat Exchangers
Formula 3b
Steam flow rate required to balance heat losses Usually, you will be provided with a flow
rate for the secondary fluid and the required rise
in temperature. A derivation of Formula 3b will
k × A × ∆t × 3.6 provide a steam flow rate where the flow rate
Ws =
hfg through the secondary side of the exchanger is
expressed in m3/h, as shown in Formula 4.
where:
Ws = steam flow rate kg/h
k = heat transfer coefficient, W/m2 °C
A = heating area, m2 Formula 4
∆t = temperature difference, °C Calculating steam load on a heat exchanger from
hfg = enthalpy of evaporation of steam, kJ/kg secondary flow rate
M × 1 000 × d × Cp × ∆t
Ws =
hfg
Steam load on heat exchangers
When considering the actual steam load on a where:
heat exchanger, enough steam needs to be Ws = steam flow rate kg/h
provided to the primary side of the exchanger to M = fluid flow rate m3/h
provide the required rise in temperature in the d = fluid relative density
liquid or gas passing through the secondary side Cp = fluid specific heat kJ/kg°C
of the exchanger. ∆t = temperature rise °C
hfg = enthalpy of evaporation of steam, kJ/kg
17
Sometimes the heat requirement in a heat meet a given condition can be checked, using
exchange application will be expressed as an Formula 2a, if the heat exchange area and heat
energy rate requirement given in kilowatts (kW) transfer coefficient are known.
or megawatts (MW).
A Watt is an energy rate of 1 Joule per
second (J/s), where the Joule is a basic unit of Examples
energy.
If heat requirements are expressed in these Example 1
units, they can be converted to steam flow rates Calculate the steam flow rate on an exchanger
using either Formula 5 or Formula 6. required to heat 15 m3/h of water from 20°C to
60°C. The steam pressure is 2 bar g.
Formula 5
Using Formula 4
Calculating steam load on a heat exchanger
from kW energy rate requirement
15 ×1 000 × 1× 4.19 × 40
Ws =
2 163.3
kW × 3 600
Ws = Ws =1 162 kg / h
hfg
NB: Relative density of water = 1 (fromTable 1).
where: Specific heat of water = 4.19 kJ/kg°C (from
Ws = steam flow rate kg/h Table 1)
kW = energy rate requirement Specific enthalpy of evaporation of steam at
hfg = enthalpy of evaporation, kJ/kg 2 bar g = 2 163.3 kJ/kg (from Appendix 1).
Example 2
Formula 6
Calculating steam load on a heat exchanger
The energy rate requirement on a heat
from MW energy rate requirement exchanger is 150 kW. Calculate the required
steam flow rate, with steam at 3 bar g.
MW × 1 000 × 3 600
Ws =
hfg
Using Formula 5
where:
Ws = Steam flow rate kg/h 150 × 3 600
Ws =
MW = Energy rate requirement 2 133.4
hfg = Enthalpy of evaporation, kJ/kg
Ws =253 kg /h
18
Steam and Plate Heat Exchangers
3. System design
Water
3rd. pass
2nd. pass
19
Fig. 8 Steam and condensate system
11 14
12
1
13
10
15
16
5
6
9 17
7
8
4
25 bar g is the packaged shell & tube boiler. connected to a steam drum at their top and a
This type of boiler has a water filled shell with a water drum at their base. Often, water tube
steam space at the top. Immersed in the water is boilers have a superheater incorporated into their
a combustion chamber connected to banks of design.
tubes through which the hot flue gases pass.
Each bank of tubes is called a "pass". With this
type of boiler it is unlikely the steam produced Steam line sizing
will be 100% dry.
For higher pressures, temperatures and The correct size of pipe to carry the required
capacities, water tube boilers are used. Here, the amount of steam at the required pressure should
water is circulated through tubes, hence "water be selected.
tube boiler" and the hot combustion gases are If the pipe is too small, a high pressure drop
passed over these tubes. The tubes are and high velocity will occur, resulting in lack of
20
Steam and Plate Heat Exchangers
25
18 22
19
23
20
24
21
21
Table 3 Pipeline steam capacities at specific velocities
Table 3 gives pipe line capacities of a range of therefore the correct temperature is available at
pipe sizes at 15 m/s, 25 m/s and 40 m/s. the steam using equipment. Normally a pressure
drop of approximately 0.3 bar per 100 m run is
Sizing on pressure drop acceptable
In lines over a few metres in length it is Pressure drop in steam lines can be
better to size the pipe using the pressure drop calculated, but is a lengthy process requiring the
method, ensuring the correct steam pressure and use of a number of factors related to such things
22
Steam and Plate Heat Exchangers
E D
Steam pressure
bar g
B
C
Steam temperature
23
Step 1 Fig.10 Heat loss from a steam pipe
Using Fig. 9, draw a vertical line from
184°C on the steam temperature scale (Point A)
up to 10 bar g on the saturated steam scale,
Point B.
Steam Insulation
Step 2
From point B draw a horizontal line across to
10 000 kg/h on the steam flow rate scale,
Point C.
Pipe
Step 3
From Point C draw a vertical line up the
150 mm line on the inside pipe diameter scale,
Point D. Heat loss
Condensate
Step 4
From Point D draw a horizontal line across to
the pressure drop scale, Point E. In this case the pipe at steam velocity.
pressure drop will be approximately 0.4 bar per These slugs arrive at a valve or pipe bend and
100 m length of pipe. are suddenly stopped. The kinetic energy in the
condensate converts into pressure energy and a
pressure shock is exerted on to the obstruction
Draining steam lines which can cause considerable damage.
Waterhammer
Waterhammer occurs when condensate Slugs of condensate can develop and be
builds up into 'slugs' and is carried along the carried along at steam velocity
24
Steam and Plate Heat Exchangers
drain the condensate away from the collection load, when the boiler starts up and the steam
leg. A steam trap is a device that will allow lines are brought up to normal operating
condensate to pass through it, but will not allow temperature, will be greater than the running
steam to pass. load when steam only condenses due to heat
Steam lines up to 100 mm in size should have loss from the pipe. Usually the steam trap
a collection leg the same size as the line. Larger should be sized to handle the greater warm up
pipes should have collection legs two or three load but there are occasions where steam lines
pipe sizes smaller, but not less than 100 mm. are always live and sizing on the running load
Where timed automatic slow start up will be appropriate.
procedures are in place, the length of the It should also be remembered that at start up
collection leg should be approximately 1.5 pipe the pressure in the steam line will be much
diameters but not less than 200 mm. If the boiler lower than during normal operation. Table 4.
is shut down each night and automatic slow start shows the warm up and running loads for steam
up procedures are not used, it may be necessary pipes up to 400 mm.
to provide a longer collection leg of 700 mm or
more.
Steam flow
Steam trap
Condensate collection leg
Condensate out
Steam trap set
Blowdown valve
25
Table 4 Warm up and running condensate loads for steam lines
26
Steam and Plate Heat Exchangers
when sizing for warm up conditions, a 15 mm or the steam trap's operation to be carried out. If
20 mm steam trap will normally be suitable. this is not fitted a sight glass should be fitted
The problem of air in a steam system is after the steam trap.
discussed in the next section, but it is important A strainer should be fitted before the steam
that a steam trap selected for this application is trap to protect it from pipeline debris.
also capable of passing any air trapped in the A check valve should be fitted after the steam
steam line. The inverted bucket trap deals with trap to ensure that reverse flow through the
steam trap does not occur.
■ Strainer
■ Check valve
27
carried to heat exchange equipment will lower by either the process requirements or the process
its efficiency. equipment itself. Where this is necessary the
Automatic air vents should be fitted to the steam pressure will be reduced through a
ends of steam lines and at strategic points along pressure reducing station, incorporating a steam
their length to ensure that these incondensable pressure reducing valve.
gases are removed. Many types of steam pressure reducing
Otherwise, they will mix with the steam, and valves are available including direct acting
form an insulating barrier on heat exchange types, pilot operated types and electro/pneumatic
surfaces, lowering the rate at which heat is types. The choice will depend upon the steam
transferred, and at the same time promote load, the stability of the steam load, the steam
corrosion. pressure and the expected variations in the
upstream and downstream steam pressures.
A direct acting type valve is very robust and
Pressure reduction simple in its operation. Because of its method of
operation the downstream pressure will deviate
Often, steam pressure needs to be reduced to from the set pressure if the upstream pressure
meet the needs of a particular process. alters or the steam load changes. This is often
Steam should be generated at, or close to, the referred to as "offset" and this characteristic can
boiler design pressure to ensure that it is of the be acceptable where the steam load and
highest quality. It should then be distributed at upstream pressure do not vary very much, or
high pressure which requires smaller diameter where variations in downstream pressure can be
distribution mains. Individual pieces of steam accepted.
using process plant may require steam at much A pilot operated valve provides greater
lower pressures, with the pressure limitation set accuracy of downstream pressure while
28
Steam and Plate Heat Exchangers
operating under conditions where the upstream A steam separator removes any water droplets
pressure may change or there may be variations suspended in the steam. It has a much larger
in the steam flow rate. cross sectional area than the approach pipework;
Flexibility and accuracy under all operating as the steam enters the separator its velocity
conditions can be achieved by using an electro/ drops, while the inertia of the heavier water
pneumatic actuated valve arrangement. droplets causes them to impinge on the internal
baffles within the separator. The droplets are
then directed to the drain connection and
Pressure reducing stations removed by a steam trap. Removing these
The prime purpose of a pressure reducing droplets from the steam will help to ensure that
valve station is to provide steam at the correct maximum heat transfer rates are achieved within
pressure in sufficient quantity. It should also be the heat exchanger and that valve seats are not
designed to ensure that the steam provided is damaged by wiredrawing. Wiredrawing is a
dry and clean.
Safety valve
Isolation Pressure reducing Pressure
High valve gauge Reduced
valve
pressure pressure steam
steam
Strainer
Separator Isolation
valve
Condensate
Steam trap set
To ensure that this is achieved the following name for the erosion that occurs when the
components should be provided in a pressure droplets are carried across valve seats at
reducing valve station: velocities of up to 300 m/s during normal
operation.
■ Steam separator & steam trap set Isolation valves are required to facilitate
repairs and cleaning of the reducing valve
■ Upstream and downstream isolation valves station components. The upstream valve is fitted
after the separator so that the approach
■ Strainer pipework is drained and kept free of condensate
even when the valve is closed.
■ Upstream and downstream pressure A strainer is required to protect the reducing
gauges valve from pipe debris; prior to a valve it should
be fitted with a fine 100 mesh screen, with the
■ Pressure reducing valve basket on its side.
29
Fig.18 Steam separator At full load, both valves will be open. As the
load decreases, the controlled pressure will rise
Baffles
slightly and the valve which is
set at the lower pressure will
Wet steam Dry steam
out begin to close.
in
Further reduction in the load
will cause it to close and the
other valve to modulate down
through its proportional band.
If a high pressure turndown
Condensate is required it may be advisable
drain to fit two pressure reducing
valves in series. When making
this decision, much will
This prevents it from filling with condensate depend upon the type of valve being used and
under no flow conditions when the reducing the operating conditions, but as a general guide,
valve is closed, which could then be carried two valves should be considered when the
through the valve when it opens again. turndown ratio exceeds 10:1.
The safety relief valve fitted after the
pressure reducing valve ensures the equipment
fitted downstream from the station will not be
subjected to unacceptable high pressures should
the pressure reducing valve fail. Flash steam
When widely varying load conditions are
present, two pressure reducing valves with their When steam gives up its specific enthalpy of
pressure settings slightly offset, fitted in parallel evaporation, condensate forms at the same
with a combined capacity to meet the peak load, temperature and pressure as the steam from
perform better than a single large valve. which it condenses. When this condensate is
High Reduced
pressure pressure
steam steam
Condensate
30
Steam and Plate Heat Exchangers
High
pressure
steam
Reduced
pressure steam
Condensate Condensate
discharged to a lower pressure, the energy it amount of flash steam formed per kg of
contains is greater than it can hold while still condensate can be read from Fig.21, extending a
remaining in its liquid state. line from the higher pressure shown on the left
This excess energy re-evaporates some of the axis of the chart to the relevant lower pressure
condensate back into steam at the lower line, and then reading off the amount of flash
pressure. Although this steam is referred to as steam released per kilogram of condensate from
"flash steam", it is just saturated steam at a the bottom axis.
lower pressure. The amount of flash steam Where possible, this flash steam should be
released from high pressure condensate can be utilised as a source of steam for low pressure
calculated from Formula 7. Alternatively, the steam applications. A flash vessel can be used to
1.5
2.0
0.5
1.0
0
Higher pressure bar g
31
separate the flash steam from the condensate. Condensate return system
In cases where the flash steam supply does
not match the low pressure steam demand,
excess steam may be vented through a
surplussing valve arrangement. Any shortfall in An effective condensate return system is
supply can be made up by steam supplied required to remove condensate away from the
through a pressure reducing valve from a high steam using equipment and return it to the boiler
pressure supply. house. Condensate is already treated for use in a
boiler and contains useful heat. This decreases
the amount of heat the boiler will need to
provide to convert it back into steam.
Formula 7. Condensate return systems will fall into three
Calculate flash steam quantity main categories, as illustrated in Fig. 23.
Flash steam/
Flash vessel Non pumped discharge lines
condensate from On the discharge side of the steam trap,
higher pressure condensate lines have to carry condensate, any
incondensable gases carried through the process,
and flash steam released from the condensate as
Low pressure
its pressure drops through the steam trap.
condensate As can be seen from the previous chapter, the
mass of flash steam released can be relatively
32
Steam and Plate Heat Exchangers
Process
equipment
(b) Non pumped discharge
lines from steam traps. Steam
Vent
Electrical condensate
pumping set
small compared to the remaining mass of the flash steam velocities inside that line within
condensate it is released from. But the volume acceptable limits.
of flash steam can be very large and must be This chart is constructed, using a velocity
taken into consideration when sizing the sizing method. Pressure drop along the length of
condensate line. the condensate line due to frictional losses will
To illustrate this, if condensate is discharged occur at the rate of approximately 0.3 bar g per
from a steam trap with an upstream pressure of 150 m.
3 bar g, into a condensate line pressurised to
0.5 bar g, 6.2% of that condensate will convert Example
into flash steam. With each kg of flash steam Select a non pumped condensate line to carry
occupying 1.15 m3 and each kg of condensate the condensate from a process operating at
only occupying 0.001 m3, 99% of the 3 bar g (4 bar abs). The maximum condensate
condensate line will be occupied by flash steam load will be 750 kg/h and the back pressure
and just 1% occupied by condensate. within the condensate line is estimated to be
Therefore, non pumped condensate lines 0.5 bar g (1.5 bar abs).
need to be sized with this in mind. Fig. 24,
provides a means of sizing this type of Step 1
condensate line, where steam pressure upstream Using Fig. 24, mark Point A, the system
of the steam trap is known and the pressure steam pressure in bar a.
within the condensate system is known. It will
provide a condensate line size that keeps the
33
Fig. 24 Condensate line sizing
0 0 0 0 0 0
50 40 35 30 25 20
100,000 0
15
50,000 5
12
0
10
20,000 80
5,000 50
D 40
2,000 32
Condensate rate kg/h
1,000 25
C
500 20
15
200
100 10
50
20
10
350 200
300 100 50
60
250 20
Condensate system pressure bar a
30
10
Steam system pressure bar a
200
180 10
Steam temperature ºC
5
160 6 4
A 3
140
3 B 2
120
1.5
100 1
90
80
0.6 0.5
70 0.3 0.3
60
50
0.1
34
Steam and Plate Heat Exchangers
Step 4
Process 3
Extend the line from Point C to
2 000 kg/h
Point D on the condensate line size 4 bar g
scale.
65 mm
Step 5
Read off the required condensate 50 mm
Process 1
line size from the scale. In this
500 kg/h
example a 40mm NB pipe will be 3 bar g 25 mm 80 mm
40 mm
required.
35
If sizing is correctly carried out, the third com- This can create a low pressure area within the
ponent will be negligible and only one and two pipe behind the moving slug of water which
need to be considered for practical purposes. could cause it to flow back along the pipe when
its momentum is exhausted. To prevent this, a
suitably sized vacuum breaker can be fitted at
Pumped return lines the start of the discharge line, together with
The individual or common non pumped another check valve to protect the pump. An air
condensate lines are often collected into a eliminator may be required at the delivery end of
receiver and then pumped back to the boiler the line to discharge the air drawn in through the
house. vacuum breaker, as shown in Fig. 26.
In most instances, pumped condensate lines
carry only water, with no flash steam present.
This will always be the case where the Fig. 26 Long pumped delivery line
condensate receiver is vented.
Fig. 24 can also be used to size pumped
Vacuum breaker
condensate lines where no flash steam is Air eliminator
present.
Condensate
Example pumping unit Check valve
Size a pumped condensate line to
carry 10 000 kg/h of condensate.
Step 1
Locate the condensate load, Point E on the
condensate rate scale at the left hand side of the
top section of the chart.
Step 2
Extend a line horizontally from Point E to
Point F at the right hand side of the chart and
read off the required condensate line size. In
this case it will be a 65 mm NB pipe.
Pumps do not run continuously and normally Problems can also occur when the discharge
have on on/off type action. This should be taken lines from steam traps are connected directly
into account when sizing the condensate line into a pumped condensate line. This should be
from the pump, as the discharge rate from the avoided by piping the discharge into a separate
pump will be greater than the actual non pumped condensate line which carries the
condensation rate from the process equipment. condensate to a pump receiver.
Depending upon the type of pump this
discharge rate can range from 1.5 times to 6
times the actual condensation rate.
Long, pumped delivery lines also may need Sizing for combined pump/steam trap
special attention, if waterhammer within them is units
to be avoided. The water being pumped can In the next section, which deals with the
gain considerable momentum and may carry on subject of temperature control of plate heat
moving along the pipe when the pump stops. exchangers in some detail, reference is made to
36
Steam and Plate Heat Exchangers
Receiver
Condensate pump
37
Automatic pump Fig. 29 Automatic pump packaged unit
The steam or air operated automatic pump
operates on a positive displacement principle. Condensate in
The pump consists of an inlet and outlet check Vent
valve, and a body, containing an exhaust and Condensate in
inlet valve assembly operated by a float
mechanism. Fig. 28 shows its method of
operation.
Inlet Outlet
check valve check valve
38
Steam and Plate Heat Exchangers
39
the pressure drop on the secondary side is a exchanger.
major consideration. Often, when steam is the The point at which this condition will occur
primary heating medium, a greater heat transfer in a particular application can be predicted,
area than necessary is selected in order to keep either by calculation, or by plotting the known
this secondary side pressure drop within operating conditions onto a chart and reading off
reasonable limits. the stall points. Both of these methods can be
It can be seen from Formula 9., that if the illustrated by example.
heat transfer area (A) is increased from that
needed to give output (Q), the only variable that Calculation
can change, to give the required output with this A plate heat exchanger is required to heat
increased heat transfer area, is the mean 4 kg/s of water from 30°C to 90°C. Steam is
temperature difference. This must decrease and available at 4 bar g and it is initially assumed
the only way this can decrease, without the there will be a 25% pressure drop through the
secondary conditions changing, is if the primary temperature control valve, giving 3 bar g at the
side mean temperature decreases. heat exchanger. Condensate discharges to a
Put another way, the steam temperature, gravity return system at 0 bar g. To give the
therefore its pressure, must decrease if the required output and provide a reasonable
desired output is to be achieved with an pressure drop of approximately 35 kPa on the
increased heat transfer area. secondary side, a heat exchanger has been
This oversizing of the heat transfer area in selected with a heat exchange area of 2.6 m2 and
plate heat exchangers to facilitate reasonable a heat transfer coefficient (k) of 7 450 W/m2 °C.
pressure drops on the secondary side is quite First the full design heat load is calculated,
common in steam applications. This oversizing using Formula 12.
is often in the region of 100% to 200% and can
have a considerable effect on the actual steam
pressure within the exchanger, even under full Formula 12
load conditions. Calculate heat load (full load)
The pressure at the inlet of the steam trap
may be less than the back pressure imposed on
the outlet of the steam trap. Where this is the
(
Q= M × Cp × TC(out) - TC(in) )
case, condensate will not be discharged and will
back up into the heat exchanger. This will Q= 4 × 4.186 × (90- 30)
certainly cause temperature control problems
and may also cause structural damage to the Q=1 004.6 kW
exchanger through waterhammer and thermal
where:
stress.
Q = heat load, kW
M = secondary flow rate, kg/s
Cp = specific heat capacity, kJ/kg°C
Stall condition (for water - 4.186 kJ/kg °C)
TC(in) = secondary inlet temperature, °C
If the back pressure imposed upon a steam TC(out) = secondary exit temperature, °C
trap is greater than the pressure available at its
inlet, the heat exchanger is described as being in
a 'stall' condition. Condensate cannot pass
through the trap and will back up, resulting in From the information now available we can
the loss of effective control over the heat calculate the actual arithmetic mean
40
Steam and Plate Heat Exchangers
temperature to give the required output at full A stall condition will exist, when the
load, as shown in Formula 13. pressure on the inlet of the steam trap is equal
to, or less than, 0 bar g. At this pressure the
steam's temperature will be 100 ºC.
Formula 13
Calculate actual arithmetic mean temperature
difference required Formula 14
Calculate actual primary temperature
where: where:
2
A = heat transfer area, m Tamtd = arithmetic mean temperature
Q = heat requirement, kW difference, °C
k = heat transfer coefficient, W/m2 °C TH(in) = primary side inlet temperature, °C
Tamtd = arithmetic mean temperature TC(out) = secondary side exit temperature, °C
difference, °C TC(in) = secondary side inlet temperature, °C
As the secondary mean temperature is fixed, This can occur when either, or a combination
the primary mean temperature at full load, of the following things, happen:
TH(in), required to provide this overall
arithmetic mean temperature difference can be ■ The secondary inlet and exit temperatures
calculated using Formula 14. to and from the exchanger (∆T secondary
From the steam tables it can be seen this side) remain constant but the flow
temperature of 112°C equates to a saturated reduces.
steam pressure of approximately 0.5 bar g.
This example shows that irrespective of the ■ The flow remains constant but the
steam pressure available before the temperature secondary ∆T reduces - The inlet
control valve, the pressure inside the heat temperature rises or the exit temperature
exchanger will depend upon the actual duty falls or both.
required and the heat transfer aera available
within the heat exchanger. The point at which either happens can be
It can be seen that in this example, under full predicted by calculation.
load, a stall condition will not exist, as the Either logarithmic mean temperatures
pressure on the inlet of the steam trap will be difference (lmtd) or arithmetic mean
0.5 bar g, providing a positive pressure temperature difference (amtd) can be used in
differential of 0.5 bar across the steam trap. the calculations. Using lmtd is technically
41
correct, while amtd is easier to use. at full load.
The calculations used in this manual use amtd To calculate the fraction to be applied to
and provide solutions accurate enough for predict by how much the secondary ∆T (the
practical day to day use. The calculations also temperature rise on the secondary side) must
assume a constant k value under all conditions; reduce to produce a stall condition, use Formula
in practice the k value will change as velocities 16, which expresses the temperature difference
and temperatures of the media alter. between the steam and secondary outlet
A calculation to predict the reduction in flow temperatures at full load and at stall as a fraction.
to produce a stall condition is shown in
Formula 15.
Formula 16
Formula 15 Calculate stall fraction for variable ∆T condition
Calculate stall fraction for variable flow
condition TH(in)(stall) - TC (out)
Fs =
TH(in)(full) - TC(out)
TC (out) + TC(in)
TH(in)(stall) -
2
Fs = 100- 90
TC(out) + TC(in) Fs=
TH(in)(full) - 112- 90
2
Fs =0.45
100-
90 + 30
2 where:
Fs= Fs = stall fraction
90 + 30
112 - TH(in)(stall) = primary side inlet temperature at
2
stall point, °C
TH(in)(full) = primary side inlet temperature at
FS=0.77
full load, °C
TC(out) = secondary side exit temperature, °C
where:
Fs = Stall fraction
TH(in)(stall) = Primary side inlet temperature at
stall point, °C Once calculated, this fraction can be applied
TH(in)(full) = Primary side inlet temperature at to the secondary ∆T at full load to predict when
full load, °C stall will occur.
TC(out) = Secondary side exit temperature,°C In this case, it will be when the secondary ∆T
TC(in) = Secondary side inlet temperature, °C falls to 27ºC (60ºC x 0.45) or below. Therefore,
if the exit temperature remains at 90ºC, stall will
occur if the inlet temperature rises to
63ºC (90ºC - 27ºC).
Once calculated, this fraction can be applied
to the flow rate at full load to predict when stall
will occur. In our example, stall will occur when The stall chart
the flow rate falls to 3.1 kg/s (4kg/s x 0.77) or Fortunately a simpler method of predicting
below. when stall will occur is available in the form of a
This calculation is, in fact, expressing the stall chart, shown in Fig 30. On a stall chart a
amtd at the stall point as a fraction of the amtd graphical representation of a heat exchange
42
Steam and Plate Heat Exchangers
Step 2
Mark secondary fluid outlet control
process can be plotted from 100% load down to temperature and temperature of steam at
0% load. pressure equal to back pressure on right axis;
A large scale stall chart that can be copied for secondary fluid outlet temperature = 90ºC and
use is attached as Appendix II. steam temperature equal to back pressure =
100ºC.
43
Fig. 31 Use stall chart to establish flow rate at stall point
1 control
temperature 3 2
6 2
5
4
1 7
ordinate. Draw a horizontal line from this point stall will occur. In this case it is 77%.
to the right axis. This point is the mean Therefore stall will occur if the flow falls below
secondary temperature; 60ºC. 4 kg/s x 77% = 3.1 kg/s.
Step 6
Join full load steam temperature on left axis
to mean secondary temperature on right axis. To establish secondary inlet temperature
This line should terminate at the control and % ∆T at which stall will occur (Refer
temperature. to Fig. 32)
Step 7
Step 1
Where this line intersects the back pressure
Mark full load steam temperature and
line, drop a vertical line to the % line.
secondary fluid inlet temperature at design
Step 8 condition, on the left axis. Note that the steam
From this scale read off the % flow at which design temperature should be as calculated in the
44
Steam and Plate Heat Exchangers
Fig. 32 Use stall chart to establish secondary inlet temperature at stall point
1
5
3 2
7
4
1 6
45
Temperature control 1. Primary steam two-port control +
steam trap, Fig. 33
methods With this method of control the heat
exchanger is sized to handle 100% of the
Various methods of temperature control are secondary flow rate at full load and to heat it up
available when steam is the primary heating to its design condition.
medium in a heat exchange application, using a The steam flow (and therefore its pressure) is
plate heat exchanger. adjusted by a two port control valve on the
It is vital to take into consideration the actual steam supply to the heat exchanger. The control
operating conditions when considering the valve's position is adjusted by a signal from the
method of control, as discussed in this section. controller according to the information it
The following need to be considered when receives from a temperature sensor fitted in the
deciding upon the temperature control method secondary flow from the heat exchanger.
to be used. A steam trap set is fitted on the outlet of the
primary side of the exchanger to remove
■ Actual steam pressure expected in the condensate.
exchanger.
Use when:
The available pressure in the heat
■ Total back pressure exerted on the primary
exchanger will always be greater than the
side (condensate) outlet of the exchanger.
back pressure exerted on the primary side
under normal design operating conditions.
■ Whether the secondary ∆T is fixed or
variable during normal operation.
Advantages:
Simple design.
■ Whether the secondary fluid flow rate is
constant or will fluctuate. Easily commissioned.
Suitable for all types of plate heat
■ Heat exchanger construction. exchanger.
high
limit
pressure safety valve control air vent &
sensor
reducing valve vacuum
separator valve breaker
flow
steam out
control
sensor
46
Steam and Plate Heat Exchangers
high
pressure limit
safety valve control sensor
reducing control
separator valve valve sensor
flow
steam out
air
vent
steam
high limit flow
steam trap set cut out in
plate heat exchanger
47
Advantages: 3. Primary steam two-port control +
Easily commissioned. secondary shunt + steam trap, Fig. 36
The objective of this control method is to be
Pump/steam trap combination will operate able to match more closely the actual heat
under all conditions within the operating transfer area within an exchanger to that
limits of the equipment. actually required for a given duty. This
reduction of heat transfer area, coupled with the
Will remove condensate when the need for a higher secondary exit temperature,
available steam pressure within the heat will reduce oversizing of the heat exchanger,
exchanger is always lower than the back which in turn, will require higher steam
pressure exerted on the primary side under pressures to be used within the exchanger.
normal design operating conditions. This is achieved by only passing part of the
flow on the secondary side through the heat
Suitable for all types of plate heat exchanger, heating it to a higher temperature
exchanger. than required, then blending it with the cooler
secondary return flow to provide the final
Disadvantages: temperature.
Possible oversizing of heat exchanger to With this method, a primary control is
accommodate secondary pressure drop provided on the steam supply to the exchanger
restrictions. and a fixed by-pass is provided on the secondary
side. The control sensor is installed in the
Extra cost of pump blended flow. The exit temperature from the
exchanger is not directly controlled, but is
Filling head required above pump inlet. established by the ratio of the flows passing
through the exchanger and the by-pass.
With this arrangement, the secondary flow
control
pressure safety valve high sensor
reducing control limit
valve valve sensor
separator
flow out
steam
by-pass
valve
48
Steam and Plate Heat Exchangers
Disadvantages:
Reduction in heat load requirement or
°C
49
4. Primary steam two-port control + Use when:
secondary three port control + Provision of a higher, fixed secondary
steam trap, Fig. 37 temperature from the heat exchanger
This method of control also enables the will allow the use of a higher steam
closer matching of heat transfer area, within an pressure to overcome a stall problem.
exchanger, to that actually required for the given
duty. There is a combination of large secondary
Instead of providing a fixed volume flow rate and small secondary temperature
secondary by-pass, as described in the previous rise.
method, a three port blending valve is installed
on the secondary circuit. The blending valve Advantages:
blends return flow with heated water from the Allows closer matching of actual heat transfer
heat exchanger, to provide the final flow area to the design requirement, resulting in a
temperature. smaller plate heat exchanger.
With a fixed by-pass, the secondary flow rate
through the heat exchanger is constant. A Minimum steam temperature, and
change in secondary load conditions will result therefore equivilent pressure, within the
in a change in the secondary flow temperature exchanger will be the same as the
from the heat exchanger. secondary fixed outlet temperature.
With this method, a secondary three-port
blending valve plus a primary two-port valve, Disadvantages:
the secondary flow temperature from the heat Cost of secondary three-port valve;
exchanger is constant. A change in secondary although this can be less than the cost of
load conditions will result in a change in a pump/steam trap combination.
secondary flow rate through the heat exchanger.
The maximum outlet temperature on the
secondary side can be limited by the fluid
characteristics and/or system pressure.
50
Steam and Plate Heat Exchangers
flow out
high limit control
steam trap set cut out valve by-pass
valve
flow in
condensate
steam trap set plate heat exchanger
51
Control requirements
Automatic temperature A correctly selected, sized and applied
control automatic contol system should be capable of
providing accurate, predictable, stable control
The control methods discussed in the under all normal operating conditions. If
previous section require the use of a two port necessary, it should also be capable of being
control valve, fitted either on the steam inlet to integtrated into a plant's existing distibuted
the plate heat exchanger, or the condensate process control or data acquisition system.
outlet from the heat exhanger.
Control system elements
■ When fitted on the steam inlet, the A basic automatic temperature control
purpose of this valve is to control the system suitable for controlling the secondary
amount and the pressure of the steam that outlet temperature from a steam heated plate
flows into the heat exchanger. heat exchanger will consist of the elements
illustrated in Fig. 38.
■ When fitted on the condensate oultlet, it is
used to control the level of condensate ■ Sensor - This measures the actual
within the heat exchanger. temperature of the secondary flow and
provides this information to the controller
The former requirement will be, by far, the via an input signal.
most common need when applying automatic
temperature control to a plate heat exchanger.
Controller
Desired
Output signal temperature
Input signal
Actuator
Sensor
Measured
temperature
Plate
Valve Heat
Exchanger
Steam Secondary
fluid
52
Steam and Plate Heat Exchangers
53
54
Steam and Plate Heat Exchangers
General
A plate heat exchanger consists of a
pack of thin corrugated metal plates
with openings for the passage of the
fluids. The plates are arranged in such a
way that to neighbour plates form a
channel. Every second channel is open
to the same fluid. The actual heat
transfer takes place between two
adjacent channels. The corrugations
support the plates against differential
Stea
pressure and create a turbulent flow in m
the channels. In turn, the turbulent flow
provides a high heat transfer efficiency,
making the plate heat exchanger very
compact compared with the traditional
shell-and-tube heat exchanger. Con
den
sate
Depending on which method is used when
Fig. 41 Flow principle in a plate heat exchanger
sealing the plates, the plate heat exchanger types
are divided into three groups:
The gasketed plate heat exchanger was
■ Gasketed plate heat exchangers invented in the early 1930’s. In those days it
(or plate & frame heat exchangers) was primarily used in the food industry, where
a heat exchanger that was easy to clean was
■ Brazed plate heat exchangers demanded to meet hygienic requirements. The
first steam heated plate heat exchangers were
■ All-welded plate heat exchangers launched during the 1940’s, serving as milk
pasteurisers. Over the years, the plate heat
Fig. 40 Performance limits for plate heat
exchangers exchanger concept has proven successful and it
Bar (g) has evolved into new product innovations. In the
50 late 1970’s, the brazed plate heat exchanger was
launched, which uses vacuum brazing
40 techniques to seal the plates. The next step in
All-Welded
Plate Heat the development process was taken in 1994,
30 Exchangers
when the all welded plate heat exchanger was
Brazed
Gasketed
Plate introduced. Here, the plates are laser welded,
20 Heat
Plate Heat
Exchangers
Exchangers forming a very strong construction. Today, the
plate heat exchanger is used in a multitude of
10
duties in chemical processing, HVAC, food
0
processing, marine / off shore applications and
-50 0 100 200 300 Temp. (°C) refrigeration.
55
The gasketed plate heat
exchanger
In the gasketed plate heat exchanger
(frame & plate heat exchanger), the plates
are fitted with elastomeric gaskets which
seal the channels and direct the fluids into
alternate channels. The plate pack is
assembled between a frame plate and a
pressure plate, and compressed by
tightening bolts fitted between these plates.
The channel plates and the pressure plate
are suspended from an upper carrying bar
and located by a lower guiding bar, both
of which are fixed to the support column.
The physical design of the gasketed plate
heat exchanger allows easy cleaning and
modification of its capacity by adding or
removing plates. Fig. 42 The gasket plate heat exchanger
56
Steam and Plate Heat Exchangers
The gaskets
The most common gasket type in steam
heaters is the glue-free Clip-on gasket. Glue-free
gaskets are easy to change and have a longer
lifetime than glued gaskets. Glued gaskets are
preferred when the duty requires frequent
mechanical cleaning of the plates. The glue will
keep the gasket in the same position regardless
of how many times the unit is opened, which
reduces the risk of leakage. Furthermore, the
gasket will not fall off if the plates are cleaned
by means of a high pressure nozzle or manual
brushing.
57
The brazed plate heat applications where the presence of copper ions is
undesired.
exchanger Unlike the gasketed plate heat exchanger, the
brazed plate heat exchanger cannot be
The brazed heat exchanger is a variation of the
disassembled. The scrubbing action of the highly
traditional gasketed plate heat exchanger. It
turbulent flow retards fouling. If cleaning is
evolved from the conventional gasketed plate to
needed, the unit can be back-flushed to prevent
answer the need for a compact plate heat
clogging or chemically cleaned to eliminate scale
exchanger, suitable for high pressure and high
build-up.
temperature duties.
The brazed plate heat exchanger as
steam heater
The robust design makes it suitable for higher
pressure and temperature applications, but is also
a disadvantage, as the many contact points
between the plates make the heat exchanger
prone to thermal fatigue. This means that special
attention must be paid to the application it is used
in and which control method is applied.
Fig. 46 Flow principle in a brazed plate heat Generally, duties where the brazed plate heat
exchanger
exchanger may be exposed to large, sudden, or
Like the gasketed plate heat exchanger, the frequent changes in temperature and load must
brazed plate heat exchanger is constructed of a be avoided. An example of such a duty is
series of corrugated metal plates, but without instantaneous tap water heating with steam.
gaskets, tightening bolts, frame etc. Space heating is a suitable application for the
The brazed plate heat exchanger simply con- brazed plate heat exchanger, provided that a
sists of stainless steel plates and two end plates. proper control method is applied and the
All the plates are brazed together in a vacuum components in the control system are correctly
furnace to form an extremely compact and sized.
pressure/temperature resistant heat exchanger Primary steam two-port control with active
with superior heat transfer characteristics. condensate drainage is the preferred method, as
Copper is the usual brazing material. Nickel is this system will minimise the risk of thermal
used in its place where the heated media contains cycling, as long as the heat exchanger and the
ammonia, which would dissolve copper, or, in control components are correctly matched. Any
type of on/off control would almost inevitably
lead to thermal stress and must not be applied.
The brazed plate heat exchanger is a very
price competitive alternative to other heat
exchanger types. Its primary areas of use are in
space heating and simple industrial utility
applications.
58
Steam and Plate Heat Exchangers
Fig. 48 Laser welded plate pack Fig. 49 The all-welded plate heat exchanger,
the AlfaRex
59
Comparison between the plate heat exchanger and the
shell & tube heat exchanger
Thermal performance
The turbulent flow encouraged in a plate heat condensate within it. This can be achieved by
exchanger contributes to a very efficient heat introducing a condensate level control and
transfer, that is, the k-value is high. Compared utilising the lower part of the plate as a
with a shell & tube heat exchanger, it is, subcooler. It is very difficult to make a similar
typically, 3-5 times higher. This high thermal arrangement in a shell & tube heat exchanger in
efficiency has a price, and that is the pressure an economical way. Instead a separate subcooler
drop on the heated media side. Compared with a is needed.
shell & tube heat exchanger, the plate heat
exchanger normally requires a slightly higher
pressure drop to enable an efficient design.
Condensation temperature
60
Steam and Plate Heat Exchangers
Mechanical design
The shell & tube heat exchanger can be
designed for very high temperature and pressure
applications. The operating limits of today’s all-
welded plate heat exchangers are 350°C and
40 bar g which is sufficient for most applications.
Exotic materials of construction, such as
titanium and Hastalloy, are standard options for
the plates of a plate heat exchanger. When used in
a shell & tube heat exchanger this solution can be
very expensive, since much more material is
needed.
The tubes of shell & tube heat exchangers are
sensitive to vibrations, whereas plate heat
exchangers are much more resistant to vibration,
or any other type of pressure fatigue.
The inlet and outlet connections are usually all
located in the frame plate on a plate heat
exchanger. This simplifies the piping, compared
with a shell & tube heat exchanger.
The corrugations in the plates creates a very
turbulent flow, which efficiently retards fouling
Fig. 53 The swirling motion of the fluid retards
of the heat transfer surface. In a shell & tube heat fouling
exchanger, the flow is less turbulent, and
consequently the risk of fouling is greater, which
means that a shell & tube heat exchanger has to
be cleaned more often.
The vertical orientation of the plates makes
condensate drainage easier in the plate heat
exchanger than in a shell & tube heat exchanger,
where the tubes usually are horizontal.
61
Steam as the heating medium in plate heat exchangers
A major advantage of the plate heat exchanger is its outstanding thermal
efficiency, but other factors may influence the size of the plate heat exchanger.
By-pass arrangement
When the secondary side fluid is heated just
a few degrees, i.e. the flow rate is compara-
tively large, it is actually the allowable
secondary side pressure drop that sizes the plate
heat exchanger. This means that extra plates
need to be added to the design just to fulfil the
pressure drop requirement. This in turn, leads to
a thermally over surfaced plate heat exchanger.
The over surfacing not only increases the price,
it also makes the heat exchanger more difficult
to control. In many cases, this problem can be
overcome by introducing a by-pass on the Fig. 54 A secondary side by-pass arrangement
secondary side. This allows the flow rate
through the heat exchanger to be optimised,
reducing the heat transfer area, which can lead
to considerable cost savings. The temperature
rise of the heated medium will need to increase,
which will improve the stability of the
temperature control.
62
Steam and Plate Heat Exchangers
63
Design calculations of
plate heat exchangers
Plate heat exchangers are easily selected and To enable a good steam heater design the
designed using software developed by the plate following information should preferably be
heat exchanger manufacturers. Below, two known:
interfaces of Alfa Laval’s design software, are
shown. ■ The thermal duty
That is heat load, temperatures in/out of
Using this computer program, it is possible to the heated medium (or one temperature
optimise the steam heater design for any given and the flow rate), allowable pressure drop
duty. It can handle wet, saturated and super- on the secondary side, the state (pressure
heated steam, as well as almost any medium on and temperature) of the available steam.
the secondary side. Velocities of the fluids in The pressure drop on the steam side would
connections and channels as well as condensate normally not be considered.
exit temperature are calculated. The steam
heater design can be tailor made to fit any ■ Fouling
established control method. The control stall It is important to know whether the heated
point can also be found. fluid contains fibres or other fouling
substances, or, if the fluid itself is fouling.
64
Steam and Plate Heat Exchangers
65
Appendix I. Steam tables
66
Steam and Plate Heat Exchangers
67
Appendix I. Steam tables (continued)
68
Steam and Plate Heat Exchangers
69
Appendix II. Stall Chart
70
Steam and Plate Heat Exchangers
71
The world leaders in steam controls
and plate heat exchangers