Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

TREASURY DEPT.

ACCOUNTING DEPT. FRESH AIR REQUIREMENT=17CFM


FRESH AIR INSTALED=0CFM
EXHAUST AIR REQUIREMENT=54CFM
AIR PURIFIER
AIR PURIFIER
TREASURY & AUDIT DEPT.
ACCOUNTING DEPT EXHAUST AIR INSTALLED=0CFM

FRESH AIR REQUIREMENT=174CFM


FRESH AIR INSTALLED=439CFM INSTALLATION OF NEW EXHAUST FAN
REQUIRED:54CFM
EXHAUST AIR REQUIREMENT=1167CFM
EXHAUST AIR INSTALLED=439CFM FRESH AIR GRILL W/ VD

EF1 EF 2

TAILEE BBRAND
FRESH AIR FAN, 439 CFM
TAILEE BBRAND FRESH AIR GRILL W/ VD
EXHAUST FAN, 439 CFM EF 5 EF 5
PROVIDE VOLUME DAMPER
FOR EVERY FRESH AIR GRILL HR DEPT. EF 3

FRESH AIR DUCT EXHAUST DUCT


( EXISTING ) ( EXISTING )

AIR PURIFIER
HRD DEPT.

CAN WE RELOCATE 2 UNIT EXHAUST FAN


FROM HR ROOM TO EXTERNAL AFFAIRS AIR PURIFIER
CMG, TPD & SCM

ROOM?
EF 4
FRESH AIR GRILL W/ VD
NOTE:
FRESH AIR REQUIREMENT=255CFM
FRESH AIR REQUIREMENT=56CFM FRESH AIR INSTALLED=0CFM EF 6
AS PER PLAN, WE HAVE AROUND 565 CFM
LEGAL / MARKETING DEPT.
FRESH AIR INSTALLED=0CFM EXHAUST AIR REQUIREMENT=972CFM INSTALLED PER DIFFUSER

EXHAUST AIR REQUIREMENT=275CFM EXHAUST AIR INSTALLED=1130CFM


AIR PURIFIER
LEGAL & MARKETING DEPT.
EXHAUST AIR INSTALLED=2260CFM
AIR PURIFIER
CMG, TPD & SCM

FRESH AIR REQUIREMENT=49CFM


FRESH AIR GRILL W/ VD
FRESH AIR INSTALLED=0CFM
PROPOSED TAILEE BRAND
EXHAUST AIR REQUIREMENT=402CFM FRESH AIR FAN 439 CFM
INSTALLATION OF NEW EXHAUST FAN EXHAUST AIR INSTALLED=0CFM
SAME W/ EXISTING 565CFM

AIR PURIFIER AIR PURIFIER


N-WING MEETING ROOMS & COMMON AREA HALLWAY S-WING MEETING ROOMS & COMMON AREA HALLWAY

AWNING WINDOW AWNING WINDOW AWNING WINDOW AWNING WINDOW AWNING WINDOW AWNING WINDOW AWNING WINDOW AWNING WINDOW AWNING WINDOW AWNING WINDOW

2FL - TLDC OFFICE