TECHNICAL REQUIREMENT AND GUARANTEEE SCHEDULE FOR

33/0.415 KV, 3 PHASE 100 KVA STATION TRANSFORMER

REB Bidders
Description Unit Requirement Guaranteed
Values
STATION SERVICE TRANSFORMERS
1. Manufacturer's Name Required Danish Private
Limited
2. Manufacturer's Address Required Jaipur, India
3. Type Required Oil cooled
4. Applicable Standard Required IEC 60076
5. Rated power kVA 100 100 kVA
6. Rated voltage
- High voltage winding kV 33 33
- Low voltage winding at nominal tap - V 415/240 415/240
no load
7. Vector diagram Dyn11 Dyn11
8. Rated frequency HZ 50 50
9. Type of cooling ONAN ONAN
10. Type of bushing
- High voltage Required Porcelain bushing
- Low voltage Required Porcelain bushing
11. Off load tap-changer
- Rated tap kV 33 33
- Tap range % + 5 to - 5 + 5 to - 5
- Number of taps Taps 5 5
12. Impedance voltage at 75deg C, at
nominal ratio and rated power % 4% 4% IEC Tol.
13. Temperature rise at rated power Required
(Max. ambient temp: 40deg C)
- Oil by thermometer deg. 60 60 deg C
C
- Winding by resistance method deg. 65 65 deg C
C
14. Dimensions and Total Weight
1100 x 860 x 1790
- Height x width x depth mm Required mm
approx
- Total weight kg Required 790 kgs approx
18. Core loss at reted frequency
and rated voltage at nominal kW Required 360 W (IEC Tol)
tap
19. Copper loss at full load, at
rated frequency at nominal kW Required 2100 W (IEC Tol)
tap