Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

1 2 3 4 5 6 7 8

FOR TENDER DRAWINGS

NOTES : DATE OF ISSUE : 30 JUNE 2021

: IN FUTURE PHASE GENERAL NOTES :


1. This drawing is indicative of the design intent only and does not purport to
identify or solve completely the problems related to the construction.
: IN PHASE 1
A 2. Before proceeding with the works, the contractor is to submit to the
Design consultants for approval of shop drawings showing all aspects of A
the construction details.
3. Contractor is to check and verify all dimensions before commencement
of work.

4. All drawings to be read in conjunction with other Architectural, M&E and


Structural drawings.

C 01.07.21 REVISED FOR TENDER ISSUE


B 30.06.21 REVISED FOR TENDER ISSUE
A 17.06.21 FOR TENDER ISSUE
REV DATE DESCRIPTIONS

GEN B1 2500Kw
3150Kw (Cos φ = 0.8)
1) GEN B-REDUNDANT 2500Kw (Cos φ = 0.8) GEN B2 2500Kw (Cos φ = 0.8) GEN B3 2500Kw (Cos φ = 0.8) GEN B4 2500Kw (Cos φ = 0.8) GEN B5 2500Kw (Cos φ = 0.8)

N
G CONTINUOUS RATING
400V/1500rpm 3PHASE 50Hz N
G CONTINUOUS RATING
400V/1500rpm 3PHASE 50Hz N
G CONTINUOUS RATING
400V/1500rpm 3PHASE 50Hz N
G CONTINUOUS RATING
400V/1500rpm 3PHASE 50Hz N
G CONTINUOUS RATING
400V/1500rpm 3PHASE 50Hz N
G CONTINUOUS RATING
400V/1500rpm 3PHASE 50Hz

DEVELOPER/OWNER
E E E E E E
NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)
B B
+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2
DM DM DM DM DM DM
PT. Bank Central Asia Tbk
E/f O/V U/V OL Rp E/f E/f O/V U/V OL Rp E/f E/f O/V U/V OL Rp E/f E/f O/V U/V OL Rp E/f E/f O/V U/V OL Rp E/f E/f O/V U/V OL Rp E/f Menara BCA Grand Indonesia
PF Hz
UPS
W Hr
AMF
A CT 3X GCP-B1 PF Hz
UPS
W Hr
AMF
A CT 3X GEN-DB-B PF Hz
UPS
W Hr
AMF
A CT 3X GCP-B2 PF Hz
UPS
W Hr
AMF
A CT 3X GCP-B3 PF Hz
UPS
W Hr
AMF
A CT 3X GCP-B4 PF Hz
UPS
W Hr
AMF
A CT 3X GCP-B5 Jl MH Thamrin No. 01 , Jakarta 10310
LOCATED AT: GEN-SET RM LOCATED AT: GEN-SET RM LOCATED AT: GEN-SET RM LOCATED AT: GEN-SET RM LOCATED AT: GEN-SET RM LOCATED AT: GEN-SET RM
DCP

DCP

DCP

DCP

DCP

DCP
MES MES MES MES MES MES
GEN-1
DL102
GEN-1
DL102
GEN-1
DL102
GEN-1
DL102
GEN-1
DL102
GEN-1
DL102 LEAD DESIGN CONSULTANT
M ACB-3P M ACB-3P M ACB-3P M ACB-3P M ACB-3P M ACB-3P
5000A 5000A 5000A 5000A 5000A 5000A

6300A,380V,100kA,COPPER BUSBAR 6300A,380V,100kA,COPPER BUSBAR 6300A,380V,100kA,COPPER BUSBAR 6300A,380V,100kA,COPPER BUSBAR 6300A,380V,100kA,COPPER BUSBAR 6300A,380V,100kA,COPPER BUSBAR
A
ACB-3P ACB-3P ACB-3P MCCB MCCB MCCB MCCB ACB-3P M ACB-3P ACB-3P ACB-3P ACB-3P ACB-3P ACB-3P ACB-3P ACB-3P MCCB MCCB ACB-3P ACB-3P ACB-3P MCCB MCCB ACB-3P ACB-3P ACB-3P MCCB ACB-3P ACB-3P ACB-3P MCCB MCCB
M
5000A
M
5000A
M
5000A 3P 3P 3P 3P 3P
M
5000A 5000A
M
5000A
M
5000A
M
5000A
M
5000A
M
5000A
M
5000A
M
5000A 3P 3P
M
5000A
M
5000A
M
5000A 3P 3P
M
5000A
M
5000A
M
5000A 3P 3P
M
5000A
M
5000A
M
5000A 3P 3P NTTFACILITIES,INC.
R Y G R Y G R Y G 100AT 100AT 200AT 200AT 200AT G Y R G Y R G Y R G Y R G Y R G Y R R Y G R Y G R Y G 100AT 100AT R Y G R Y G R Y G 100AT 100AT R Y G R Y G R Y G 100AT R Y G R Y G R Y G 100AT 100AT
2A 2A 2A 2A 2A 2A 2A 2A 2A 2A 2A 2A 2A 2A 2A 2A 2A 2A 2A 2A 2A nIdoneasPiWRO
Wisma 46-Kota BNI, 5F,Jl.Jend. Sudirman Kav.1,
NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)
Jakarta 10220, Indonesia
QUANTITY SURVEYOR
JUST BREAKER

JUST BREAKER

JUST BREAKER

JUST BREAKER

JUST BREAKER

JUST BREAKER
+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2
NYY 4x35mm2

NYY 4x35mm2

NYY 4x35mm2

NYY 4x35mm2

NYY 4x35mm2

NYY 4x35mm2

NYY 4x35mm2

NYY 4x35mm2

NYY 4x35mm2

NYY 4x35mm2
+ NYA 16mm2

+ NYA 16mm2

+ NYA 50mm2

+ NYA 50mm2

+ NYA 50mm2

+ NYA 16mm2

+ NYA 16mm2

+ NYA 16mm2

+ NYA 16mm2

+ NYA 16mm2

+ NYA 16mm2

+ NYA 16mm2

+ NYA 16mm2
NYY 4x95mm²

NYY 4x95mm²

NYY 4x95mm²
NO CABLE

NO CABLE

NO CABLE

NO CABLE

NO CABLE

NO CABLE
C
C
CP CP CP CP SCOPE OF WORK CP CP SCOPE OF WORK CP CP SCOPE OF WORK CP CP SCOPE OF WORK

TO TO TO TO TO
BY MECHANICAL
TO TO
BY MECHANICAL
TO TO
BY MECHANICAL
TO TO
BY MECHANICAL PT Lantera Sejahtera Indonesia
LOAD BANK LVDP-B1-2 LOAD BANK LOAD BANK LVDP-B2-2
CONTRACTOR LOAD BANK LVDP-B3-2
CONTRACTOR LOAD BANK LVDP-B4-2
CONTRACTOR LOAD BANK LVDP-B5-2
CONTRACTOR Level 18 Ratu Plaza Office Tower, Jl. Jenderal Sudirman Kav 9,
M M M M M M M M M M Jakarta 10270, Indonesia
C FAF-L1-G-B13 FAF-L1-G-B14 FAF-L1-G-B11 FAF-L1-G-B12 FAF-L1-G-B15 FAF-L1-G-B16 FAF-L1-G-B19 FAF-L1-G-B20 FAF-L1-G-B21 FAF-L1-G-B22
Tel: (021) 739 7550, Fax: (021) 739 7846 C
SCOPE OF WORK BY
MECHANICAL CONTRACTOR ARCHITECT

ARCHITECTS,ENGINEERS,PLANNERS,PROJECT MANAGER & INTERIOR DESIGNERS

JALAN KAPTEN P.TENDEAN NO.6, MAMPANG PRAPATAN, JAKARTA 12790


TELP : (021) 7900290 (HUNT), FAX : (021) 7949094, Email : jasaferrie@cbn.net.id

R Y G R Y G NOTE: R Y G R Y G R Y G R Y G R Y G R Y G R Y G R Y G
2A 2A GEN-LVSB-B1 About control of Gen-set for IT load 2A 2A GEN-LVSB-B2 2A 2A GEN-LVSB-B3 2A 2A GEN-LVSB-B4 2A 2A GEN-LVSB-B5 CIVIL & STRUCTURE CONSULTANT
C/W M+E INTERLOCK - Receiving start signal from LVDP, duty & stand-by gen-set will start. C/W M+E INTERLOCK C/W M+E INTERLOCK C/W M+E INTERLOCK C/W M+E INTERLOCK
LOCATED AT: GEN-SET RM - If duty gen-set can supply to LVDP, stand-by gen-set stops. LOCATED AT: GEN-SET RM LOCATED AT: GEN-SET RM LOCATED AT: GEN-SET RM LOCATED AT: GEN-SET RM
ACB ATS ACB DL102 - If duty gen-set cannot supply to LVDP(gen-set is broken, CB in GEN-LVSB is broken, or etc.), ACB ATS ACB DL102 ACB ATS ACB DL102 ACB ATS ACB DL102 ACB ATS ACB DL102
4P M 4P M power supply will switch to from stand-by gen-set. 4P M 4P M 4P M 4P M 4P M 4P M 4P M 4P M PT. PERKASA CARISTA ESTETIKA
5000AT 5000AT - When GEN-LVSB is inspected, CB from Gen-set to GEN-LVSB should be opened to make inside 5000AT 5000AT 5000AT 5000AT 5000AT 5000AT 5000AT 5000AT
ST ST of LVSB non-voltage. And if utility power fails, Gen-set will start and supply power directly to LVDP. ST ST ST ST ST ST ST ST
65kA 65kA 65kA 65kA 65kA 65kA 65kA 65kA 65kA 65kA CONSULTING ENGINEERS
CL 0.5 15VA F C CL 0.5 15VA F C CL 0.5 15VA F C CL 0.5 15VA F C CL 0.5 15VA F C CL 0.5 15VA F C CL 0.5 15VA F C CL 0.5 15VA F C CL 0.5 15VA F C CL 0.5 15VA F C
PLAZA KEBUN JERUK BLOK C7 & C8
5000/5A CT E O
5000/5A CT E O
5000/5A CT E O
5000/5A CT E O
5000/5A CT E O
5000/5A CT E O
5000/5A CT E O
5000/5A CT E O
5000/5A CT E O
5000/5A CT E O JL. RAYA PEJUANGAN JAKARTA 11530
DTL DTL DTL DTL DTL DTL DTL DTL DTL DTL DTL DTL DTL DTL DTL DTL DTL DTL DTL DTL PHONE (021) 5331182 (HUNTING)
CL 0.5 15VA TO BAS CL 0.5 15VA TO BAS CL 0.5 15VA TO BAS CL 0.5 15VA TO BAS CL 0.5 15VA TO BAS CL 0.5 15VA TO BAS CL 0.5 15VA TO BAS CL 0.5 15VA TO BAS CL 0.5 15VA TO BAS CL 0.5 15VA TO BAS FAX (021) 5331184
5000/5A CT DM 5000/5A CT DM 5000/5A CT DM 5000/5A CT DM 5000/5A CT DM 5000/5A CT DM 5000/5A CT DM 5000/5A CT DM 5000/5A CT DM 5000/5A CT DM EMAIL : pce@cbn.net.id

R Y G R Y G R Y G R Y G R Y G R Y G R Y G R Y G R Y G R Y G
2A 2A 6300A,380V,65kA,COPPER BUSBAR 2A 2A 6300A,380V,65kA,COPPER BUSBAR 2A 2A 6300A,380V,65kA,COPPER BUSBAR 2A 2A 6300A,380V,65kA,COPPER BUSBAR 2A 2A 6300A,380V,65kA,COPPER BUSBAR
MEP CONSULTANT
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
SCOPE OF WORK 4P 4P 4P 4P 4P 4P 4P 4P 4P 4P 4P SCOPE OF WORK
BY GENSET 5000AT 5000AT 5000AT 5000AT 5000AT 5000AT 5000AT 5000AT 5000AT 5000AT 5000AT BY GENSET
65kA 65kA 65kA 65kA 65kA 65kA 65kA 65kA 65kA 65kA 65kA
CONTRACTOR R Y G R Y G R Y G R Y G R Y G R Y G R Y G R Y G R Y G R Y G R Y G CONTRACTOR

D 2A 2A 2A 2A 2A 2A 2A 2A 2A 2A 2A Consulting Engineers, Planners, Managers

PT Meinhardt Indonesia
D
NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)

NYY 10(4x1Cx300mm2)
SCOPE OF WORK SCOPE OF WORK Grha Tirtadi 3/F, Jalan Raden Saleh No. 20 Jakarta 10430 - Indonesia
BY ELECTRICAL BY ELECTRICAL Tel : (62-21) 392 9911 Fax : (62-21) 392 5995
Email : indo@meinhardt.co.id
+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2

+ NYA 300mm2
CONTRACTOR CONTRACTOR

NOTE:
In Phase 1, CRAH load will be 278.4kW but generator capacity will be 2,000kW,
so generator for CRAH will be operated at low load. In order to avoid low load operation,
in Phase 1, CRAH load will be supplied from generator for IT.
And in Phase 2, generator for CRAH can avoid low load operation, so we will install dedicated generator for CRAH.

TO TO TO TO TO TO TO TO TO TO TO
LVDP-B1-1 LVDP-B1-2 LVDP-CR-B (FOR PHASE 1) LVDP-B2-1 LVDP-B2-2 LVDP-B3-1 LVDP-B3-2 LVDP-B4-1 LVDP-B4-2 LVDP-B5-1 LVDP-B5-2

MCC-ACMV-GR-B1/1 C
ATS,4P
200A
MCCB,4P
200A

"SEE DRAWING NO. EL.546"

E E

Project title

BCA NEW DATA CENTER


SCALE: DRAWN BY:
NTS IS
F DATE: CHECKED BY: F
30.06.21 DWM
DRAWING TITLE:
DATA CENTER 1
ELECTRICAL SERVICES
DC BLOCK FOR IT LOAD.4
PART 6
DRAWING NO: REV:

FOR TENDER EL403.6A C

1 2 3 6 7 8