UAE - MISSION TO
SELF CONTAINED AIR CONDITIONING UNIT SCHEDULE
SUPPLY FAN EVAPORATOR CONDENSER COMPRESSOR THE UNITED
L

TAG LOCATION SERVICE MANUFACTURER ECONOMIZER TYPE AIRFLOW


FAN TYPE
ESP TSP
Fan
Power
Motor Size
O.A.
(CFM)
EAT
LAT
OFF UNIT COIL CAPACITY
Tons
Refrig
lb/ton
COIL
SENSIBLE
EER
EVAP COIL
EWT LWT
FLUID
FLOW
WATER
PR. DROP
POWER
(kW)
Ref. Type
NATIONS
(CFM) (inH2O) (inH2O) (HP TOTAL) DB WB DB WB (MBH) (lbs) CAPACITY ROWS/FPI (FT H2O)
(BHP) (GPM)
(MBH)

AC-1-1 1ST FLOOR AUDITORIUM THERMOPLUS WATER SIDE 1400 1.25 0.89 1.5 430 81.4 68 55.6 54.2 61.07 39.2 16.1 87 102 12.5 4.6 3.6 R410A
AC-1-2 1ST FLOOR MAIN LOBBY THERMOPLUS WATER SIDE 3100 1.25 1.5 3 1250 83.3 69 55.5 53.6 151.5 93.5 15.2 87 102 32 3.6 9.6 R410A 315 EAST 46TH STREET, NEW
AC-1-3 1ST FLOOR LOBBY A THERMOPLUS AIR SIDE 1000 PLUG 1 1.67 0.35 0.5 1000 95 75 55.1 53.8 72.4 43.3 15.1 4/12 87 102 15 5.5 4.6 R410A YORK, NEW YORK 10017
AC-2-1 2ND FLOOR PRE-FUNCTION THERMOPLUS WATER SIDE 5400 PLUG 1.5 2.25 7 10 2700 85.1 70 52 51.3 308 189 16.1 5/12 87 102 64 5.8 19.1 R410A
OWNER
AC-2-2 2ND FLOOR MULTI PURPOSE ROOM THERMOPLUS WATER SIDE 5100 PLUG 1.5 2.21 3.35 4 2100 83.5 69.3 51.7 51 282 172 16.4 5/12 87 102 58.5 1.8 16.9 R410A
15 R410A
Permanent Mission of the United Arab
AC-3-1 3RD FLOOR KITCHEN MAKEUP AIR THERMOPLUS WATER SIDE 2000 1 3.01 1.5 2000 95 75 54 53 142 85 16.4 87 102 30
Emirates to the United Nations New York
AC-9-1 9TH FLOOR MECH SOUTH SIDE TYPICAL OFFICES MAMMOTH AIR SIDE 12000 FAN WALL 2.5 3.72 10.07 10.5 1500 80.07 66.35 52.5 51.1 578 387 15.5 6/10 87 102 95 2.7 36.5 R410A
3 Dag Hammarskjold Plaza
AC-9-2 9TH FLOOR MECH NORTH SIDE TYPICAL OFFICES MAMMOTH AIR SIDE 9600 FAN WALL 2.5 3.93 8.36 9 2400 82.15 67.66 52.7 51.3 500 330 15.4 6/12 87 102 80.8 2.5 30.8 R410A 305 East 47th Street, 7th Floor, New York, NY 10017
K

AC-9-3 9TH FLOOR MECH 7TH FLOOR AAON AIR SIDE 5500 2 3.44 5.16 8 1650 80.85 66.54 56.2 54.3 212 157.4 12.2 6/12 87 102 35 3.1 R410A
Fisher Brothers Management
AC-9-4 9TH FLOOR MECH 8TH FLOOR AAON AIR SIDE 5500 2 3.44 5.16 8 1650 80.85 66.54 56.2 54.3 212 157.4 12.2 6/12 87 102 35 3.1 R410A
299 Park Avenue, New York, New York 10171

SELF CONTAINED AIR CONDITIONING UNIT SCHEDULE (CONT.)


ARCHITECT

HOT WATER COIL DEMAND ELECTRICAL FILTERS MODEL REMARKS

TAG O.A.
EAT LAT TOTAL CAPACITY EWT LWT FLUID FLOW WATER PR. DROP
VFD (Y/N)
CONTROL
VENTILATION MCA MOCP FILTER AREA
WEIGHT LOUVERED PENTHOUSE SCHEDULE
(CFM) FPP CP (Y/N) VOLT/PH/HZ TYPE TAG MODEL CFM PD (IN WG) THROAT WIDTH THORAT LENGTH UNIT LENGTH UNIT WIDTH HEIGHT REMARKS
(MBH) (GPM) (FT H2O) (A) (A)
(HEATING)
PH-R-1 ESD435P 45,000 0.23 80 80 88 88 60 2' ROOF CURB Skidmore, Owings & Merrill LLP
AC-1-1 430 48.5 103.2 83.1 180 160 8.5 5.9 - CP-1 Y N 208/3/60 25 40 MERV-13 382 KACE-060H5AARS-654G HOT GAS REHEAT
14 Wall Street, New York, NY 10005
AC-1-2 1550 35 102.6 227.2 180 160 23.3 12 FPP-A CP-1 Y N 208/3/60 14 20 MERV-13 775 KACE-144V5AART-654G HOT GAS REHEAT
J
NOTES: STRUCTURAL ENGINEER
AC-1-3 1000 0 100.6 109 180 160 6.0 6.1 FPP-A CP-1 Y N 208/3/60 30 50 4 MERV-13 306 KACE-048V5AART-685G HOT GAS REHEAT 1. ARCHITECT TO SELECT COLOR & FINISH OF LOUVERED PENTHOUSE.
HOT GAS REHEAT, PLUG FAN, PROVIDE Desimone Consulting Engineers
AC-2-1 2700 35 97.4 382 180 160 39.0 5.5 FPP-A CP-1 Y Y 208/3/60 134 175 19.75 MERV-13 1878 KACE-240V55AART-685G SIDE ACCESS FOR COMPRESSORS 18 West 18th Street, New York, New York 10011
HOT GAS REHEAT, PLUG FAN, PROVIDE
AC-2-2 2100 41.2 97.1 309 180 137 15.0 9 - CP-1 Y Y 208/3/60 88 110 19.75 MERV-13 1878 KACE-240V55AART-685G-1 SIDE ACCESS FOR COMPRESSORS MEP ENGINEER / IT / LEED CONSULTANTS

AC-3-1 2000 0 95.5 239 180 160 24.5 8 FPP-A CP-1 Y N 208/3/60 19 25 MERV-13 KACE-084H5AARS-654G Cosentini Associates
AC-9-1 - 60 87.3 355 180 160 36.4 6.2 FPP-A - Y N 460/3/60 90.3 110 40 MERV-13 6700 VVX-473-GHST 2 Pennsylvania Plaza, New York, New York 10121
AC-9-2 - 60 86.5 276 180 160 27.2 5.1 FPP-A - Y N 460/3/60 75.3 90 30 MERV-13 6600 VVX-393-GHST
CODE CONSULTING
AC-9-3 - 60 75.0 90.8 180 160 8 - FPP-A - Y N 460/3/60 50 70 MERV-13 1400 SB-018-3-0-E80A-000
AC-9-4 - 60 75.0 90.8 180 160 8 - FPP-A - Y N 460/3/60 50 70 MERV-13 1400 SB-018-3-0-E80A-000 Code Consultants, Inc.
215 W. 40th Street 15th Floor, New York, NY 10018
I
NOTES: 6. PROVIDE AIR FLOW METERS FOR O.A. MONITORING & SUPPLY 12.PROVIDE ECONOMIZER FOR ALL AC UNITS.
1. ALL UNITS PROVIDED WITH CONTROL PANEL FOR FIELD AIR. 13. PROVIDE (3) 24x24 ACCESS PANELS FOR ALL AC UNITS LOCATED VERTICAL TRANSPORTATION

MOUNTING. 7. PROVIDE FREEZE PROTECTION PUMP AS NOTED IN SCHEDULE ABOVE A NON-ACCESSIBLE CEILING.
Van Deusen & Associates
2. ALL UNITS NOT ON LEVELS 1 AND 2 TO BE ON 6" CONCRETE PAD 8. PROVIDE HOT GAS REHEAT AS NOTED ON SCHEDULE. 14. PROVIDE VIBRATION ISOLATION AS PER SPEC. CONDENSATE PUMP SCHEDULE
AND PROVIDED WITH VIBRATION ISOLATION PER SPEC. ALL 9. PROVIDE HOT WATER COIL HEATING FOR ALL UNITS ON 9TH 15. CONTRACTOR SHALL PROVIDE ALL UNITS WITH A PRESSURE INDEPENDENT 120 Eagle Rock Avenue, Suite 310, East Hanover,
TANK CAPACITY MOTOR DIMENSIONS New Jersey 07936
UNITS ON LEVELS 1 AND 2 TO BE ON 4" CONCRETE PAD AND FLOOR FOR MORNING WARM-UP. FLOW SETTING VALVE AND CONTROL VALVE ON RETURN PIPING, AND BALL UNIT NO. MANUF. MODEL NO. FLOW (GPH) LIFT (FT.) WEIGHT (LBS.) REMARKS
(LITERS) HP AMPS V (L x W x H) (IN.)
PROVIDED WITH VIBRATION ISOLATION AS PER SPEC. 10. ALL AIR CONDITIONING UNITS TO COMPLY WITH REQUIREMENTS ISOLATION VALVES ON SUPPLY AND RETURN PIPING. CIVIL / GEOTECH / SURVEY ENGINEER

3. MIXED AIR PLENUMS PROVIDED BY UNIT MANUFACTURER. IN UL-1995 OR CERTIFIED BY A NRTL PROGRAM. CP-1 LITTLE GIANT VCMX-20ULS-C 2.5 GPH 15 1.1 1/30 1.5 115 5.5 10.2 x 4.8 x 6.5 PROVIDE SAFETY SWITCH
Langan
4. ALL UNITS TO BE PROVIDED WITH DISCONNECT SWITCH. 11. ALL THE UNITS TO BE CERTIFIED BY A NRTL PROGRAM.
NOTES: 21 Penn Plaza, 360 West 31st Street, 8th floor
1. PROVIDE DISCONNECT. New York, NY 10001
SECURITY CONSULTANT

FAN POWERED TERMINAL UNIT SCHEDULE Thornton Tomasetti


ELEC. UNIT INFO.
40 Wall Street
SIZE CFM STATIC PRESSURE HEATING COIL NC LEVELS FAN
New York, NY 10005
H

BOX
TAG MANUF. MODEL WEIGHT
STYLE UNIT INLET OUTLET MAX MIN INLET DOWN MIN EAT LAT EWT LWT GPM RAD DIS CFM ESP HP MCA MOP VOLT/PH HAND EXTERIOR MAINTENANCE CONSULTANT
(LBS)
FP-A TITUS DTFS-F SERIES B 08 14.1x11.1 500 150 1 0.5 0.06 50 95 180 160 2.4 24 19 500 0.25 0.33 2.3 15 120/1 190 SEE PLANS
Entek Engineering, LLP
FP-B TITUS DTFS-F SERIES C 10 14.1x11.1 730 220 1 0.5 0.07 50 95 180 160 3.6 22 19 730 0.25 0.33 4 15 120/1 195 SEE PLANS
166 Ames Street
Hackensack, NJ 07601
FP-C TITUS DTFS-F SERIES C 10 14.1x11.1 900 270 1 0.5 0.11 50 95 180 160 4.4 25 23 900 0.25 0.33 4 15 120/1 195 SEE PLANS FOOD SERVICE CONSULTANT

FP-D TITUS DTFS-F SERIES D 10 16.5x14.62 950 285 1 0.5 0.12 50 95 180 160 4.6 24 17 950 0.25 0.50 8.5 15 120/1 270 SEE PLANS
Cini Little
FP-E TITUS DTFS-F SERIES D 10 16.5x14.62 1050 315 1 0.5 0.15 50 95 180 160 5.1 25 20 1050 0.25 0.50 8.5 15 120/1 270 SEE PLANS
261 Madison Avenue, 9th Floor
FP-F PRICE FDC-G2 SERIES 50 14 20x17.5 1950 1 0.5 0.15 50 95 180 160 9.5 36 2000 0.25 0.75 8.6 15 120/1 SEE PLANS New York, NY 10016
SIGNAGE CONSULTANT

NOTES: 4. PROVIDE 24 VAC TRANSFORMER. 7. ELECTRONIC DIGITAL CONTROLLER, MULTI-POINT CENTER


1. MIN. CFM SHOWN IS THE LOWEST MFG'S RECOMMENDED SET-POINT. 5. FOR CONTROL SEE SPECS AVERAGING SENSOR, OUTPUTS TO BMS FOR DAMPER ADJUSTMENT Pentagram Design, Inc.
G
2. REFER TO PLANS FOR LEFT HANDED OR RIGHT HANDED 6. PROVIDE 15'-0" OF 1" THICK ACOUSTICAL LINING DOWNSTREAM OF AND MONITORING. 204 Fifth Avenue
CONNECTIONS. FPB BOX 8. ALL FAN POWERED TERMINAL UNITS TO BE UL LISTED OR CERTIFIED New York, NY 10010
3. PROVIDE FIBRE-FREE LINING IN THE BOX. BY A NRTL PROGRAM. LIGHTING CONSULTANT

ELECTRIC HEATERS SBLD


CAPACITY 132 W 36th Street
UNIT TYPE LOCATION DIMENSIONS CFM VOLT/PH/HZ TOTAL AMPS MANUF. MODEL NOTES
(W) New York, NY 10018
TRENCH FIN-TUBE RADIATION SCHEDULE VERANO AS STANDARD CUH-A WALL HEATERS REFER TO DWGS 18"H x 35-1/2"L x 2-7/8"D 2000 - 208/1/60 10 STELPRO AMIR2008 1
AVERAGE ENCLOSURE Maximum Fan Max EUH-A ELECTRIC UNIT HEATER REFER TO DWGS. 12-1/16"W x 10-7/16"D x12-3/8"H 3000 300 208/1/60 12.9 INDEECO 925U03000VA 1,4,5,6
LENGTH RATING FLOW RATE AIRFLOW
TAG MODEL WATER TEMP DEPTH CERTIFICATION Current Voltage Power REMARKS
(IN) (BTU/H) (GPM) (CFM) EUH-B ELECTRIC UNIT HEATER REFER TO DWGS. 16.063"L x 21.75"D x 19.375"H 3000 650 208/1/60 17 INDEECO 233-FA-0036C 1,2,4,5,6
DEG F. (IN) (A) (VDC) (W)
FTR-A 29.5 VKN5-6.5/17/750-12 170 2,559 0.3 100 2.5 EN442 0.35 24 8.4 EUH-C ELECTRIC UNIT HEATER REFER TO DWGS. 12-1/16"W x 10-7/16"D x12-3/8"H 5000 300 208/1/60 21.2 INDEECO 925U05000VA 1

FTR-B 42.5 VKN5-6.5/17/1150-12 170 3,924 0.4 175 2.5 EN442 0.45 24 10.8 EUH-D ELECTRIC UNIT HEATER REFER TO DWGS. 16 3/8"W x 5"D x 23 1/4"H 1500 - 208/1/60 7 STELPRO AWFA1508T 1

FTR-C 61 VKN5-6.5/17/1550-12 170 5,289 0.6 255 2.5 EN442 0.6 24 14.4 EH-A ELECTRIC TRENCH HEATER REFER TO DWGS. 3-1/2" H x 7" D x 7'L 2500 N/A 208/1/60 15.4 JOHNSON CONTROLS SoHo-e 3
F

FTR-D 76.75 VKN5-6.5/17/1950-12 170 6,653 0.9 345 2.5 EN442 0.9 24 21.6
NOTES: 4. PROVIDE 4" SURFACE MOUNTING FRAME.
NOTES: 4. PROVIDE VALVE PACKAGE BY MANUFACTURER
1. PROVIDE UNIT WITH INTEGRAL THERMOSTAT. 5. PROVIDE DISCONNECT.
1. GRILL ON ENCLOSURE TO BE MINIMUM 50% FREE AREA. 5. 24V ACTUATOR ON/OFF
2. PROVIDE UNIT WITH EXPLOSION PROOF MOTOR. 6. BUILT IN TAMPER PROOF STAT.
2. TEMP CONTROL BY DANFOSS VALVE 6. TRENCH FIN-TUBE RADIATION TO HAVE CAPABILITY OF
3. PROVIDE UNIT WITH LINE VOLTAGE THERMOSTAT.
3. PROVIDE POWER PACK PSU 120V TO 24V SERIES CONNECTION. SERIES CONNECTION IS LIMITED TO
TWO RADIATORS.

H&V SCHEDULE WILLIAMS AS STANDARD LINEAR DIFFUSER SCHEDULE TITUS AS STANDARD


KEYPLAN
E
HEATING CAPACITY MOTOR REMARKS ACTIVE AIR
MAX MAXIMUM AIRFLOW
SIZE OF DUCT FRAME AND
SYMBOL TYPE DIFFUSER PER FOOT OF ACTIVE NO. & SIZE MANUF. MODEL NO. REMARKS
EXT. S.P. FAN HOT WATER COIL LENGTH DEFLECTION CONNECTION BORDER E. 47TH STREET
SYMBOL MODEL NO. CFM (IN.W.G.) FPP NC LENGTH
SPEED E.W.T. BHP HP V/PH/HZ
ROWS LD-1 LINEAR FLOW-BAR SEE ARCH 1 SLOT TITUS FL-10
L.A.T. MBH GPM L.W.T. SEE PLANS ADJUSTABLE 27 55 SEE PLANS PROVIDE PLENUM FBPI-10
DAG HAMMARSKJOLD PLAZA
COIL (CFM/LF) DIFFUSER DETAIL 1.0" EACH HIGH THROW
HV-C-1 AH-B-020 2115 1 1148 0 66.5 155 8 180 120 1 .75 1.5 120/1/60 Y LD-2 LINEAR FLOW-BAR SEE ARCH 1 SLOT TITUS FL-15
(CFM/LF) SEE PLANS ADJUSTABLE 27 72 SEE PLANS PROVIDE PLENUM FBPI-15
NOTES: DIFFUSER DETAIL 1.5" EACH HIGH THROW
1. PROVIDE FREEZE PROTECTION PUMPS FOR ALL H&V UNITS. LD-3 LINEAR FLOW-BAR SEE ARCH 1 SLOT TITUS FL-10
(CFM/LF) SEE PLANS ADJUSTABLE 27 55 SEE PLANS PROVIDE PLENUM FBPI-10
2. ALL H&V UNITS SHALL BE TESTED AND CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY PROGRAM. DIFFUSER DETAIL 1.0" EACH JET THROW
LD-4 LINEAR FLOW-BAR SEE ARCH 1 SLOT TITUS FL-15
(CFM/LF) SEE PLANS ADJUSTABLE 27 72 SEE PLANS PROVIDE PLENUM FBPI-15
DIFFUSER DETAIL 1.5" EACH JET THROW
E. 46TH STREET

NOTES : 4. SEE ARCHITECTURAL PLANS FOR EXACT LENGTHS & LOCATIONS.

D
VARIABLE REFRIGERANT FLOW - FAN COIL UNITS LG AS STANDARD 1. SEE PLANS FOR EXACT ACTIVE LENGTHS, PLENUM SIZES & AIR
FLOW QUANTITIES.
5.
6.
PROVIDE SAMPLES FOR ARCHITECTURAL REVIEW.
ALL DIFFUSERS IN TOILET ROOMS AND POOL ROOM TO BE SEAL
CONNECTED TO: SUPPLY FAN COOLING CAPACITY HEATING CAPACITY ELECTRICAL DIMENSIONS WEIGHT 2. TRIM VOLUME DAMPERS ARE UNACCEPTABLE. ALUMINUM.
Max 3. ALL CUSTOM COLORS & BORDER TYPES SHALL BE APPROVED BY
Min
ZONE AIR FLOW ENTERING POWER Circuit Overcurren NOMINAL ARCHITECT PRIOR TO ORDER.
UNIT TAG SERVING TYPE CONDENSING E.S.P TOTAL SENSIBLE ENTERING AIR TOTAL WxHxD Net MODEL NO. NOTES
CHANGEOVER RATE AIR SUPPLY Amps t TONNAGE
UNIT TAG (in. H2O) Btu/hr Btu/hr Btu/hr Protection
DEVICE CFM OFdb
OF DB OF WB V/P/HZ MCA MOP Inch lbs AIR INLET & OUTLET SCHEDULE TITUS
FCU-R-1,2 ROOF EMR MultiV ACCU-R-1 No 1,435 0.19 54,000 40,000 80 67 61,400 70 230/1/60 55x15x24-13/16 112 4.5 ARNU543BRA4 SIZE
TAG SERVICE MIN CFM MAX CFM MODEL REMARKS NOTES
FACE NECK

CD-1 SUPPLY DIFFUSER 50 170 12x12 OMNI FOR LAY-IN CEILINGS

VARIABLE REFRIGERANT FLOW - AIR-COOLED CONDENSING UNIT SCHEDULE LG AS STANDARD CD-2 SUPPLY DIFFUSER 171 300 12x12 OMNI FOR LAY-IN CEILINGS

COOLING CAPACITY HEATING CAPACITY REFRIGERANT CHARGE ELECTRICAL DIMENSIONS CD-3 SUPPLY DIFFUSER 100 175 24x24 OMNI FOR LAY-IN CEILINGS
C

NO. AMBIENT CONNECTION MIN


MAX NOMINAL MODEL CD-4 SUPPLY DIFFUSER 175 300 24x24 OMNI FOR LAY-IN CEILINGS
TAG DESCRIPTION AMBIENT Factory Add'l RATIO (%) OVERCURR RUNNING NOTES
MODULES DESIGN VOLTAGE/ CIRCUIT (WxHxD) WEIGHT TONNAGE NO. TR-A SUPPLY GRILLE 150 350 14x14 12x12 300 FS FOR WALL SUPPLY
Btu/hr DESIGN Btu/hr Charge Refrigerant ENT CURRENT
( OF DB / PHASE AMPS (inch) (lbs)
(OF DB) (lbs) (lbs) PROTECTIO (A) TR-B RETURN GRILLE 20 133 10x10 8x8 350 RL
WB) (MCA)
N (MOP)
TR-C RETURN GRILLE 150 300 14x10 12x8 350 RL
120,000 135,000 47/43 n/a 230/3 48-13/16 x 66-1/8 x 29-15/16 ARUN121B
ACCU-R-1 1 AIR COOLED HEAT PUMP 95 23.6 90 40.3 60 33.4 540 10 TR-D SUPPLY GRILLE 150 250 12x8 10x6 300 RL
TE4
TR-E SUPPLY GRILLE 150 250 10x10 8x8 300 RL 3 03 AUG 2018 BULLETIN NO. 05
2 01 JUN 2018 BULLETIN NO. 01
Single Duct Terminal Unit Schedule TITUS
NOTES:
TR-F
TR-G
SUPPLY GRILLE
SUPPLY GRILLE
50
-
150
-
8x8
18x10
6x6
16x8
300 RL
300 RL
1 6 FEB 2018
17 OCT 2017
22 DEC 2017
ISSUED FOR CONSTRUCTION DOCUMENTS
ISSUED TO DOB
ISSUED FOR MEP BID
17 OCT 2017 ISSUED TO DOB
NC AT 1. ALL UNITS PROVIDED WITH CONTROL PANEL FOR FIELD TR-H RETURN GRILLE 375 1800 24x24 12x8 350 RL STAINLESS STEEL 27 SEPT 2017 ISSUED FOR DESIGN DEVELOPMENT
Size CFM Hot Water Heat Coil
Tag Model INLET MOUNTING. TR-G RETURN GRILLE 375 1800 24x24 12x8 350 RL
NO. DATE DESCRIPTION

@1" SP 2. ALL UNITS TO BE MOUNTED ON 6" CONCRETE PAD AND


B
Unit Max Min CFM MBH EAT EWT LAT APd GPM LWT WPd Rows FPI PROVIDED WITH VIBRATION ISOLATION PER SPEC. TR-I RETURN GRILLE 50 615 12x12 10x10 350 RL
VAV-A DESV 6 300 0 30 - - - - - - - - - - - 3. MIXED AIR PLENUMS PROVIDED BY UNIT MANUFACTURER. TR-J RETURN GRILLE 50 125 6x6 4x4 350 RL
DRAWING TITLE
VAV-B DESV 8 450 301 30 - - - - - - - - - - - 4. ALL THE UNITS TO BE CERTIFIED BY A NRTL PROGRAM. TR-K SUPPLY GRILLE 375 1800 24x24 12x8 300 RL
5. PROVIDE (1) 18x18 ACCESS PANEL FOR ALL VAV BOXES
VAV-C DESV 10 900 451 30 - - - - - - - - - - -
VAV-D DESV 12 1745 901 30 - - - - - - - - - - -
LOCATED ABOVE A NON-ACCESSIBLE CEILING. TR-L SUPPLY GRILLE 760 4575 42x24 40x22 350 RL
MECHANICAL
VAV-E DESV 6 300 0 30 300 13.2 55 180 95 1.3 160 NOTES:
SCHEDULE SHEET 2
CV-A DESV 6 300 0 30 - - - - - - - - - - - 1. TRIM VOLUME DAMPERS ARE UNACCEPTABLE.
2. ALL CUSTOM COLORS AND BORDER TYPES SHALL BE APPROVED BY ARCHITECT PRIOR TO ORDER.
3. REFER TO ARCHITECTURAL PLANS FOR EXACT LENGTHS AND LOCATIONS.
4. PROVIDE PXP LIGHT SHIELD FOR NON-DUCTED APPLICATION ON RETURN AIR GRILLE.
DRAWING NUMBER
5. ALL VOLUME DAMPERS IN NON-ACCESSIBLE CEILING TO BE PROVIDED WITH REMOTE ACTUATORS
OR CORD OPERATED DAMPER THRU FACE OF DIFFUSER.
A
6. ALL DIFFUSERS IN TOILET ROOMS AND POOL ROOM TO BE ALUMINUM.
M-402