NEMA TR 1

TRANSFORMERS~
REGULATORS~ AND REACTORS
STD.NEMA TR 1-ENGL 1993 11 6470247 0524462 267 11

NEMA Standards Publication No. TR 1-1993 (R2000)

Transformers, Regulators and Reactors

Published by:

National Electrical Manufacturers Association


1300 North 17th Street, Suite 1847
Rosslyn, VA 22209

©Copyright 2000 by the National Electrical Manufacturers Association. All rights including
translation into other languages, reserved under the Universal Copyright Convention, the Berne
Convention for the Protection of Literary and Artistic Works, and the International and Pan
American Copyright Conventions.

COPYRIGHT 2003; National Electrical Manufacturers Association Document provided by IHS Licensee=Aramco HQ/99807551 00, User=, 06/11/2003
01:58:16 MOT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
STD-NEMA TR 1-ENGL 1993 11 6470247 0524463 1T3 11

NEMA Standards Publication No. TR 1-1993 (R2000)

Transformers, Regulators and Reactors

Published by:

National Electrical Manufacturers Association


1300 North 17th Street, Suite 1847
Rosslyn, VA 22209

© Copyright 2000 by the National Electrical Manufacturers Association. All rights including
translation into other languages, reserved under the Universal Copyright Convention, the Berne
Convention for the Protection of Literary and Artistic Works, and the International and Pan
American Copyright Conventions.

COPYRIGHT 2003; National Electrical Manufacturers Association Document provided by IHS Licensee=Aramco HQ/99807551 00, User=, 06/11/2003
01:58:16 MOT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
STD. NEMA TR 1-ENGL 1993 • 6470247 0524LI64 03T •

TABLE OF CONTENTS

PARTO GENERAL . . . . • . . . . • . . . . . . . . . • . . . . . . . . . . . . . • . • • . . . . • . .
....
1
Preferred \bltage Ratings . . . . . . . • . . . • . . . . . . . . . • . . . . . . • . • • . . . . 1
Forced-Air (FA) and F~-0il (FOA) Ratings . . . . . . . . . . . • • • . • • . . • . . . . 1
Perfonnance . . . . . . . . . • . • • . . . . . . . . . . • . • • . . . . . . • . . . • . . . . • 2
Radio Influence \bltage Levels . . . . . . • . . . . . • • . . . . . . . . • . . . . • . . • • • 2
Power Facror of Insulation of Oil-Immersed
Transfonners . . . . . . . . . . . . . • . • . . . . . . . . . . . . . • . • . . . • • • . • . . 2
Audible SoWld Levels . . . . . . . . . . . . . . . . . • . • . . . • . • . • • . . . . . . . . . 2

PART1 roWER. 1RANSFORMERS . . . . . . . •. . •. . •. •. . . . . . . . . . . . . . . . . . S


PART2 DISTRIBUTION 1RANSFORMERS
Design Test for Enclosure Secwity of Padmounted
Cornparunental Transfonners . . . . . • • . . . . . . . . . . . . . . . • • . . . • . . • . . 7
PART3 SECONDARY NE1WORK TRANSFORMERS . . • . . . . . . . . . . • . . . . . . . . . . 9
PART4 DRY-TYPE 1RANSFORMERS . • . . . . . . . . . . . . . . . • . . • . • • . • . . • . . . . 11
PARTS UNIT SUBSTATION TRANSFORMERS . • . . . . . . . . • . . . . . . . . . • . . . • . • 13
PART& TERMINOLOOY . . . . . . . . . . . . . . . . . . . . . . . . • . . . . . . . . . . . . . . • 15
PART7 TEST CODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • . . . . . . . . • . . 17
Test Code for Measurement of Radio Influence
Voltage Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Transformer Test Report . . . . . . . . . . . . • . • . . • . . . . . . . . . . . . • . . . . • . 20
Transformer Impulse Test Report . . . . . . . . . . . . • . . • . • . . . . . . . . . . . • . • 21
Reactor Test Report . . . . . . . . . • . . . . . . . . . • . • . . . . . . . . . . . . . . • . . 22
PART I TRANSMISSION AND DISTRIBUTION VOLTAGE REGULATORS . . . . • . . . . . . . 23
PART9 CURRENT-LIMrfiNG REACI'ORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
PART10 ARC FURNACE TRANSFORMERS . . . • • • • . . . . . . . . . . . • • . . . . . • . . . • 27
PART11 SHUNT REACTORS . . . . . . . . . • . . . . . . . • . . . . . . . . . . . • . . . . . . . . 29
PART12 UNDERGROUND-TYPE THREE-PHASE DISTRIBUTION TRANSFORMERS . . . . . . 31

COPYRIGHT 2003; National Electrical Manufacturers Association Document provided by IHS Licensee=Aramco HQ/99807551 00, User=, 06/11/2003
01:58:16 MOT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
STD-NEMA TR 1-ENGL 1993 11 6470247 0524465 T76 11

FOREWORD

The standards appearing in this publication have been developed by the Transfonner Section and
have been approved for publication by the National Electrical Manufacturers Association. They are
used by the electrical industry to promote production economies and to assist users in the proper selec-
tion of transformers.
The Transformer Section is working actively with the American National Standards Committee,
C57, on Transfonners, Regulators and Reactors, in the development, correlation and maintenance of na-
tional standards for transfonners. This Committee operates under the procedures of the American Na-
tional Standards Institute (ANSI).
It is the policy of the NEMA Transformer Section to remove material from the NEMA Standards
Publication as it is adopted and published in the American National Standard C57 series. The NEMA
Standards Publication for Transformers, Regulators and Reactors references these and other American
National Standards applying to transfonners, and is intended to supplement, without duplication, the
American National Standards.
The NEMA Standards Publication for Transformers, Regulators and Reactors contains provision for
the following:

a. American National Standards adopted by reference and applicable exceptions approved by


NEMA, if any.
b. NEMA Official Standards Proposals. These are official drafts of proposed standards devel-
oped within NEMA or in cooperation with other interested organizations, for consideration
by ANSI. They have a maximum life of five years, during which time they may be approved
as American National Standards or adopted as NEMA Standards, or rescinded.
c. Manufacturing Standards. These are NEMA Standards which are primarily of interest to the
manufacturers of transformers and which are not yet included in an American National
Standard.
d. Standards Which Are Controversial. These are NEMA Standards, on which there is a differ-
ence of opinion within Committee C57. The NEMA version will be included in the NEMA
Standards Publication until such time as the differences between ANSI and NEMA are re-
solved.

NEMA Standards Publications are subject to periodic review and take into consideration user input.
They are being revised constantly to meet changing economic conditions and technical progress. Users
should secure latest editions. Proposed or recommended revisions should be submitted to:
Vice President, Engineering Deparunent
National Electrical Manufacturers Association
2101 L Street, N.W.
Washington, D.C. 20037-1526

SCOPE

This publication provides a list of all ANSI C57 Standards that have been approved by NEMA. In ad-
dition it includes certain NEMA Standard test methods, test codes, properties, etc., of liquid-immersed
transformers, regulators, and reactors that are not American National Standards.

COPYRIGHT 2003; National Electrical Manufacturers Association Document provided by IHS Licensee=Aramco HQ/99807551 00, User=, 06/11/2003
01:58:16 MOT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
STD-NEMA TR 1-ENGL 1993 11 6470247 0524466 902 11
TA 1-1993
Page 1

PARTO
GENERAL
The following American National Standards have been approved as NEMA Standards and should be inserted in this
PactO:

ANSI/IEEE C57.12.00-1988 General Requirements for Liquid-Immersed Distribution, Power and Regulating
Transformers
ANSI/IEEE C57.12.01-1989 General Requirements for Dry Type Power and Distribution Transformers
ANSI CS7.12.10-1988 Requirements for Transformers 230,000 volts and below, 8331958-8333110,417
kVA single-phase 7501862-60,000180,0001100,000 kVA three phase, including
supplements
ANSI CS7.12.70-1993 Terminal Markings and Connections for Distribution and Power Transformers
ANSI/IEEE C57.12.90-1993 Test Code for Liquid-immersed Distribution, Power & Regulating Transformers
and Guide for Short-Circuit Testing of Distribution & Power Transformers
AN SI/IEEE C57 .19.00-1992 General Requirements and Test Procedure for Outdoor Apparatus Bushings
ANSI/IEEE C57 .19 .01-1992 Standard Performance Characteristics & Dimensions for Outdoor Apparatus
Bushings
ANSI/IEEE C57 .92-1992 Guide for Loading Mineral-oil-immersed Power Transformers up to and including
100 MVA with 55C or 65C Average Winding Rise

The NEMA Standards TR 1-0.ot through TR 1-0.09 on the following pages (sec Part 0 Pages 1-9) also apply generally
to transformers.

0.01 PREFERRED VOLTAGE RATINGS 0.02 FORCED-AIR (FA) AND FORCED-OIL


Preferred system voltages and corresponding trans- (FOA) RATINGS
former voltage ratings are given in the American Na- Under the conditions of par. 5.11 of American Na-
tional Standard for Electric Power Systems and Equip- tional Standard ANSI/IEEE C57.12.00-1988, the rela-
ment--Voltage Ratings (60Hz), C84.1-1989. It is rec- tionship between self-cooled ratings and forced-air-
ommended that these ratings be used as a guide in the cooled or forced-oil-cooled ratings shall be in accordance
purchase and operation of transformers. with Table 0-1.

Table 0-1
FORCED-AIR AND FORCED-OIL RATINGS RELATIONSHIPS
Percent of Self-Cooled Ratings
Self-cooled Ratings• (k VA) With Auxiliary Cool I~
a ass Single Phaw Three Phaw First Stage Second Stage
OA/FA 501-2499 501-2499 115
OA/FA 2500-9999 2500-11999 125
OA!FA 10000 and above 12000 and above 133-1/3
OA/FA/FA 10000 and above 12000 and above 133-1/3 166-2/3
OA/FA/FOA 10000 and above 12000 and above 133-1/3 166-2/3
OA!FOAIFOA 10000 and above 12000 and above 133-1/3 166-2/3
•In the case of multi-winding transfonners or autotransfonncrs, the ratmgs g1ven are the cquivalcnttwo-wmding ratings_

COPYRIGHT 2003; National Electrical Manufacturers Association Document provided by IHS Licensee=Aramco HQ/99807551 00, User=, 06/11/2003
01:58:16 MOT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
STD.NEMA TR 1-ENGL 1993 11 6470247 0524467 849 11
TR 1-1993
Page2

PERFORMANCE
0.03 RADIO INFLUENCE VOLTAGE LEVELS probable condition of the insulation. It is not feasible to
The following values apply to liquid-filled transform- establish standard power-factor values for oil-immersed
ers. They do not apply to load tap changing during transformers because:
switching or to operation of auxiliary relays and control a. Experience has definitely proved that little or no
switches. relation exists between power factor and the
0.03.1 Distribution Transformers ability of the transformer to withstand the pre-
Radio influence voltage levels for distribution trans- scribed dielectric tests.
formers, for systems rated 69 kV and less, shall not b. Experience has definitely proved that the vari-
exceed 100 microvolts when measured in accordance ation in power factor with temperature is sub-
with Section 7.01. The test voltage shall be the line-to- stantial and erratic so that no single correction
neutral voltage corresponding to 110 percent excitation curve will fit all cases.
of the transformer. This will be the coil voltage for wye When a factory power-factor measurement of a trans-
connections and 1/3 times the coil voltage for delta former is required, the measurement should be made with
connections. the insulation at room temperature, preferably at or close
0.04 POWER FACTOR OF INSULATION OF to 20°C.
OIL-IMMERSED TRANSFORMERS 0.05 AUDIBLE SOUND LEVELS
While the real significance which can be attached to Transformers shall be so designed that the average
the power factor of oil-immersed transformers is still a sound level will not exceed the values given in Tables
matter of opinion, experience has shown that power 0-2 through 0-4 when measured at the factory in accord-
factor is helpful in assessing the probable conditions of ance with the conditions outlined in ANSI/IEEE
the insulation when good judgement is used. C57.12.90-1993.
The proper interpretation of power factor of oil-im- The guaranteed sound levels should continue to be per
mersed transformers is being given careful attention by Tables 0-2 through 0-4 until such time as enough data on
manufacturers in connection with the problems of (1) measured noise power levels becomes available.
selecting insulating materials, (2) sealing, and (3) proc- Sound pressure levels are established and published in
essing the transformers. However, it is the comparative this document. Sound power may be calculated from
values which are guides for the successful solution for sound pressure, using the method described in
these problems rather than an absolute value of power C57.12.90-I993.
factor.
Rectifier, railway, furnace, grounding, mobile and mo-
The generally accepted factory tests for proving the bile unit substation transformers are not covered by the
insulation level are the prescribed low-frequency tests tables. The tables do not apply during the time that power
and impulse tests given in the American National Stand- switches arc operating in load-tap-changing transformers
ard C57.12.90-1993. and in transformers with integral power switches.
When required, a factory power-factor test can be
made, and this measurement will be of value for compari-
son with field power-factor measurements to assess the

COPYRIGHT 2003 ; National Electrical Manufacturers Association Document pro....;ded by IHS Ucensee=Aramco HQ/9980755100, U ser= , 06/11/2003
0 1:58:16 MOT Questions or comm ents about this message: please call the Document
Policy Management Group at 1-800-451- 1584 .
0
0
-u
~
ble 0·2
~
....
AUDIBLE SOUND LEVELS Fl .-IMMERSED POWER TRANSFORMERS
~
-~ Column 1 • Clut' OA. Ow and FOW R.ttnvo
z
Column 2. Cla,.· FA and FOA Ftrot ot-ue "'" '&atY
Coolinv"t
I
m
Column 3 ·Straight FOA' Rattngs. FA' F.OA' Second·otage AuxiiaryCooling't
Average Sound E!!!!ivalanl Two-windi!!jl Aat!!!SI•
"~ Lewltt. 350 k\1 Btl and Below 450. SSO. 850 kV Bll 750 and 825 k\1 Bll 900 llnd 1050 k\1 BIL 1175 k\1 BIL 1300 k\1 BIL M>d Allow VI
"-
s: Decl:>alt 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 2 3 ~
~
~ .
~

z
I
G.'
57
58
59
700
1000
- 700
rr1
3
~ 1500 1000 >
0. 80
a 61 2000
~r ~
:;c
62 2500 ... ... 1500
63 3000 ... ... 2000 1:-'
64 4000 ... 2500 I
85 5000 ... 3000 rr1
68 8000 ... 4000 3000 z
67 7500 82504.4
7500
5000
8000
3750.4.4
5000
4000
5000
3125••
3750
"'
r
68 10000
611 12500 9375 7500 6250 8000 5000 1:-'
70 15000 12500 10000 7500 7500 6250 -D
71 20000 16667 12500 11375 10000 7500 Jl
w
72 25000 20000 20800 15000 12500 12500 11375
16667 15000 12500 ... 12500
73
74
75
30000
40000
50000
26667
33333
40000
25000
33333
41687
20000
25000
30000
20000
26667
20800
25000
20000
25000
16667
20000 20800
15000
20000
...
16667
...
...
12500
15000 12500 ... ...
I
76 60000 53333 50000 40000 33333 33333 30000 26667 25000 25000 20000 20800 20000 16667 15000 ... ... Er
-u o o .s:
~~ ~ n 60000 66687 66687 50000 40000 41687 40000 33333 33333 30000 26667 25000 25000 20000 20800 20000 18887 ... ~
c
60000 50000 50000 40000 41687 40000 33333 33333 30000 26667 25000 25000 20000 20800
~~a 100000 80000 83333 53333
78
80000 68687 66667 60000 53333 50000 50000 40000 41867 40000 33333 33333 30000 26667 25000
ru
~3 0~ lc:
711 106687 100000
4 1687 40000
s:
80 133333 133333 100000 80000 63333 60000 66667 66667 60000 53333 50000 50000 40000 33333 33333 ~
~~:!. 81 ... 186667 ... 106867 100000 100000 80MO 83333 80000 68687 66687 60000 53333 50000 50000 40000 4 1887
Qc:: cr
, g~ c
8 1/JI
" O (J) 82 ... ... 200000 ... 133333 133333 ... 108867 100000 100000 80000 83333 80000 86667 86687 80000 53333 50000 tn
; ~ ~·
• "r
83 ... 250000 ... ... 166667 ... 133333 133333 ... 108867 100000 100000 60000 833:r.l 80000 881187 881187 ru
64 300000 ... ... 200000 ... ... 186687 ... 133333 133333 ... 106667 100000 100000 80000 83333 .s:
:;! 3~ .s:
""'a.?: 85 ... 400000 250000 ... 200000 ... ... 168867 133333 133333 106667 100000
Er
~~ ;;- ... ... ... ...
~ g- ~ 86 ... ... 300000 250000 200000 166687 133333 133333
0:0
~ s.s
. S: :r
u;·o 87 ... ... ... ... 400000 300000 250000 ... 200000 1881187 ~
3 ii3 88 ... ... ... ... ... 400000 ... ... 300000 ... 250000 200000 0:0
...
.
~ 1!l
~ ~ 119 ... ... ... ... ... ... ... ... 400000 ... ... 300000 250000 tn
"'"'
"' go ... ... 400000 300000
iJO
(D _o

~~
0 •
111 400000
I
~_11 ' Ciu- ol cooling (""" 2.6.1 of Ametic8n National Standard C57.12.()().ta88.
~ 0
"Fi,.1· and teoond· l1age au•iliary oooltng (tee TA 1.0 .02).
~~
g i:l
tFOf column 2 and 3 ratings, the tound ,.,... ate with the au•iliary cooling aquip!Nnl in apetalion.
38 ttFO< Intermediate k\IA ratinvo , u. . the awrage tound lewl ol the nelfllatger kVA ra ting. -j
•"'
a 4 The equivalent two-winding ss·c or es·c ne1ing it defined • -.hall tha oum o1 the k\IA nl1ing ol all windinge. :0
44Sixty· o-n decibel• for all kVA nt1"'9' equal to 1hit or tmaller. "U-£
Dl .:...
IOtO
ctltO
c.> c.>
STD. NEMA TR 1-ENGL ],993 • 6470247 0524469 611 •
TR 1-1993
Page4

Table 0-3
AUDIBLE SOUND LEVELS FOR LIQUID-IMMERSED
DISTRIBUTION TRANSFORMERS AND NETWORK TRANSFORMERS
Equivalent Average Sound Level,
Two-winding k VA Decibels

0-50 48
51-100 51
101-300 55
301-500 56
750 57
1000 58
1500 60
2000 61
2500 62

Table 0-4
AUDIBLE SOUND LEVELS FOR DRY-TYPE TRANSFORMERS 15000-VOLT
NOMINAL SYSTEM VOLTAGE AND BELOW
A vcragc Sound
Equivalent Average Sound Level, Dcdbcls Equivalent Level, Decibels
Two-Winding Sclf·CCKIIL>d Sclf-ccKIIL>d Two-"inding VcntUated
kVA Ventilated• Sca!t>d• kVA Forced Air Cooled ••,t
0-50 50 .)()

51-150 55 55
151-300 58 57 3-300 67
301-500 60 59 301-500 67
501-700 62 61 501-833 67
701-1000 64 63 834-1167 67
1001-1500 65 64 1168-1667 68
1501-2000 66 65 1668-2000 69
2001-3000 68 66 2001-3333 71
3001-4000 70 68 3334-5000 73
'
4001-5000 71 69 S<Xll-6667 74
5001-6000 72 70 6668-8333 75
6001-7500 73 71 8334-10000 76
* Class AA rating
.. Does not apply to sealed-type transfonncrs
tCiass FA and AFA raungs

COPYRIGHT 2003; National Electrical Manufacturers Association Document provided by IHS Licensee=Aramco HQ/99807551 00, User=, 06/11/2003
01:58:16 MOT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
STD· NEMA TR 1-ENGL l.993 • 6470247 0524470 333 •
TA 1-1993
PageS

Part 1
POWER TRANSFORMERS
The American National Standard C57.12.1 0-1988 has The following other pans of this NEMA Publication
been approved as a NEMA Standard for power trans- No. TR 1 shall also apply:
fonners and should be inserted in this Part 1. a. Part 1 General
The ANSI/IEEE Standard CS7.92-1992, has been ap- b. Part6 Tenninology
proved by NEMA and should be inserted in this Part 1. c. Part 7 Test Code
d. Part 12 Underground-Type Three-Phase
Distribution Transformer

COPYRIGHT 2003 ; National Electrical Manufacturers Association Document provided by IHS Ucensee:::Aramco HQ/99807551 00 , User= , 06/11/2003
01 :58:16 MOT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
STD.NEMA TR 1-ENGL 1993 11 6470247 0524471 27T . .
TA 1-1993
Page7

Part 2
DISTRIBUTION TRANSFORMERS

The following American National Standards have been approved as NEMA Standards for distribution transformers
and should be inserted in this Part 2:

ANSI C57.12.20-1988 Requirements for Overhead-Type Distribution Transformers, 500 kVA and
Smaller: High Voltage, 34500 Volts and Below; Low Voltage, 7970!13800Y Volts
and Below
ANSI C57.12.21-1980 Requirements/or Pad-Mounted. Compartmental-Type, Self-Cooled, Single-Phase
Distribution Transformers with High-Voltage Bushings; (High-Voltage, 34500
GrdY/19920 Volts and Below; Low-Voltage,240!120 Volts; 167 kVA and Smaller)
ANSI C57.12.22-1989 Requirements/or Pad-Mounted, Compartmental-Type, Self-Cooled, Three-Phase
Distribution Transformers with High-Voltage Bushings 2500 kVA and Smaller;
High-Voltage, 34500 Grd Y/19920 Volts and Below; Low Voltage, 480 Volts and
Below
ANSI C57.12.23-1992 Requirements for Underground-Type SelfCooled Single-Phase Distribution
Transformers, with Separable Insulated 1/igh-Voltage Connectors; High-Voltage
24940 Grd Y/14400 Volts and Below; Low-Voltage 2401120; 167 kVA and Smaller
ANSI C57.12.25-1990 Requirements/or Pad-Mounted, Compartmental-Type. Self-Cooled, Single-Phase
Distribution Transformers with Separable Insulated 1/igh-Voltage Connectors:
High-Voltage 34500 Grd Yl 19920 Volts and below: Low-Voltage 2401120 Volts;
167 kVA and Smaller
ANSI C57.12.26-1987 Pad-Mounted Compartmental-Type Self-Cooled, Three-Phase Distribution Trans-
formers for use with Separable High-Voltage Connectors (High-Voltage 34500
Grd YIJ9920 Volts and Below: 2500 kVA and Smaller)
ANSI C57.91-1992 Guide for Loading Mineral Oil-Immersed Overhead-type Distribution Transform-
ers with 55C or 65C Average Winding Rise

The following parts of this NEMA Publication No. TR I shall apply for distribution transformers:
Part 0 General
Part 6 Terminology
Part 7 Test Code
Part 12 Underground-type Three-Phase Distribution Transformers
2.01 DESIGN TEST FOR ENCLOSURE SECURITY OF PADMOUNTED
COMPARTMENTALTRANSFORMERS
This standard provides a means for evaluating the security of enclosures for tmnsformcrs conforming to the following
American National Standards.

ANSI C57.12.21-1980 Requirements for Pad-Moumed, Compartmemal-Type, Self-Cooled, Single-Phase


Distribution Transformers with /I igh-Voltage Bushings; fl igh-Voltage, 34500 Grd
Yll9920 Volts and Below; Low-Voltage, 2401120 Volts; 167 kVA and Smaller
ANSI C57.12.22-1989 Requirements for Pad-Mounted, Compartmental-Type, Self-Cooled, Three-Phase
Distribution Transformers with Nigh-Voltage Bushings 2500 kVA and smaller;
High-Voltage, 34500 Grd Y/19920 Volts and Below; Low Voltage 480 Volts and
Below
ANSI C57.12.25-1990 Requirements for Pad-Mounted, Compartmental-Type, Self-Cooled, Single-Phase
Distribution Transformers with Separable Insulated High-Voltage Connectors:
1/igh-Voltage 34500 Grd Y/19920 Volts and below: Low-Voltage 2401120 Volts;
167 kVA and Smaller

COPYRIGHT 2003; National Electrical Manufacturers Association Previous pa~ Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 06/11/2003
i 01:58:16 MOT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
STD·NEMA TR 1-ENGL 1993 11 6470247 0524472 106 11
TA 1-1993
PageS

ANSI C57.12.26-1987 Pad-Mounted Compartmental-Type Self-Cooled, Three-Phase Distribution Trans-


formers for use with Separable High-Voltage Connectors (High-Voltage 34500
Grd Y/19920 Volts and Below: 2500 kVA and Smaller)

COPYRIGHT 2003; National Electrical Manufacturers Association Document provided by IHS Licensee=Aramco HQ/99807551 00, User=, 06/11/2003
01:58:16 MOT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
STD.NEMA TR 1-ENGL 1993 11 6470247 0524473 042 11
TR 1-1993
Page9

Part 3
SECONDARY NETWORK TRANSFORMERS

The American National Standard Requirements for The following other pans of this NEMA Publication
Secondary Network Transformers, Subway and Vaull No. TR 1 shall also apply for secondary network trans-
Types (Liquid Immersed), C57.12.40-1990, (with the fonncrs:
exception of paragraphs 5.5.4 and 11.5.2 on finishes) a. Part 0 General
have been approved as NEMA Standards for secondary
b. Part 6 Terminology
network transformers and should be inserted in this
c. Part 7 Test Code
Part 3.

COPYRIGHT 2003; National Electrical Manufacturers Association Document provided by IHS Licensee=Aramco HQ/99807551 00, User=, 06/11/2003
01:58:16 MOT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
STD-NEMA TR 1-ENGL 1993 11 6470247 0524474 T89 11
TR 1-1993
Page 11

Part 4
DRY-TYPE TRANSFORMERS

The following American National Standards have been approved as NEMA Standards for dry-type transformers and
should be inserted in this Part 4:

ANSIIIEEE C57.12.01-I989 General Requirements for Dry-type Distribution and Power Transformers
ANSI/IEEE C57 .12.91-1979 Test Code for Dry-Type Distribution and Power Transformers
ANSI C57.12.50-1989 Requirements for Ventilated Dry-Type Distribution Transformers, 1 to 500 kVA,
Single-Phase; and 15 ro 500 kVA, Three-Phase: With High-Voltage 601-34500
Volts, Low-Voltage 120-600 Volts
ANSI C57.12.51-1989 Requirements for Ventilated Dry-Type Power Transformers, 501 kVA and Larger,
Three-Phase With 1/igh-Voltage 601-34500 Volts, Low-Voltage 208Y/120-4160
Volts
ANSI C57.12.52-1989 Requirements for Sealed Dry-Type Power Transformers, 501 kVA and Larger,
Three-Phase, With 1/igh-Voltage 601-34500 Volts, Low-Voltage 208Y!120-4160
Volts
ANSIIIEEE C57 .94-1982 Recommended Practices for Installation, Application, Operation and Maintenance
of Dry-Type General Purpose Distribution and Power Transformers
ANSI/IEEE C57 .96-1989 Guide for Loading Dry-Type Transformers, Appendix to C57.12 Standards

• • • ~ I
COPYRIGHT 2003; National Electrical Manufacturers Association PreVl( Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 06/11/2003
01:58:16 MOT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
STD-NEMA TR 1-ENGL 1993 11 6470247 0524475 915 11
TR 1-1993
Page 13

PartS
UNIT SUBSTATION TRANSFORMERS

The following other parts of this NEMA Publication No. TR 1 shall also apply for unit substation transformers.
a Part 0 General
b. Part 6 Terminology
c. Part 7 Test Code

COPYRIGHT 2003; National Electrical Manufacturers Association PreviOUS paJ Doc~me~t ~rovided by IHS Licensee=Aramco HQ/9980755100, User=, 06/11/2003
01:58:16 MOT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
STD.NEMA TR 1-ENGL 1993 . . 6470247 0524476 851 . .
TR 1-1993
Page 15

Part 6
TERMINOLOGY

The ANSI/IEEE Standard C57 .12.80-1992, has been approved as a NEMA Standard for terminology and should be
inserted in this Part 6.

COPYRIGHT 2003 ; National Electrical Man ufacturers Association


STD-NEMA TR 1-ENGL 1993 . . 6470247 0524477 798 . .
TA 1-1993
Page 17

Part 7
TEST CODE

The American National Standard ANSI/IEEE One tenn inal of each winding not under test, the
C57.12.90-1987, has been approved as a NEMA Stand- ground terminal if one is available, shall be
ard for transformer tests and should be inserted in this connected to the tank and ground.
Part 7. d. Connections fortesting- Class A-2 Apparatus
This NEMA standard, Pan 7, shall also apply for The test voltage shall be applied to the winding
transformer tests. under test, with all terminals of the winding
The ANSI/IEEE Standard C57.98-1992, should be under test tied together (see Fig. 7-3).
inserted in this Part 7. e. Use of bushing capacitance tap
7.01 TEST CODE FOR MEASUREMENT OF If radio influence voltage is measured at the
RADIO INFLUENCE VOLTAGE LEVELS capacitance tap of the bushing, a suitable device
a. Apparatus shall be used which can be tuned with the bush-
The apparatus to be tested under this code can ing tap to ground capacitance at the measuring
be divided into two general classes as follows: frequency. This device shall constitute all cir-
cuit elements from the capacitance tap of the
Class 1- Potential-type transformer apparatus,
bushing to the radio noise meter.
such as transformers for step-up, step-
down or interconnected service, and The coaxial cable, an element of the device, may
some arrangements of regulating be any suitable impedance and need not be
transformers and autotransformers. lerminated in its characteristic impedance. The
Class 2- Series-type transformer apparatus, purpose of the device is to minimize the dividing
such as series transformers, shunt effect of the bushing capacitance and to convey
(iron core) reactors, current-limiting the radio influence voltage to the radio noise
reactors and some arrangements of meter with minimum attenuation. See Fig. 7-4
regulating transformers and auto- and 7-5.
transformers. f. Calibration for circuits using bushing capaci-
b. Equipment tance tap
The equipment and general method used in de- The calibration ratio will be determined by:
termining the radio influence voltage shall be in 1. Applying to the terminal under test the out-
accordance with the NEMA Standards Publica- put of a sine-wave signal generator at ap-
tion Methods of Measurement of Radio Influ- proximate! y 100 microvolts and atthe meas-
ence Voltage (RI V) of High-voltage Apparatus, uring frequency, or that of a pulse signal
107-1964 (R-1971, 1976, R-1992). For anal- generator at approximately 100 microvolts.
ternate method, see par. E, Use of Bushing Ca- 2. Measuring the voltage on the terminal with
pacitance Tap. the radio noise meter connected directly to
c. Connections for testing-Class A-1 Apparatus the terminal.
The test voltage shall preferably be impressed 3. Measuring, with the same radio noise meter,
across the winding under test (see Fig. 7-1). It the voltage appearing in the test circuit at the
may, however, be induced from a winding other location where the radio noise meter will be
than that being tested (see Fig. 7-2). In order connected during the radio influence voltage
that the results be comparable, the circuit ar- measurement on the transformer (a second
rangements and constants must be as shown in radio noise me1er shall be permitted to be
Fig. 7-1 or 7-2. The winding shall be tested first used instead, provided its relationship to the
with one end grounded and then with the other first radio noise meter has been established).
end grounded. 4. It shall be established that this calibration
The test on a reduced-voltage neutral terminal ratio remains valid over the radio influence
voltage range of interest.
shall correspond to the insulation class of the
neutral. Windings with one end solidly The ratio of the voltage measured with the radio noise
grounded obviously will receive no test on the meter at the terminal to the voltage measured with the
grounded end. radio noise meter at the normal location in the circuit

CO PY RIGHT 2003 ; Nation al Electrical Man ufacturers Association Document provided by IHS Licen see=Aram co HQ/99807551 00, User= , 06/11 /2003
Previous pa1 ~~:t~c~~a~~:e~~~~~r~~:a~~~8:_n~; 1~~~~~is message: please call the Docum ent
STD-NEMA TR 1-ENGL 1993 11 6470247 0524478 624 11
TR 1-1993
Page 18

which has been selected for the corona test on the trans- h. Precautions in making tests
former will be applied as a correction factor to the radio The following precautions should be observed
influence voltage reading obtained during the corona test in measuring the radio influence voltage. The
to detennine the actual radio influence voltage at the apparatus should be:
terminal of the winding under test. 1. Tested at approximately the same tempera-
g. Test voltage ture as the room in which the tests are made
The test voltage shall be determined from the 2. Located as to provide the outside clearnnces
preferred nominal system voltage in accordance recommended.
with 0.04 in Part 0, except that the test voltage
shall not exceed ll 0 percent of the rated voltage
of the winding on the highest tap connection.

COPYRIGHT 2003; National Electrical Manufacturers Association Document provided by IHS Licensee=Aramco HQ/99807551 00, User=, 06/11/2003
01:58:16 MOT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
STD.NEMA TR 1-ENGL 1993 .. 6470247 0524479 SbO ..
TA 1-1993
Page 19

z z

E
Fig. 7-1* Fig. 7·2*

z
A -Transformer under test
c B - Testmg transformer
B A
C -Coupling capac1tor

3 NM-Radio no1se meter


R -Terminating resistance
Z -Rad1o frequency choke

• Values for radio circuit clcmcms and deLailcd connections


shall conform lo lhc NEMA Standards Publication M£thods of
Measure~lll of Radio lnfluenu Voltage (RIV) of 1/igh-vo/tage
Fig. 7-3* Apparatus, 107-1964 (R 1971, 1976, R 1992).

TEST CIRCUITS FOR RADIO INFLUENCE MEASUREMENTS


USING THE BUSHING CAPACITANCE TAP:

cl CABLE

] B A
NM

Fig. 7-4

cl

Fig. 7·5
A -Transformer under test CABLE-Shielded cable
B -Testing transformer Z1 -Variable inductance
C 1 -High-voltage bushing capacitance R2 -Resistor
C2 -High-voltage bushing capacitance tap NM -Radio noise meter

COPYR IGHT 2003; National Electrical Manufacturers Association Docu ment provided by IHS Licensee=Aramco H019980755100, User= , 06/1 1/2003
01 :58:16 MOT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584 .
STD-NEMA TR 1-ENGL 1993 11 6470247 0524480 282 . .
TR 1-1993
Page 20

7.02 TRANSFORMER TEST REPORT


To facilitate safe and effective opemtion of tmnsformers it is recommended that the following information be included
in the test report:

Manufacturer's Name - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -__


Purchaser ______________________________________________________________________ -

Date of Test---------------- Purchaser's Order No.------------ Mfr.'s Ref. No.----------------


Cooling Class Phase _ Hertz ------------Insulating Fluid ------------------
Volts Volts Volts
Winding (1) kVA (2) kVA (3l _ _ _ _ _ _ _ _ _ kVA
{
Taps _________________________________________________________________________________

RESISTANCE, EXCITING CURRENT, LOSSES AND IMPEDANCE-Based on normal rating unless otherwise stated. Losses
and regulation are based on wattmeter measurements. For three-phase transformers the resistances given are the sum of
the three phases in series.

Watts Loss and Impedance at as·c


Resistance in Ohms
at as·c Exciting V V V
Current No Load
Serial No. Percent Loss to V to V to V
at In Watts
100% 100% kVA kVA kVA
(1) (2) (3) Voltage Voltage Load Loss %Imp. Load Loss %Imp. Load Loss %Imp.

Total Loss Total Loss Total Loss


Average
Guarantee
TEMPERATURE RISES are in degrees C corrected to instant shutdown.
Serial No _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ with windings connected and loaded as follows:
Multi·winding transformer heat run connections for the determination of the maximum winding rises over ambient may
not be the same as that for the maximum losses which produce the maximum fluid rise. Such temperature rise entries
shall be 011 separate lines in the Temperature Rise table of the Test Report Form. Precautions should be taken to assure
that the fluid temperature rise and winding rises entered on a common line correspond to the same test conditions.
Temp. Fluid R. Above Amb. Winding Differential Above Average Fluid
Rise
Ave.
Energized Winding Shorted Winding Rise by Res. •c
Cool Guar. Losses Top
Mode ·c Dissipated ·c ·c Tap-kV Amps Tap-kV Amps (1) (2) (3)

••',

DIELECTRIC TESTS-If Impulse Tests are requ~red, see separate Transformer Impulse Test Report.
Voltage Rating of Test Voltage Duration of Test
Winding Tested Applied in Seconds
APPLIED POTENTIAL TESTS
Voltage applied between each winding and all
other windlngs connected to core and ground.

hertz times rated voltage across full winding


INDUCED POTENTIAL
TESTS for cycles kV from kV line terminal to ground

REMARKS:

1 hereby certify this is a true report based on factory tests made in accordance with the Transformer Test Code C57.12.90
current edition of the American National Standards Institute, and that each Transformer withstood the above insulation tests.

Signed---------------------- Date---------------------- Approved by--------,_.,--------


Transformer Engineering Dept.
Authorized Engineering Information 11·20·1980.

COPYRIGHT 2003; National Electrical Manufacturers Association Document provided by IHS Licensee=Aramco HQ/99807551 00, User=, 06/11/2003
01:58:16 MOT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
STD.NEMA TR 1-ENGL 1993 .. 6470247 0524481 119 ..
TA 1-1993
Page 21

7.03 TRANSFORMER IMPULSE TEST REPORT


To facilitate safe and effective operation of transformers it is recommended that the following infoonaaion be included
in the test report:
M1nutacturer's N a m e - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
Purchaser ________________________________________________

Date of Test - - - - - - - - - - - - - Purchaser's Order No. Mtr.' s References - - - - - - - - - -


Type Phase - - - - - - Cycles - - - - - - - - Insulating Fluid
H-winding - - - - - - - - - V o l t s X-winding------- Volts V-winding - - - - - - - Volts

s..rv.
Applied Mlcro.IICond Microsecond
on
Serial T-nal kV kV to to
No. Oaclllograms Test• Ne. Required Applied Crest Flashower

"AFW-Recluced Full Wave •cw-Chopped Wave "FW.f=ull Wave

REMARKS:

Signed - - -- - - - - - -- - - - Dat•- - - - - - -- Approved------~---....,.


Transformer Engineering Dept.

P•e•---------- of ----------Pages

COPYRIGHT 2003; N ational Electrical Manufacturers Association Document provided by IHS Ucensee=Aramco HQ/9980755100, U ser=, 06/11/2003
01 :58:16 MOT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451- 1584.
STD.NEMA TR 1-ENGL 1993 . . 6470247 0524482 055 . .
TR 1-1993
Page 22

7.04 REACTOR TEST REPORT


To facilitate safe and effective operation of transformers it is recommended that the following information be included
in the test repon:

Manufacturer's N a m e - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
Purchaser ______________________________________________________________

Date of T e s t s - - - - - - - - - - Purchaser's Order No. - - - - - - - - - Mfr.'s Ref. No. - - - - - - - - -


T y p e - - - - - - - - - Phase - - - - - - - C y c l e s - - - - - - - - Insulating Fluid - - - - - - - -
Volts D r o p - - - - - - - - - - - - - - kVA - - - - - - - - - - Amperes - - - - - - - - - - - -
For connection in Volt Circuit
RESISTANCES, LOSSES AND IMPEDANCE are based on normal rating, unless otherwise stated. Losses are based on
wattmeter measurements.

Resistance at 85 •c Total Loss Impedance


Serial No.
Watts ss·c
Phase A Phase B Phase C Volts %

Average
Guarantee
TEMPERATURE RISE in degrees C corrected to instant of shutdown.

Serial No. Amperes Rise by Resistance Guarantee

INSULATION TESTS-h1gh-potent1at tests were made on each reactor. Voltage was applied between wmdmg and ground
and between phases of a polyphase reactor. Voltage at high frequency was induced in each winding to test the turn-to-
turn strength.

Voltage Rating of Applied Voltage at Induced Voltage at


Winding Normal Frequency High Frequency

REMARKS:

Signed Date----- Approved - - - - - - - - - - - - - - -

COPYRIGHT 2003; National Electrical Manufacturers Association Document provided by IHS Licensee=Aramco HQ/99807551 00, User=, 06/11/2003
01:58:16 MOT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
STD·NEMA TR 1-ENGL 1993 . . 6470247 0524483 T91 . .
TR 1-1993
Page23

PartS
TRANSMISSION AND DISTRIBUTION VOLTAGE REGULATORS

The ANSI/IEEE Standard C57.15-1992, has been ap- The ANSI/IEEE Stanard C57.95-1992. Appendix to
proved as NEMA Standards for transmission and distri- C57.15, has been approved as NEMA Standard for
bution voltage regulators and should be inserted in this Transmission and distribution voltage regulators and
PanS. should be inserted in this Part 8.

COPYRIGHT 2003; National Electrical Manufacturers Association Document provided by IHS Licensee=Aramco HQ/99807551 00, User=, 06/11/2003
01:58:16 MOT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
STD.NEMA TR 1-ENGL 1993 11 6470247 0524484 928 11
TA 1-1993
Page25

Part 9
CURRENT-LIMITING REACTORS

(To Be Published]

COPYRIGHT 2003; National Electrical Manufacturers Association


Previous page ~~:~~~~n~~~~~~~~~~rL~~:~:~7:~~:~~~;v!::::;:1 ~1~a~::,i ,~:~~~!!nt
Policy Management Group at 1-800-451- 1584.
STD.NEMA TR 1-ENGL 1993 11 6470247 0524485 864 11
TA 1-1993
Page27

Part 10
ARC FURNACE TRANSFORMERS

The following olher parts of !his NEMA Publicalion No. TR 1 shall also apply for arc furnace transformers:
a. Part 0 General
b. Part 6 Terminology
c. Part 7 Test Code

Previous pa ~~:~~~~n~~~~~~s~;~~~L!~:~:~~:~~:~t~i~:;~~:~;: ~,a~=~=~~ t~~~~~~~!nt


COPYRIGHT 2003; National Electrical Manufacturers Association 1

Policy Management Group at 1-800-451-1584.


STD.NEMA TR 1-ENGL 1993 11 6470247 0524486 7TO 11
TR 1-1993
Page29

Part 11
SHUNT REACTORS
The American National Standard, CS1 .21-1991, has been approved by NEMA and should be inserted in this Pan 11.

COPYRIGHT 2003; National Electrical Manufacturers Association


Previous pag ~~:~~~~n~~~~~~s~;~~~L!~:~:~~:~~~~~t~i~:;~~:~;: ~,a~=~=~~ t~~~~~~~!nt
1

Policy Management Group at 1-800-451-1584.