Professional Documents
Culture Documents
Abstract Toumi
Abstract Toumi
Abstract Keywords
In this paper, we will develop an improvement in Perturb & Observe (PO). Wind Energy Conversion
the P&O optimization algorithm where will System (WECS) . Maximum Power Point Tracking
consider different step sizes according to the (MPPT) . Permanent Magnet Synchronous
power-speed curve. For that, we will subdivide the Generator (PMSG) - Robust Variable Step Perturb
power-speed curve into several sectors, where the & Observe (RVS_PO) . SOSMC.
corresponding step size will be predefined. VS-PO
algorithms showed their effectiveness in accessing 1. Introduction
MPPT, in a suitable environment for the selected
Traditional energy sources, such as fossil fuels,
system. Despite this improvement, the previous
techniques suffered from many problems, On the occupied a high percentage of more than 75% of
one hand, No directives about step size selection. In the global energy for electricity production MAD,
the event of important continuous variation of the
as they are considered the most sources of
wind speed, either in increasing or decreasing,
direct power variation calculation from power environmental pollution and global warming due to
measurement may provide inexact values which the gases resulting from them. To reduce its effects
induce divergence from the maximum power point.
PRO-VAR, the world has turned to exploiting
In this work, we suggest the new strategy of alternative resources in what is known as renewable
systematic step size selection on the basis of power energy as a vital solution. Wind energy is the
and speed measurements normalization as a
source that contains the largest potential energy and
solution, an intelligent and robust P&O (RVS-PO)
algorithm is tested for variable-speed wind energy the fastest growing, reaching an average of 20%
conversion systems (WECSs). In addition, The annually in the energy sector. Wind energy is clean
proposed RVS-PO algorithm reduces the oscillation
and sustainable.
around the area of the maximum power point by
using through correction of power variation
Nowadays, studies on increasing the power of wind
calculus. The proposed RVS-PO algorithm
enhanced the MPPT with more robustness against turbines installed in the world are accelerating more
high and long wind speed variation. In this study, and more every year. And the development of a
we will consider a wind-turbine system composed
system for converting kinetic energy into electrical
of the following parts : a three-blade wind turbine, a
Permanent Magnet Synchronous Generator energy. The includes pneumatic parts, mechanical
(PMSG) with a required power of 10 kW, a three systems, electrical installations, and control
phase controlled rectifier, DC link capacitor, three
techniques for energy systems [2]. In the global
phase controlled inverter, and an electrical grid. The
simulation results show the high level of the market, we find two different types of wind
improvement in eliminating distortions resulting turbines that we distinguish according to the nature
from wind speed changes, as well as showing its of speed, fixed-speed turbines characterized by ease
superiority over the traditional algorithm.
of operation, variable-speed turbines improve the disturbance by adopting fixed The P&O algorithms
capture and control of power points on a large mainly depend on fixed step size or variable step
scale. size. Conventional (CPO) algorithms apply Small
or large fixed step sizes. Adopting fixed steps in the
Variable speed wind turbine systems (VSWT's)
speed adjustment: the control response makes it
have been in receipt of extensive attention among
possible to reach the point of maximum power but
the various renewable energy systems. Many
with relatively slow non-optimal dynamics in the
references have studied variable speed wind energy
event of a small step. Otherwise, applying a large
conversion systems (VSWT)Rw42. Generators are
step size has a high oscillation around the
used as an essential part in the work of energy
maximum power point (MPP) which reduces the
systems mpo5, , the most important of which are
system efficiency.
the double-feed induction generator (DFIG) and the
permanent magnet synchronous generator (PMSG). The P&O algorithms mainly depend on fixed step
The direct drive generators (PMSG) have high size or variable step size. Conventional (CPO)
efficiency and reliability, which makes them of algorithms apply Small or large fixed step sizes
interest and preferred over (DFIG) mpo2. when using the small step size increases the output
power losses. Otherwise, applying a large step size
In the aim to produce maximum power of wind
has a high oscillation around the maximum power
source, several techniques were established under
point (MPP) which reduces the system efficiency.
the denomination MPPT or maximum power point
tracking techniques. In the research filed, we find As a result, (E, A) work is moving towards the
several algorithms of MPPT which are employed to adoption of variable steps to reduce the CPO
maximize the production of the provided power drawbacks and ameliorate its efficiency. The results
under varying wind speed conditions WECSs at any show a marked improvement in the response in
given instant. For each wind speed, the system must terms of damping quality (F) speed. (B.E) The
find the maximum power, which is equivalent to controller reaches the point of maximum power and
finding the optimum speed of rotation. In the maintains its position with a rapid response. So that
literature, most of the MPPT algorithms and the authors classify them into two categories. First
designs were classified as illustrated in table 1 the modified P&O (MPO) algorithms to improve
Among the method used in MPPT, we find the the speed tracking response, large oscillations less,
disturbance and observation (PO) technique which and slow tracking speed(C). Second, Adaptive P&O
is based on the application of variation of algorithms (AD-PO) are used to reduce the inertia
disturbance on the speed setpoint followed by influence in addition to eradicating solve the loss-
observing its influence on the observed power. tracking problem for power. (F)
Among the method used in MPPT, we find the This article proposes a robust variable-step P&O
disturbance and observation (PO) technique is (RVS-PO) MPPT algorithm. A technique that
based on the application of variation a variation of lessens drawbacks of conventional P&O MPPT
disturbance on the speed setpoint followed by techniques such as slow speed tracking response
observing its influence on the observed power. and inertia influence. It also improves and
Several works by researchers such as (N,S) have addresses two problems.
focused on the quantification of observation and
The regulator requires the readjustment of the PSF Power Signal Feedback
ORB
increments of the setpoint steps according to the LS-PO Large Step P&O
MPO Modified P&O
power and the rotation speed. Indeed, with high-
VS-PO Variable Step P&O
speed machines, the increment step must also be AD-PO Adaptive Step P&O
RVS-PO Robust Variable Step P&O
increased in order to always keep or optimal (fast H-MPPT Hybrid MPPT
response). Otherwise, it is necessary to reduce it to
obtain damped dynamics (not oscillatory)
2. Mathematical Model of WECS
Nomenclature
WECS Wind Energy Conversion System
PMSG Permanent Magnet Synchronous Generators
MSC Machine Side Converter
BTBC Back-To-Back Converters
FSWT Fixed Speed Wind Turbine
VSWT Variable Speed Wind Turbine
DFIG Doubly Fed Induction Generator
FOC Field-Oriented Control
MPPT Maximum Power Point Tracking
SOSMC Second Order Sliding Mode Control
SVPWM Space Vector Pulse Width Modulation
DPC Direct Power Control
IPC Indirect Power Control
TSR Tip speed ratio
OT Optimal Torque
The mechanical power Pt of the wind is expressed
1 nc
Pt = ρ . S . v 3 (1) C p ( λ , β )=∑ ai λi (3)
2
i=0
The actual mechanical power Pω captures by the wi
In this work we have applied a sinusoidal form of
nd blade is expressed by the following expression
Cp :
MPO1:
−C 7
1 C
Pω= ρ . S C p ( λ , β ) . v 3 (2)
2 (
C p ( λ , β )=C 1 2 −C 3 β−C 4 β C −C 6 e
λi
5
) λi
(4 )
To easily the process of controlling the dynamic 3. Control of the Machine Side Converter
performance of the electric generator, the equations
The generator side converter control ensures turbine
based on the stator voltage V d , V q in the Park speed control while providing a maximum power.
As illustrated in figure 2, two controllers are
transform are described as follows Rw42:
needed:
the reference frame in radians/second (rad/s) and R s Fig.2. Machine Side Converter Control Strategy.
is the resistances of the stator winding.The describe
3.1. MPPT control
of the electromagnetic torque can by: Meghni Art
21 Although the speed of the wind turbine can be
fixed or variable, maximization of the energy
3 extracted is achievable with only variable speed
T e = p [ ( Ld−Lq ) I d I q + I d ψ f ] (9)
2
wind turbines. The figure 3 depicts the curve of
mechanical turbine power versus the mechanical
Where p is the number of poles.
speed for various wind speed rates. It show that a
It is noticeable that for low speed surface mounted maximum power retrieving can be performed
PMSG, d- and q-axes inductances are the same i.e.
0.6
Ld ≈ Lq ref-15 λopt,Cpmax,β=0
Betz limit
0.5
following expression:
0.2
dω
Jt + f φ=T −T (10)
0.1
dt m e 0
0 2 4 6 8 10 12 14 16 18
Tip Speed Ration λ
through continuous speed adjustment each time The second order sliding mode controllers contain
the wind speed varies. two parts:
t
(17)
{
proposed to achieve the speed control of PMSG for N1>
Lg
each wind speed in order to maximize the extracted ( 18 )
μi ( k i + μi )
power at the turbine output. In this algorithm, the N2≥
chattering phenomenon can be limited so as to L g2 ( k i−μi )
improve the PMSG performance when compared to
the classical FOSMC and conventional PI control
Where, I sqeq μ i, k i, Lg
Let us introduce the following sliding surface for the
4. MPPT algorithm
speedΩ .
Different available MPPT algorithms are
sΩ =Ωt ref −Ω t (11)
t
described for extracting maximum power which is
Then we have: classified according to the power measurement
i.e. direct, indirect power controller, or hybrid
1
ṡΩ =Ω̇ tref −Ω̇ t =Ω̇ tref − ( T t +T e −F Ω t ) (12) MPPT. Proprieties and comparisons of MPPT
t
J
algorithms are also highlighted on the one hand
If we define the functions G Ωt as follows: wind speed requirements, complexity, speed
The control algorithm proposed which is based on given function. This technique does not need the
super twisting algorithm (ST) has been introduced requirement of sensors and specifications of the
by Levant [47]. system; therefore they are more reliable and reduce
the cost [ REF].
It is implemented through successive adjustment of new characteristic curve is that corresponding to V 2
the reference speed (ω ) and the recording of the ∆ P13 <0then the P&O algorithm
. In this situation
power variation sign ( ∆ P). If ∆ P> 0, we should decrease the speed reference to move the
continue in the same action (speed increment by¿) P4 .But again the wind speed
state point towards
if not we reverse the action. As shown in fig. 4.
decreases at V 3, so the real state point will be at P4
. If speed continues in decrease, there are stagnation
MPP
(3)
DP23
DP12
(2)
Dw
points.
(1)
M echa nical Power
Dw
Pt-MPP
MPP
M echa nical Po wer
DPt
2
Mechanical Power
Dt
SS 3
V1
1
4 6
LS
V2
Rotor speed 5 7
8 V3
V4
Rotor speed
Fig.4.MPPT Perturb and Observation method
Let us consider the first case where turbine is Fig.5. Wind speed decreasing effect on convergence to
driven by fixed wind speed. . If the initial operating maximum power point.
point is located at point P1, we increment at instant The same situation can be conducted in the case of
k , the reference ω ref ref continuous wind speed rising particularly when the
k by ∆ ωk and we will reach
functioning point is located to the right of the
point P2. Since ∆ P12 >0 then we continue by
maximum power point. The figure 6 illustrates the
incrementing the speed reference again by the same state point trajectory over characteristic curves for
amount ∆ ωref to reach point P3 and so on until we several wind speeds (V 1 <V 2 <V 3 <V 4 ). If speed
reach the peak point of maximum power.
reference is increased when starting at P1, the
Now, we examine the second case of wind speed succession of points will be in order P1, P3 and P3
decreasing from V 1 to V 4 while P&O algorithm . So, in this particular case, the P&O algorithm
control the turbine speed. The characteristic curves produce very slow convergent process.
are illustrated in figure 5. If initially the functioning
V4
V3 4
V2
2
V1 5
1 3
Rotor speed
Fig .6. Illustrates the power versus rotor speed curves Also, we will introduce correction on the variation
when the wind speed varies augmented. power calculus through cancelation of wind
disturbance effect.
Table 2 : Effect Of wind speed variation on P&O under the wind speed v k. The maximum
algorithm convergence rate
mechanical power Pmax
k is given by :
MPP( Wopt,Pmax)
∆ P k+1=Pk +1 ( ω k+1 , v k +1 )−Pk ( ω k , v k ) (24)
1
α3 α3
Sector
α3
The development in first order of equation (24)
L=3 α3
α3 α3 gives:
Sector α2 α2 α1>α2>α3
∂f
L=2
α2 α2
∆ P k+1 ≃ f ( ωk +1 , v k ) +
∂v |
( ωk+ 1 ,v k )
∆ v k+1−f ( ω k , v k ) (25)
Sector
L=1 The second term in previous equation represents the
α1 α1
wind speed variation perturbation. Indeed, when the
1 WN=W/Wopt wind speed is constant this term goes to zero. So,
the corrected power variation ∆ Pωk+1without wind
Fig.7. RVS-P&O MPPT controller operation disturbance is computed as follows:
∂f 1
∆ Pωk+1=∆ P k+1−
∂v | (ωk+ 1 , vk )
∆ v k +1( 26) Pω= ρs v 3 C p ( λ ) because β=0
2
𝜔𝑟𝑒𝑓 = 𝜔 + ∆𝜔 𝐾
increment step of the reference speed according
𝜔𝑟𝑒𝑓 = 𝜔 − ∆𝜔 𝐾
to the wind speed for example:
t
∂P
∆ ωnew =∆ ω+∫ ( ¿) ∗γdZ ¿
0 ∂v P
Fig.8.a.General flowchart of the RVS-PO MPPT k
Technique.
With:
γ :Gain de normalization
Fig.8.b.Detailed flowchart of the RVS-PO MPPT
technique.
Start
Measure
w(k), Pw(k),V(k)
Wref=w(k1)
Calculate
Popt(k)
DPw=Pw(k+1)-Pw(k)
DPnew-w=DPw-(dPw/dV)*DV
Yes DPnew-w>0 NO
W(k+1)=W(k)-DW2 W(k+1)=W(k)-DW2
NO αL>S YES
YES αL>S NO
W(k)=W(k-1)
Pw(k)=Pw(k-1)
Return
speed where these oscillations around the MPP
badly affect the mechanical energy observed and
the vibration of the machine.
Simulation results and discussion
In contrast, RVS-PO has a very fast response of 0
In order to evaluate this work, avoid drawbacks of milliseconds than VS-PO with reduces oscillations,
Conventional P&O algorithms, the proposed RVS- where RVS-PO achieved a settling time without
PO algorithm is investigated for the MPPT control any oscillations. The proposed technique reached
of the wind turbine system, and its proposed control and maintained a maximum value of CP = 0.48
system was implemented in the environment compared to LS-PO, SS-PO, and VS-PO. Also,
“MATLAB/Simulink” with PMSG/WT parameters RVS-PO sustains the optimal value of the tip speed
provided in “Appendix.” Simulation tests were ratio (8.1) faster than the conventional P&O and
conducted under two different profiles of wind (the algorithms with variable-step as illustrate in fig .11
step-change profile of wind speed with average (c).
speed (11.4 m/s) as shown in Fig. 11a, and real
random wind speed in Fig. 11b). The rotor speed tracking of the different examined
P&O algorithms is presented in fig.11.d.The LS-PO
To demonstrate the effectiveness and the reliability has large oscillation during the change of speed, it
of the proposed MPPT algorithm, this simulation is ripple peak = 8.5 rad/sec), decreases the ripple peak
based on an individual comparison of the until a settle after about 1.6 s, as for the LS-PO has
performance of the proposed RVS-PO algorithm small instant not continued oscillations (speed peak
with are compared with the conventional fixed step- ripples = 6 rad/sec.), then stabilizes after 0.57 s.
size P&O, using small and large step-sizes, and the Moreover, the VS-PO have deflection takes 0.38 s,
VS-PO to illustrate the effectiveness of the as for RVS-PO, it has proven its strength in
proposed algorithm, In addition, Optimal Rotational tracking speed without any oscillation and complete
Speed “ORC” and the WECS overall efficiency is stability. The proposed VS-PO capture the
calculated. The results are summarized in Table 3. maximum mechanical power efficiency compared
to studied algorithms as shown in Fig. 11(e).
The parameters of the wind turbine system with a
PMSG, utilized in the simulation, are presented in 12
11.4
9.5
validated using step wind speed change. The most
8
7.5
important criteria for studying the efficiency of the 6.6
4
coefficient and tip speed ratio, 0.48 and 8.1, 0 5 10
Time (s)
15 20 25
Zoom
LS-PO, and the VS-PO, It as such achieved high
0.48
efficiency of 97.91% as depicted in Fig. 12.b.
0.4 0.46
0.44
7
6 Zoom On the other hand, we notice for VS-PO has a
9
4
8.1
medium response and small oscillations, but it fails
2 7 to track when the speed reaches 11.42 m /s that is, it
0
0 2 4 6 8 10
15
12
15.2
14
15.4
16
15.6 15.8
18
16
20
does not have high efficiency during a large change
Time (s)
in speed.
(c)
In contrast, the proposed RVS-PO has a fast
Ref-PO SS-PO LS-PO VS-PO RVS-PO
response and very small oscillations that resisted
60
wind speed fluctuation. As such The RVS-PO
50
reaches the optimal value of the tip speed ratio
Rotor Speed (rad/s)
40
30 55
Zoom
compared to other techniques, which fail to achieve
50
20
40
the optimal tip speed ratio as clarified in Fig.12. c.
10
15 15.2 15.4 15.6 15.8
0
0 2 4 6 8 10 12 14 16 18 20 The effectiveness of rotor speed tracking for the
Time (s)
studied P&O algorithms is shown in Fig. 12.d. The
(d) RVS-PO has the ability to regulate the generator
speed according to wind speed variations with very
6000
Ref-PO SS-PO LS-PO VS-PO RVS-PO
small ripples compared to SS-PO, LS-PO, and LS-
5000 PO.
Mechanical Power (W)
4000
1000
5000
LS-PO, SS-PO, and VS-PO methods shows some
0 3000
15 15.2 15.4 15.6 15.8 16
oscillations which affect the quality of the energy.
-1000
0 2 4 6 8 10 12 14 16 18 20
Time (s)
This can be explained by its inability to follow the
(e) maximum peak. In addition, it can be noted that
smooth power tracking is achieved using the RVS-
Fig. 11.a The wind speed profile step-change in PO technique, as demonstrated in Fig.12.e.
(m/s), b are the power coefficient, c tip speed ratio,
d rotor speed and e mechanical power of MPPT
methods (LS-PO, SS-PO, and VS-PO), 12
11
8
The major drawback of method P&O the 7
0.4
0.2 0.46
0.46
0.44 extracted power and the mechanical efficiency of
0.44 0.42
0.1 0.42
0 0.1 0.2 0.3 5 5.2 5.4 5.6 5.8 each MPPT technique depend on the methodology
0
0 1 2 3 4 5 6 7 8 9 10
Time (s) of research and tracking of this MPP (the time and
(b) the method of resolution).We have represented in
Fig. 13a–e, the ORC for four conventional MPPT
Ref-PO SS-PO LS-PO VS-PO RVS-PO
10
methods (SS-PO, SL-PO, and VS-PO) compared
9
8.1 with the proposed technique (RVS-PO).
Tip Speed Ratio λ
7
6
Zoom Zoom
5
9
8.1
9
8.1
These results are shown when applying a mean
6
0 0.1 0.2 0.3
6
5 5.2 5.4 5.6 5.8
wind pro-file (11.55 m/s). The results show clearly
0 1 2 3 4 5 6 7 8 9 10
Time (s) the efficiency of RVS-PO in ORC smooth tracking
(c) compared with other methods.
30 3000
Zoom
20 40 2000
10 30 1000
(d) (a)
Zoom
4000 4000
ORC
5.4 5.5 5.6 5.7 5.8 5.9
3000 3000
2000 2000
1000 1000
0
0 0 5 10 15 20 25 30 35 40 45 50 55
0 1 2 3 4 5 6 7 8 9 10
Rotor Speed (rad/s)
Time (s)
(e) (b)
Fig. 12.a The wind speed profile random in (m/s), b SS-PO Ref-PO
6000
3000
0
0 5 10 15 20 25 30 35 40 45 50 55
Rotor Speed (rad/s)
In addition, the wind energy system operates
(c)
around the optimum operating point (Optimal
Rotational Speed “ORC”), while maintaining this
Maximum Power Point (MPP) for each variation in
wind speed. Although the different characteristics
6000
VS-PO Ref-PO
Stator resistance R s=0.00829 Ω
5000
Ld =0.174 mH
Mechanical Power (W)
4000
ORC
Stator direct inductance
3000
2000
Stator quadrature Lq=0.174 mH
1000
inductance
0
0 5 10 15 20 25 30
Rotor Speed (rad/s)
35 40 45 50 55 Permanent magnet flux ψ m=0.071 wb
(d)
Number of pole pairs n p =6
Inertia J t =0.089 kg . m2
RVS-PO Ref-PO
6000
5000
Mechanical Power (W)
ORC
4000 Friction f =0.005 N . m
3000
2000
Table 3. Wind turbine parameters
1000
0
0 5 10 15 20 25 30 35 40 45 50 55
Radius of the turbine Rt =2 m
Rotor Speed (rad/s)
Fig. 13 a–e, optimal rotational speed (ORC) for Pitch angle β=0 °
four MPPT methods (SS-PO, SL-PO, VS-PO and
RVS-PO).
Optimal tip speed ratio λ opti=8.1
Appendix A
MPPT algorithms
DPC ORB Does not need any sensor for speed measurements
INC The advantage of this algorithm is that it offers a good yield method
under changing wind speed
P&O CPO It is independent and does not need sensors.
Slow convergence speed which rises the output power losses.
VS-PO It ensures faster speed tracking, and are reduced oscillation around the
MPO maximum point
AD-PO Enhances the WECS efficiency and rapidly tracks the MPP with low
steady-state oscillations
RVS-PO A robust and highly efficient algorithm to maintain the stability of the
system in the event of changes in wind speed.
IA FL It is superior in terms of efficiency and robustness. However, it
requires a great memory, prior knowledge of the results.
NN Robust, effective, and characterized by the ability to approximate
nonlinear systems.
PSO It finds the optimal solution using a population of particles and forces
the system to reach its equilibrium quickly where the turbine inertia
effect is minimized
MVPO It increases the energy production of the wind farm, which reduces the
cost of the system
Hybrid MPPT MPPT methods present disadvantages but the combination of the two
algorithms allows us to obtain hybrid algorithms more efficiently.