Liebert®: Ita2 From 10 To 20 kVA
Liebert®: Ita2 From 10 To 20 kVA
Liebert®: Ita2 From 10 To 20 kVA
ITA2
from 10 to 20 kVA
UPS CATALOGUE
LIEBERT® ITA2 - UPS Systems from 10 to 20 kVA
2
Liebert® ITA2
UPS Systems from 10 to 20 kVA
Scope 4
Relevant Directives and Reference Standards 4
System Description 4
Parallel Mode 5
Common Battery 5
3
LIEBERT® ITA2 - UPS Systems from 10 to 20 kVA
4
4. Parallel Mode 7. Control and Diagnostics 7.2 Monitoring
For higher capacity and/or reliability, the 7.1 Optional Communication Cards 7.2.1 Vertiv Trellis Power Insight
outputs of multiple UPS (of the same The Trellis™ Power Insight Application is
7.1.1 IS-UNITY-DP and
rating) can be set up in parallel with a designed to monitor your Liebert® UPS
IS-UNITY-SNMP
built-in controller ensuring automatic devices and provides real-time trending
Vertiv™ IntelliSlot UNITY-DP card for critical UPS performance including
load sharing. Liebert® ITA2 is able to provides Web access, environmental
connect up to four units in parallel voltage and current utilization.
sensor data, and third-party customer
without the need for an additional Other capabilities include:
protocols for Vertiv UPS.
parallel board, allowing maximum Consolidated view of distributed
reliability and flexibility. At anytime, a The cards manage a wide range of
operating parameters, sending data over UPS equipment
single unit can be upgraded to parallel.
Ethernet networks via secure HTTPS Automated device discovery
The parallel option consists of screened protocol and alarms and notification via Alarm views that are sorted or filtered
data cables connecting one unit to the SNMP traps.
next in a loop ring bus. Summary view of individual devices
Vertiv IntelliSlot UNITY cards allow also with specific device metrics
The loop ring bus will allow the parallel monitoring and control of Vertiv UPS
configuration to correctly share the Access to individual device Web
through Vertiv SiteScan® Web or any Interface
system load even in the case of an existing Building Management System.
interruption in the data cable.
Vertiv Intellislot UNITY-DP card delivers 7.2.2 Vertiv Nform Centralized
5. Common Battery also MODBUS and BACNET protocol via Monitoring Software
the EIA-485 or Ethernet port. Vertiv Nform will monitor the UPS via
When UPS are connected in parallel, Vertiv IntelliSlot UNITY cards provide: SNMP protocol. Authenticated alarm
each UPS can use the same battery, management, trend analysis and event
Compatibility with Vertiv shutdown
achieving cost and space savings. It notification delivers a comprehensive
software
should be noted that in a parallel monitoring solution. Available in a variety
redundant system using common A dedicated web page for monitoring
of versions to suit anything from small
battery mode, the batteries are not the UPS
computer rooms to multiple location
redundant and the availability is Interface with Vertiv Nform™ alarm distributed IT networks, Vertiv Nform
consequently reduced. Common battery notification software enables:
banks cannot be used in the Dual Bus Ease of integration with industry yyCondition based system state
mode. standard open protocol recording
Interface with Vertiv SiteScan Web yyAlarm event exporting to disk
6. Dual Bus Mode software
yySMTP email
A dual bus system is a high reliability Proactive analysis of parametric data
yyExecution of external program
architecture consisting of two to ensure facility uptime.
independent UPS systems. Each system yyShut down clients.
includes one UPS, which feeds two 7.1.2 IS-RELAY
7.2.3 Vertiv Sitescan Web
independent load buses, while a built-in Vertiv IntelliSlot IS-RELAY card provides Enterprise Monitoring System
controller ensures the two buses are contact closures for remote monitoring
of alarm conditions of Vertiv UPS. Vertiv Sitescan Web allows users to
synchronized.
monitor and control virtually any piece of
The dual bus system is suitable for loads Through a set of FORM C relay outputs critical facility support equipment -
with multiple power inputs. For single the card notifies the following status: whether it is located in the next room, or in
input loads, an STS (Static Transfer yyOn battery a facility on the other side of the globe.
Switch) can be installed to power the yyLow battery The web based system provides
load.
yyOn bypass centralized supervision of Vertiv precision
yySummary alarm cooling, UPS and distribution units as well
as any other analog or digital third party
yyOn UPS.
devices through a network of
microprocessor based control modules.
Features include real-time enhanced trend
reporting and event management.
5
LIEBERT® ITA2 - UPS Systems from 10 to 20 kVA
7.3 Vertiv Trellis™ Platform 7.4 Vertiv™ LIFE™ Services yyROUTINE: settable at intervals of
Liebert® ITA2 can be integrated in In order to increase the overall between five minutes and two days
(typically once a day)
Vertiv’s Trellis platform. A real-time availability of the system, Liebert ITA2
infrastructure optimization platform that will be compatible with an optional Vertiv yyEMERGENCY: when a problem
enables the unified management of data LIFE Services communication kit, occurs or parameters are beyond
centre IT and facilities infrastructure. providing connection to the Vertiv LIFE tolerance limits
The Vertiv Trellis platform software can Services diagnostic service center. yyMANUAL: following a request from
manage capacity, track inventory, plan the command center.
Vertiv LIFE Services will allow the remote
changes, visualize configurations, diagnosis of the UPS through a TCP/IP During the call the command center will:
analyze and calculate energy usage, and connection (Internet connection), yyIdentify the UPS connected
optimize cooling and power equipment telephone lines or GSM link in order to yyRequest the data stored in the UPS
as well as enable for virtualization. ensure maximum availability of the UPS memory since the last connection
The Vertiv Trellis platform monitors the throughout its operational life. The yyRequest real-time information from
data center, providing a thorough monitoring will be a real 24-hour, 365 the UPS (selectable).
understanding of system dependencies day service as a result of a unique The service center will analyze historical
to help IT and facilities organizations feature that allows trained Customer data and issue a regular detailed report
keep the data center running at peak Engineers to remain in constant to the customer containing information
performance. This unified and complete electronic contact with the service of the UPS operational condition and
solution, delivers the power to see the center, and therefore the UPS. The UPS any critical states.
real situation in your data center, make will automatically dial up the service
the right decision and take action with center at defined intervals to provide The Vertiv LIFE Services center allows
confidence. detailed information that will LIFE SMS delivery system option, where
be analyzed in order to predict short- the customer may receive SMS
term problems. notification which will be activated in the
event of one of the following:
The communication of UPS data to the
Vertiv LIFE Services command center yyMains power failure
will be transmitted in the following yyMains power recovery
conditions: yyBypass line failure
yyLoad supplied by reserve.
nit
e nt U
M an agem
Th e rm a l
al D ata n
N o rm
ctio
Co le
l
Serve
rs ER
EC ENT
n it
U PS U
cal E RVI C
C ri t i S
™ 24/7
LIFE
e r
gine
Y m e r E n s it
ILIT
o
C u s t - s ite V i
AC On
RF
YOU
6
8. Technical Data 10 to 20 kVA
NOMINAL POWER (KVA) 10 15 20
8.1 EUROPEAN AND INTERNATIONAL STANDARDS
General and safety - EN/IEC/AS 62040-1
requirements for UPS
EMC requirements for UPS - EN/IEC/AS 62040-2
UPS classification according - VFI-SS-111
to CEI EN 62040-3
8.2 ENVIRONMENTAL CHARACTERISTICS
Noise within 1 m
(in the front) (dBA) ≤56 ≤56 ≤58
according to ISO7779
Altitude (m) ≤3000 above sea level derate power by 1% per each 100m increase
Relative humidity (%RH) 0 to 95, non condensing
Operating temperature (°C) 0 to 40 without de-rating and 40 to 50 with derating.
Storage and transport (°C) -40 to 70
temperature for UPS
Recommended battery (°C) -20 to 30
storage temperature
Over-voltage level - Degree 2
EMC class - C3
Pollution level - Degree 2
8.3 MECHANICAL CHARACTERISTICS
Dimensions 430 x 500 x 130 (UPS)
(W × D × H) 430 x 500 x 130 (matching battery module option, 16 x 9 Ah each)
(mm)
430 x 500 x 175 (single power distribution (POD) option)
430 x 500 x 260 (1+1 parallel power distribution (POD) option)
Net / Shipping Weight 23/40 (UPS)
51/70 (matching battery module option, 16 x 9 Ah each)
(kg)
18/35 (single power distribution (POD) option)
30/47 (1+1 parallel power distribution (POD) option)
Colour - Black RAL7021
Protection degree, - IP20
IEC (60529)
8.4 RECTIFIER AC INPUT (MAINS)
Nominal input voltage(1) (V) 380 / 400 / 415 (three-phase and sharing neutral with the bypass input)
Earthing distribution systems TN, TT and IT(7)
compatibility
Input voltage range at 100%
nominal output power (V) 305 to 498
without battery discharge
Input voltage range at
derated load conditions (V) 173(2) to 498
without battery discharged
Nominal frequency (Hz) 50 or 60
Input frequency range(3) (Hz) 40 to 70
Input power factor full load (kW/kVA) 0.98 0.99 0.99
Input power factor half load (kW/kVA) 0.97 0.98 0.98
7
LIEBERT® ITA2 - UPS Systems from 10 to 20 kVA
8
NOMINAL POWER 10 15 20
8.7 INVERTER AC OUTPUT
Nominal output voltage(1) (V) 380/400/415 (three-phase) or 220/230/240 (single-phase)
Total harmonic voltage
distortion with 100% linear (%) 2
load (THDv)
Total harmonic voltage dis-
tortion with reference to non (%) 5
linear load (THDv)
Steady state voltage stability
100% balanced load (%) ±1
100% unbalanced load (%) ±3
Transient voltage stability
Input variation
(Main/Battery/Bypass) (%) ±6
0-100% linear load step (%) ±6
0-100% non linear load step (%) ±7
Transient recovery time (ms) 60
Nominal output frequency(2) (Hz) 50/60
Frequency stability
Synchronized with
internal clock (%) ±0.25
Synchronized with
bypass ±0.25
Frequency slew rate
(Max change rate of synch (Hz/s) Setting range: 0.2 to 0.5
frequency)
Frequency synchronization (%) Nominal ± 5
window(3)
Maximum phase error for (deg) 3
synchronization with bypass
Phase angle displacement
accuracy
100% balanced load
(100, 100, 100) (deg) ±1.0
100% unbalanced load
(0, 0, 100) (deg) ±1.0
Nominal apparent power (kVA) 10 15 20
Nominal active power (kW) 10 15 20
Range of load power factor 0.5 lagging to 0.5 leading (4)
Nominal output current @ (A) 14.4 21.7 28.9
400 V three phase output
Nominal output current @ (A) 43.3 65.0 86.6
400 V single phase output
Automatic active power
adjustment with temperature
@ 30°C 10 15 20
@ 35°C (kVA/kW) 10 15 20
@ 40°C 10 15 20
@ 45°C 9 13.5 18
@ 50°C 8 12 16
Overload 105% (min) 60
125% (min) 5
150% (min) 1
>150% (ms) <200
Three phase short circuit (A rms) 64
current in battery mode
Phase to neutral short circuit (A rms) 64
current in battery mode
Short circuit current duration (ms) 120
before inverter shut down
Non-linear load capability(5) (%) 100
Load crest factor handled - 3:1
without derating
Permissible load unbalance (%) 100
1. Factory set to 400 V. 380 V or 415 V selectable by commissioning engineer.
2. Factory set to 50 Hz. 60 Hz selectable by commissioning engineer. Note that the system frequency can be changed only when the UPS is on bypass. It is strictly prohibited to change the system frequency when
the UPS is on inverter.
3. If bypass frequency is outside this window the inverter cannot be synchronized.
4. From 0.5 to 0.9 leading de-rating is applied.
5. IEC 62040-3, annex E (crest factor 3:1).
9
LIEBERT® ITA2 - UPS Systems from 10 to 20 kVA
10
Customer Experience Center
Vertiv™ state-of-the-art Customer Testing includes individual modules, as Our Customer Experience Center offers
Experience Center located in well as complete power systems, with three validation experiences:
Castel Guelfo (Bologna - Italy), the added possibility of the customer’s yyDemo - carried out on new products
enables our customers to switchgear support systems being to demonstrate UPS performance
experience first-hand a wide connected, thus guaranteeing smooth,
variety of data center yyStandard - validation test showing
rapid installation and commissioning of UPS standard technical
technologies, supported by
constant consultation from R&D large power systems. performances in compliance with
and engineering specialists. Testing is also customized based on the UPS catalogue and IEC 62040-3
complexity, size and number of UPS standards
Customers visiting the center will be components in the configuration. yyCustomized - session tailored to
able to witness pre-installation validating customer’s specific
demonstrations, covering the technical technical performance needs.
performance, interoperability and
efficiency of Vertiv UPS systems under
real field conditions.
These processes can be experienced
from the facility’s control room, where
real-time performance measurements
and reporting will be available while
providing full visibility of the
demonstration area.
The center can host simultaneous tests
at full load of up to 4000 A.
The customer validation area specifically
dedicated to UPS consists of four
testing stations, each one providing up
to 1.2 MVA of capacity.
11
VertivCo.com | Vertiv Infrastructure Limited, George Curl Way, Southampton, SO18 2RY, VAT Number: GB188146827
© 2017 Vertiv Co. All rights reserved. Vertiv™, the Vertiv logo, Liebert® ITA2, Vertiv Multilink, Vertiv Trellis™, Vertiv Nform™, Vertiv SiteScan®, Vertiv IntelliSlot® and Vertiv LIFE™ Services are trademarks or registered trademarks of Vertiv Co. All other names and
logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. Assumes no responsibility, and disclaims all liability, for damages
resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.
MKA4CAT0UKITA2 Rev.1-02-2018