K-Electric Limited
Employer’s Engineer:
Contractor’s Engineer:
DESIGN STAGE
Originator Doc No. F08643S-D0907
DETAIL DESIGN
The drawing / document has been checked to ensure compliance with the
Contract. The approval status shall be interpreted as laid down in the Contract and shall
not relieve the Contractor form his contractual obligations.
Cat. 1 [ ] APPROVED
Cat. 2 [ ] APPROVED EXCEPT AS NOTED
Cat. 3 [ ] NOT APPROVED
Cat. 4 [ ] FOR INFORMATION ONLY
DATE:
SIGNATURES:
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
7 CB Q01 OPEN COMMAND COMMON X311:1 101 220kV UNIT1 GIS LOCAL CONTROL CABINET
00ADQ245103 TRANSF. BCU (BQPS I Unit 1 STEP-UP F08463S-D0901 0
8 ADQ24-O-001 CB Q01 OPEN COMMAND DO X311:2 143 PANEL(PHASE I) TRANSFORMER)
9 SPARE DO X311:3
10 SPARE DO X311:4
11 CB Q01 CLOSE COMMAND COMMON X311:5 141 220kV UNIT1 GIS LOCAL CONTROL CABINET
F08463S-D0901
00ADQ24730 TRANSF. BCU (BQPS I Unit 1 STEP-UP F08463S-D0909 0
12 ADQ24-O-002 CB Q01 CLOSE COMMAND DO X311:6 145 PANEL(PHASE I) TRANSFORMER)
13 SPARE DO X311:7
14 SPARE DO X311:8
Page 1 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
33 COMMON1 X311:29
34 SPARE1 DO X311:30
35 COMMON2 X311:31
36 SPARE2 DO X311:32
37 COMMON3 X311:33
38 SPARE3 DO X311:34
39 COMMON4 X311:35
40 SPARE4 DO X311:36
41 COMMON5 X311:37
42 SPARE5 DO X311:38
43 COMMON6 X311:39
44 SPARE6 DO X311:40
48 CB TRIP COIL 1 SUPERVISION RELAY X331:16~18 139C 00ADQ245102 220kV UNIT1 GIS LOCAL CONTROL CABINET F08463S-D0901 0
TRANSF. BCU (BQPS I Unit 1 STEP-UP
49 CB TRIP COIL 1 SUPERVISION RELAY X331:20 135A PANEL(PHASE I) TRANSFORMER)
Page 2 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
52 X331:19 connect to
X331:9
53 X331:21 connect to
X331:13
54 X331:23 connect to
X331:17
62 X332:19 connect to
X332:9
63 X332:21 connect to
X332:13
64 X332:23 connect to
X332:17
68 SPARE DI X341:3
69 SPARE DI X341:4
70 SPARE DI X341:5
71 SPARE DI X341:6
74 ADQ24-I-105 DS Q21 OPENING POSITION DI X341:9 N06 220kV UNIT1 GIS LOCAL CONTROL CABINET
00ADQ245106 TRANSF. BCU (BQPS I Unit 1 STEP-UP F08463S-D0901 0
Page 3 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
00ADQ245106 TRANSF. BCU (BQPS I Unit 1 STEP-UP F08463S-D0901 0
75 ADQ24-I-106 DS Q21 CLOSED POSITION DI X341:10 N05 PANEL(PHASE I) TRANSFORMER)
89 ADQ24-I-118 DS ES ON REMOTE OPERATING POSITION DI X341:22 N24 220kV UNIT1 GIS LOCAL CONTROL CABINET
00ADQ245119 TRANSF. BCU (BQPS I Unit 1 STEP-UP F08463S-D0901 0
INTERLOCK SWITCH ON UNLOCK
90 ADQ24-I-119
POSITION
DI X341:23 N25 PANEL(PHASE I) TRANSFORMER)
ALARM/INDICATION POWER MCB
91 ADQ24-I-120 DI X341:24 N26
TRIPPED
LCP/MECHANISM LIGHTING/HEATING
97 ADQ24-I-125 DI X341:29 N30
POWER MCB TRIPPED
Page 4 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
PANEL(PHASE I) TRANSFORMER)
100 ADQ24-I-128 Q01 CONTROL CIRCUIT 1 MCB TRIPPED DI X341:32 N33
116 ADQ24-I-142 G10 GAS ROOM SF6 PRESSURE LOW DI X341:46 N230
117 ADQ24-I-143 G11 GAS ROOM SF6 PRESSURE LOW DI X341:47 N231
118 ADQ24-I-144 G12 GAS ROOM SF6 PRESSURE LOW DI X341:48 N232
Page 5 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
144 ADQ24-A-201 CURRENT INPUT (PHASE A) ACI 0-1A 0-700A X601:1 A4071
145 ADQ24-A-202 CURRENT INPUT (PHASE B) ACI 0-1A 0-700A X601:2 B4071
Page 6 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
00ADQ24726 TRANSF. BCU F08463S-D0909-13 0
METERING PANEL
150 CURRENT OUTPUT (PHASE B) ACI X601:6 PH S PANEL(PHASE I)
152 ADQ24-V-201 VOLTAGE INPUT (PHASE A) ACI 0-57.7V (0-264/√3)kV X701:1,2 A624
153 ADQ24-V-202 VOLTAGE INPUT (PHASE B) ACI 0-57.7V (0-264/√3)kV X701:3,4 B624 220kV UNIT1 GIS LOCAL CONTROL CABINET
00ADQ245122 TRANSF. BCU (BQPS I Unit 1 STEP-UP F08463S-D0901 0
154 ADQ24-V-203 VOLTAGE INPUT (PHASE C) ACI 0-57.7V (0-264/√3)kV X701:5,6 C624 PANEL(PHASE I) TRANSFORMER)
162 X901:3 PE
165 X901:6 PE
168 X901:9 PE
171 X901:12 PE
174 X901:15 PE
Page 7 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
175
176
177
178
179
186 CB Q01 OPEN COMMAND COMMON X311:1 101 220kV UNIT2 GIS LOCAL CONTROL CABINET
00ADQ225103 TRANSF. BCU (BQPS I Unit 2 STEP-UP F08463S-D0902 0
187 ADQ22-O-001 CB Q01 OPEN COMMAND DO X311:2 143 PANEL(PHASE I) TRANSFORMER)
190 CB Q01 CLOSE COMMAND COMMON X311:5 141 220kV UNIT2 GIS LOCAL CONTROL CABINET
F08463S-D0902
00ADQ22730 TRANSF. BCU (BQPS I Unit 2 STEP-UP F08463S-D0911 0
191 ADQ22-O-002 CB Q01 CLOSE COMMAND DO X311:6 145 PANEL(PHASE I) TRANSFORMER)
Page 8 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
PANEL(PHASE I) TRANSFORMER)
199 ADQ22-O-006 DS Q21 CLOSE COMMAND DO X311:16 G203
Page 9 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
Page 10 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
253 ADQ22-I-105 DS Q21 OPENING POSITION DI X341:9 N06 220kV UNIT2 GIS LOCAL CONTROL CABINET
00ADQ225106 TRANSF. BCU (BQPS I Unit 2 STEP-UP F08463S-D0902 0
254 ADQ22-I-106 DS Q21 CLOSED POSITION DI X341:10 N05 PANEL(PHASE I) TRANSFORMER)
265 ADQ22-I-115 Q01(A) GAS ROOM SF6 PRESSURE LOW DI X341:19 N21a
266 ADQ22-I-116 Q01(B) GAS ROOM SF6 PRESSURE LOW DI X341:20 N21b
268 ADQ22-I-118 DS ES ON REMOTE OPERATING POSITION DI X341:22 N24 220kV UNIT2 GIS LOCAL CONTROL CABINET
00ADQ225119 TRANSF. BCU (BQPS I Unit 2 STEP-UP F08463S-D0902 0
INTERLOCK SWITCH ON UNLOCK
269 ADQ22-I-119
POSITION
DI X341:23 N25 PANEL(PHASE I) TRANSFORMER)
ALARM/INDICATION POWER MCB
270 ADQ22-I-120 DI X341:24 N26
TRIPPED
273 ADQ22-I-123 Q01(C) GAS ROOM SF6 PRESSURE LOW DI X341:27 N21c
Page 11 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
LCP/MECHANISM LIGHTING/HEATING
276 ADQ22-I-125 DI X341:29 N30
POWER MCB TRIPPED
277 ADQ22-I-126 Q01 GAS ROOM SF6 PRESSURE LOCKOUT DI X341:30 N31
220kV UNIT2 GIS LOCAL CONTROL CABINET
278 ADQ22-I-127 Q01 MOTOR OVERRUN/OVERLOAD DI X341:31 N32 00ADQ225120 TRANSF. BCU (BQPS I Unit 2 STEP-UP F08463S-D0902 0
PANEL(PHASE I) TRANSFORMER)
279 ADQ22-I-128 Q01 CONTROL CIRCUIT 1 MCB TRIPPED DI X341:32 N33
295 ADQ22-I-142 G10 GAS ROOM SF6 PRESSURE LOW DI X341:46 N230
296 ADQ22-I-143 G11 GAS ROOM SF6 PRESSURE LOW DI X341:47 N231
297 ADQ22-I-144 G12 GAS ROOM SF6 PRESSURE LOW DI X341:48 N232
Page 12 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
323 ADQ22-A-201 CURRENT INPUT (PHASE A) ACI 0-1A 0-700A X601:1 A4071
Page 13 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
324 ADQ22-A-202 CURRENT INPUT (PHASE B) ACI 0-1A 0-700A X601:2 B4071 220kV UNIT2 GIS LOCAL CONTROL CABINET
00ADQ225115 TRANSF. BCU (BQPS I Unit 2 STEP-UP F08463S-D0902 0
325 ADQ22-A-203 CURRENT INPUT (PHASE C) ACI 0-1A 0-700A X601:3 C4071 PANEL(PHASE I) TRANSFORMER)
331 ADQ22-V-201 VOLTAGE INPUT (PHASE A) ACI 0-57.7V (0-264/√3)kV X701:1,2 A624
332 ADQ22-V-202 VOLTAGE INPUT (PHASE B) ACI 0-57.7V (0-264/√3)kV X701:3,4 B624 220kV UNIT2 GIS LOCAL CONTROL CABINET
00ADQ225122 TRANSF. BCU (BQPS I Unit 2 STEP-UP F08463S-D0902 0
333 ADQ22-V-203 VOLTAGE INPUT (PHASE C) ACI 0-57.7V (0-264/√3)kV X701:5,6 C624 PANEL(PHASE I) TRANSFORMER)
341 X901:3 PE
344 X901:6 PE
347 X901:9 PE
Page 14 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
AO 4-20mA 00ADQ22725 TRANSF. BCU F08463S-D0911-13 0
control cubicle (ASB03)
349 REACTIVE POWER OUTPUT (-) X901:11 F18 PANEL(PHASE I)
350 X901:12 PE
353 X901:15 PE
354
355
356
357
364 CB Q01 OPEN COMMAND COMMON X311:1 101 220kV UNIT5 GIS LOCAL CONTROL CABINET
00ADQ215103 TRANSF. BCU (BQPS I Unit 5 STEP-UP F08463S-D0903 0
365 ADQ21-O-001 CB Q01 OPEN COMMAND DO X311:2 143 PANEL(PHASE I) TRANSFORMER)
368 CB Q01 CLOSE COMMAND COMMON X311:5 141 220kV UNIT5 GIS LOCAL CONTROL CABINET
F08463S-D0903
00ADQ21736 TRANSF. BCU (BQPS I Unit 5 STEP-UP F08463S-D0913 0
369 ADQ21-O-002 CB Q01 CLOSE COMMAND DO X311:6 145 PANEL(PHASE I) TRANSFORMER)
Page 15 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
Page 16 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
405 CB TRIP COIL 1 SUPERVISION RELAY X331:16~18 139C 220kV UNIT5 GIS LOCAL CONTROL CABINET F08463S-D0903 0
00ADQ215102
TRANSF. BCU (BQPS I Unit 5 STEP-UP
406 CB TRIP COIL 1 SUPERVISION RELAY X331:20 135A PANEL(PHASE I) TRANSFORMER)
Page 17 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
220kV UNIT5 GIS LOCAL CONTROL CABINET
423 ADQ21-I-101 CB Q01 OPENING POSITION DI X341:1 N02 00ADQ215106 TRANSF. BCU (BQPS I Unit 5 STEP-UP F08463S-D0903 0
PANEL(PHASE I) TRANSFORMER)
424 ADQ21-I-102 CB Q01 CLOSED POSITION DI X341:2 N01
431 ADQ21-I-105 DS Q21 OPENING POSITION DI X341:9 N06 220kV UNIT5 GIS LOCAL CONTROL CABINET
00ADQ215106 TRANSF. BCU (BQPS I Unit 5 STEP-UP F08463S-D0903 0
432 ADQ21-I-106 DS Q21 CLOSED POSITION DI X341:10 N05 PANEL(PHASE I) TRANSFORMER)
443 ADQ21-I-115 Q01(A) GAS ROOM SF6 PRESSURE LOW DI X341:19 N21a
444 ADQ21-I-116 Q01(B) GAS ROOM SF6 PRESSURE LOW DI X341:20 N21b
446 ADQ21-I-118 DS ES ON REMOTE OPERATING POSITION DI X341:22 N24 220kV UNIT5 GIS LOCAL CONTROL CABINET
00ADQ215119 TRANSF. BCU (BQPS I Unit 5 STEP-UP F08463S-D0903 0
INTERLOCK SWITCH ON UNLOCK
447 ADQ21-I-119
POSITION
DI X341:23 N25 PANEL(PHASE I) TRANSFORMER)
Page 18 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
ALARM/INDICATION POWER MCB
448 ADQ21-I-120 DI X341:24 N26
TRIPPED
451 ADQ21-I-123 Q01(C) GAS ROOM SF6 PRESSURE LOW DI X341:27 N21c
LCP/MECHANISM LIGHTING/HEATING
454 ADQ21-I-125 DI X341:29 N30
POWER MCB TRIPPED
455 ADQ21-I-126 Q01 GAS ROOM SF6 PRESSURE LOCKOUT DI X341:30 N31
220kV UNIT5 GIS LOCAL CONTROL CABINET
456 ADQ21-I-127 Q01 MOTOR OVERRUN/OVERLOAD DI X341:31 N32 00ADQ215120 TRANSF. BCU (BQPS I Unit 5 STEP-UP F08463S-D0903 0
PANEL(PHASE I) TRANSFORMER)
457 ADQ21-I-128 Q01 CONTROL CIRCUIT 1 MCB TRIPPED DI X341:32 N33
Page 19 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
473 ADQ21-I-142 G10 GAS ROOM SF6 PRESSURE LOW DI X341:46 N230
474 ADQ21-I-143 G11 GAS ROOM SF6 PRESSURE LOW DI X341:47 N231
475 ADQ21-I-144 G12 GAS ROOM SF6 PRESSURE LOW DI X341:48 N232
Page 20 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
220kV UNIT5
DC MCB POWER SUPPLY FAILURE ( 0CWF01GH00650 220kV UNIT6 TRANSF. BCU
498 ALARM X352:4 N92 TRANSF. BCU 0
PHASE I UNIT5 BCU ) 11 PANEL(PHASE I)
PANEL(PHASE I)
A251 6MD85 BCU DEVICE FAULT ( PHASE
499 ALARM X352:5 N93
I UNIT5 BCU )
DC POWER SUPPLY FAILURE ( PHASE I
500 ALARM X352:6 N94
UNIT5 BCU )
0
501 ADQ21-A-201 CURRENT INPUT (PHASE A) ACI 0-1A 0-700A X601:1 A4071
502 ADQ21-A-202 CURRENT INPUT (PHASE B) ACI 0-1A 0-700A X601:2 B4071 220kV UNIT5 GIS LOCAL CONTROL CABINET
00ADQ215115 TRANSF. BCU (BQPS I Unit 5 STEP-UP F08463S-D0903
503 ADQ21-A-203 CURRENT INPUT (PHASE C) ACI 0-1A 0-700A X601:3 C4071 PANEL(PHASE I) TRANSFORMER)
511 ADQ21-V-201 VOLTAGE INPUT (PHASE A) ACI 0-57.7V (0-264/√3)kV X701:1,2 A624
512 ADQ21-V-202 VOLTAGE INPUT (PHASE B) ACI 0-57.7V (0-264/√3)kV X701:3,4 B624 220kV UNIT5 GIS LOCAL CONTROL CABINET
00ADQ215122 TRANSF. BCU (BQPS I Unit 5 STEP-UP F08463S-D0903 0
513 ADQ21-V-203 VOLTAGE INPUT (PHASE C) ACI 0-57.7V (0-264/√3)kV X701:5,6 C624 PANEL(PHASE I) TRANSFORMER)
521 X901:3 PE
Page 21 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
AO 4-20mA 00ADQ21731 TRANSF. BCU F08463S-D0913-15 0
control cubicle (ASB11)
523 VOLTAGE OUTPUT (-) X901:5 F14 PANEL(PHASE I)
524 X901:6 PE
527 X901:9 PE
530 X901:12 PE
533 X901:15 PE
534
535
536
537
544 CB Q01 OPEN COMMAND COMMON X311:1 101 220kV UNIT6 GIS LOCAL CONTROL CABINET
00ADQ255103 TRANSF. BCU (BQPS I Unit 6 STEP-UP F08463S-D0904 0
545 ADQ25-O-001 CB Q01 OPEN COMMAND DO X311:2 143 PANEL(PHASE I) TRANSFORMER)
Page 22 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
548 CB Q01 CLOSE COMMAND COMMON X311:5 141 220kV UNIT6 GIS LOCAL CONTROL CABINET
F08463S-D0904
00ADQ25732 TRANSF. BCU (BQPS I Unit 6 STEP-UP F08463S-D0915 0
549 ADQ25-O-002 CB Q01 CLOSE COMMAND DO X311:6 145 PANEL(PHASE I) TRANSFORMER)
Page 23 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
Page 24 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
611 ADQ25-I-105 DS Q21 OPENING POSITION DI X341:9 N06 220kV UNIT6 GIS LOCAL CONTROL CABINET
00ADQ255106 TRANSF. BCU (BQPS I Unit 6 STEP-UP F08463S-D0904 0
612 ADQ25-I-106 DS Q21 CLOSED POSITION DI X341:10 N05 PANEL(PHASE I) TRANSFORMER)
Page 25 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
623 ADQ25-I-115 Q01(A) GAS ROOM SF6 PRESSURE LOW DI X341:19 N21a
624 ADQ25-I-116 Q01(B) GAS ROOM SF6 PRESSURE LOW DI X341:20 N21b
626 ADQ25-I-118 DS ES ON REMOTE OPERATING POSITION DI X341:22 N24 220kV UNIT6 GIS LOCAL CONTROL CABINET
00ADQ255119 TRANSF. BCU (BQPS I Unit 6 STEP-UP F08463S-D0904 0
INTERLOCK SWITCH ON UNLOCK
627 ADQ25-I-119
POSITION
DI X341:23 N25 PANEL(PHASE I) TRANSFORMER)
ALARM/INDICATION POWER MCB
628 ADQ25-I-120 DI X341:24 N26
TRIPPED
631 ADQ25-I-123 Q01(C) GAS ROOM SF6 PRESSURE LOW DI X341:27 N21c
LCP/MECHANISM LIGHTING/HEATING
634 ADQ25-I-125 DI X341:29 N30
POWER MCB TRIPPED
635 ADQ25-I-126 Q01 GAS ROOM SF6 PRESSURE LOCKOUT DI X341:30 N31
220kV UNIT6 GIS LOCAL CONTROL CABINET
636 ADQ25-I-127 Q01 MOTOR OVERRUN/OVERLOAD DI X341:31 N32 00ADQ255120 TRANSF. BCU (BQPS I Unit 6 STEP-UP F08463S-D0904 0
PANEL(PHASE I) TRANSFORMER)
637 ADQ25-I-128 Q01 CONTROL CIRCUIT 1 MCB TRIPPED DI X341:32 N33
Page 26 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
653 ADQ25-I-142 G10 GAS ROOM SF6 PRESSURE LOW DI X341:46 N230
654 ADQ25-I-143 G11 GAS ROOM SF6 PRESSURE LOW DI X341:47 N231
655 ADQ25-I-144 G12 GAS ROOM SF6 PRESSURE LOW DI X341:48 N232
Page 27 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
A251 6MD85 BCU DEVICE FAULT ( PHASE
672 ADQ25-I-163 DI X341:63 N93
I UNIT5 BCU )
DC POWER SUPPLY FAILURE ( PHASE I
673 ADQ25-I-164 DI X341:64 N94
UNIT5 BCU )
681 ADQ25-A-201 CURRENT INPUT (PHASE A) ACI 0-1A 0-700A X601:1 A4071
682 ADQ25-A-202 CURRENT INPUT (PHASE B) ACI 0-1A 0-700A X601:2 B4071 220kV UNIT6 GIS LOCAL CONTROL CABINET
00ADQ255115 TRANSF. BCU (BQPS I Unit 6 STEP-UP F08463S-D0904 0
683 ADQ25-A-203 CURRENT INPUT (PHASE C) ACI 0-1A 0-700A X601:3 C4071 PANEL(PHASE I) TRANSFORMER)
691 ADQ25-V-201 VOLTAGE INPUT (PHASE A) ACI 0-57.7V (0-264/√3)kV X701:1,2 A624
692 ADQ25-V-202 VOLTAGE INPUT (PHASE B) ACI 0-57.7V (0-264/√3)kV X701:3,4 B624 220kV UNIT6 GIS LOCAL CONTROL CABINET
00ADQ255122 TRANSF. BCU (BQPS I Unit 6 STEP-UP F08463S-D0904 0
693 ADQ25-V-203 VOLTAGE INPUT (PHASE C) ACI 0-57.7V (0-264/√3)kV X701:5,6 C624 PANEL(PHASE I) TRANSFORMER)
696 VOLTAGE INPUT (BUS I) (N) ACI 0-57.7V (0-264/√3)kV X701:29,30 N6302 00ADQ25701 220kV UNIT6 GIS LOCAL CONTROL CABINET F08463S-D0904 0
TRANSF. BCU (BQPS I Unit 6 STEP-UP
Page 28 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
TRANSF. BCU (BQPS I Unit 6 STEP-UP
697 ADQ25-V-221 VOLTAGE INPUT (BUS II) (A) X701:31,32 A671 PANEL(PHASE I) TRANSFORMER)
ACI 0-57.7V (0-264/√3)kV
698 VOLTAGE INPUT (BUS II) (N) X701:33,34 connect to
X701:30
701 X901:3 PE
704 X901:6 PE
707 X901:9 PE
710 X901:12 PE
713 X901:15 PE
714
715
Page 29 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
00BUB01QC212 BCU PANEL(PHASE F08643S-D0602 0
PANEL 3
721 DC POWER 2- X220:4,5 - I)
722 CB Q01 OPEN COMMAND COMMON X311:1 101 220kV ST1 TRANSF. GIS LOCAL CONTROL CABINET
00ADQ235103 BCU PANEL(PHASE (BQPS I STARTUP F08463S-D0905 0
723 ADQ23-O-001 CB Q01 OPEN COMMAND DO X311:2 143 I) TRANSFORMER 1)
connected to
726 CB Q01 CLOSE COMMAND COMMON X311:5 101 220kV ST1 TRANSF. GIS LOCAL CONTROL CABINET X311:1
00ADQ235103 BCU PANEL(PHASE (BQPS I STARTUP F08463S-D0905 0
727 ADQ23-O-002 CB Q01 CLOSE COMMAND DO X311:6 145 I) TRANSFORMER 1)
Page 30 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
763 CB TRIP COIL 1 SUPERVISION RELAY X331:16~18 139C 00ADQ235102 220kV ST1 GIS LOCAL CONTROL CABINET F08463S-D0905 0
TRANSF. BCU (BQPS I STARTUP
764 CB TRIP COIL 1 SUPERVISION RELAY X331:20 135A PANEL(PHASE I) TRANSFORMER 1)
connect to
767 X331:19
X331:9
connect to
768 X331:21
X331:13
connect to
769 X331:23
X331:17
Page 31 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
connect to
777 X332:19
X332:9
connect to
778 X332:21
X332:13
connect to
779 X332:23
X332:17
789 ADQ23-I-105 DS Q21 OPENING POSITION DI X341:9 N06 220kV ST1 GIS LOCAL CONTROL CABINET
00ADQ235106 TRANSF. BCU (BQPS I STARTUP F08463S-D0905 0
790 ADQ23-I-106 DS Q21 CLOSED POSITION DI X341:10 N05 PANEL(PHASE I) TRANSFORMER 1)
Page 32 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
220kV ST1 GIS LOCAL CONTROL CABINET
796 ADQ23-I-111 ES Q52 OPENING POSITION DI X341:15 N12 00ADQ235107 TRANSF. BCU (BQPS I STARTUP F08463S-D0905 0
PANEL(PHASE I) TRANSFORMER 1)
797 ADQ23-I-112 ES Q52 CLOSED POSITION DI X341:16 N11
801 ADQ23-I-115 Q01(A) GAS ROOM SF6 PRESSURE LOW DI X341:19 N21a
802 ADQ23-I-116 Q01(B) GAS ROOM SF6 PRESSURE LOW DI X341:20 N21b
804 ADQ23-I-118 DS ES ON REMOTE OPERATING POSITION DI X341:22 N24 220kV ST1 GIS LOCAL CONTROL CABINET
00ADQ235119 TRANSF. BCU (BQPS I STARTUP F08463S-D0905 0
INTERLOCK SWITCH ON UNLOCK
805 ADQ23-I-119
POSITION
DI X341:23 N25 PANEL(PHASE I) TRANSFORMER 1)
ALARM/INDICATION POWER MCB
806 ADQ23-I-120 DI X341:24 N26
TRIPPED
809 ADQ23-I-123 Q01(C) GAS ROOM SF6 PRESSURE LOW DI X341:27 N21c
LCP/MECHANISM LIGHTING/HEATING
812 ADQ23-I-125 DI X341:29 N30
POWER MCB TRIPPED
813 ADQ23-I-126 Q01 GAS ROOM SF6 PRESSURE LOCKOUT DI X341:30 N31
220kV ST1 GIS LOCAL CONTROL CABINET
814 ADQ23-I-127 Q01 MOTOR OVERRUN/OVERLOAD DI X341:31 N32 00ADQ235120 TRANSF. BCU (BQPS I STARTUP F08463S-D0905 0
PANEL(PHASE I) TRANSFORMER 1)
815 ADQ23-I-128 Q01 CONTROL CIRCUIT 1 MCB TRIPPED DI X341:32 N33
Page 33 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
831 ADQ23-I-142 G10 GAS ROOM SF6 PRESSURE LOW DI X341:46 N230
832 ADQ23-I-143 G11 GAS ROOM SF6 PRESSURE LOW DI X341:47 N231
833 ADQ23-I-144 G12 GAS ROOM SF6 PRESSURE LOW DI X341:48 N232
Page 34 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
861 ADQ23-A-201 CURRENT INPUT (PHASE A) ACI 0-1A 0-125A X601:1 A4021
862 ADQ23-A-202 CURRENT INPUT (PHASE B) ACI 0-1A 0-125A X601:2 B4021 220kV ST1 GIS LOCAL CONTROL CABINET
00ADQ235115 TRANSF. BCU (BQPS I STARTUP F08463S-D0905 0
863 ADQ23-A-203 CURRENT INPUT (PHASE C) ACI 0-1A 0-125A X601:3 C4021 PANEL(PHASE I) TRANSFORMER 1)
869 ADQ23-V-201 VOLTAGE INPUT (PHASE A) ACI 0-57.7V (0-264/√3)kV X701:1,2 A624
Page 35 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
870 ADQ23-V-202 VOLTAGE INPUT (PHASE B) ACI 0-57.7V (0-264/√3)kV X701:3,4 B624 220kV ST1 GIS LOCAL CONTROL CABINET
00ADQ235122 TRANSF. BCU (BQPS I STARTUP F08463S-D0905 0
871 ADQ23-V-203 VOLTAGE INPUT (PHASE C) ACI 0-57.7V (0-264/√3)kV X701:5,6 C624 PANEL(PHASE I) TRANSFORMER 1)
879 X901:3 PE
882 X901:6 PE
885 X901:9 PE
888 X901:12 PE
891 X901:15 PE
892
893
894
Page 36 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
895
902 CB Q01 OPEN COMMAND COMMON X311:1 101 220kV ST3 TRANSF. GIS LOCAL CONTROL CABINET
00ADQ265103 BCU PANEL(PHASE (BQPS I STARTUP F08463S-D0906 0
903 ADQ26-O-001 CB Q01 OPEN COMMAND DO X311:2 143 I) TRANSFORMER 3)
connected to
906 CB Q01 CLOSE COMMAND COMMON X311:5 101 220kV ST3 TRANSF. GIS LOCAL CONTROL CABINET X311:1
00ADQ265103 BCU PANEL(PHASE (BQPS I STARTUP F08463S-D0906 0
907 ADQ26-O-002 CB Q01 CLOSE COMMAND DO X311:6 145 I) TRANSFORMER 3)
Page 37 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
ES Q51 OPEN/CLOSE COMMAND
919 X311:20 G501
COMMON
Page 38 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
PANEL(PHASE I) TRANSFORMER 3)
944 CB TRIP COIL 1 SUPERVISION RELAY X331:20 135A
connect to
947 X331:19
X331:9
connect to
948 X331:21
X331:13
connect to
949 X331:23
X331:17
connect to
957 X332:19
X332:9
connect to
958 X332:21
X332:13
connect to
959 X332:23
X332:17
Page 39 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
969 ADQ26-I-105 DS Q21 OPENING POSITION DI X341:9 N06 220kV ST3 GIS LOCAL CONTROL CABINET
00ADQ265106 TRANSF. BCU (BQPS I STARTUP F08463S-D0906 0
970 ADQ26-I-106 DS Q21 CLOSED POSITION DI X341:10 N05 PANEL(PHASE I) TRANSFORMER 3)
981 ADQ26-I-115 Q01(A) GAS ROOM SF6 PRESSURE LOW DI X341:19 N21a
982 ADQ26-I-116 Q01(B) GAS ROOM SF6 PRESSURE LOW DI X341:20 N21b
984 ADQ26-I-118 DS ES ON REMOTE OPERATING POSITION DI X341:22 N24 220kV ST3 GIS LOCAL CONTROL CABINET
00ADQ265119 TRANSF. BCU (BQPS I STARTUP F08463S-D0906 0
INTERLOCK SWITCH ON UNLOCK
985 ADQ26-I-119
POSITION
DI X341:23 N25 PANEL(PHASE I) TRANSFORMER 3)
ALARM/INDICATION POWER MCB
986 ADQ26-I-120 DI X341:24 N26
TRIPPED
989 ADQ26-I-123 Q01(C) GAS ROOM SF6 PRESSURE LOW DI X341:27 N21c
LCP/MECHANISM LIGHTING/HEATING
992 ADQ26-I-125 DI X341:29 N30
POWER MCB TRIPPED
993 ADQ26-I-126 Q01 GAS ROOM SF6 PRESSURE LOCKOUT DI X341:30 N31
220kV ST3 GIS LOCAL CONTROL CABINET
Page 40 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
220kV ST3 GIS LOCAL CONTROL CABINET
994 ADQ26-I-127 Q01 MOTOR OVERRUN/OVERLOAD DI X341:31 N32 00ADQ265120 TRANSF. BCU (BQPS I STARTUP F08463S-D0906 0
PANEL(PHASE I) TRANSFORMER 3)
995 ADQ26-I-128 Q01 CONTROL CIRCUIT 1 MCB TRIPPED DI X341:32 N33
1011 ADQ26-I-142 G10 GAS ROOM SF6 PRESSURE LOW DI X341:46 N230
1012 ADQ26-I-143 G11 GAS ROOM SF6 PRESSURE LOW DI X341:47 N231
1013 ADQ26-I-144 G12 GAS ROOM SF6 PRESSURE LOW DI X341:48 N232
Page 41 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
1041 ADQ26-A-201 CURRENT INPUT (PHASE A) ACI 0-1A 0-125A X601:1 A4021
1042 ADQ26-A-202 CURRENT INPUT (PHASE B) ACI 0-1A 0-125A X601:2 B4021 220kV ST3 GIS LOCAL CONTROL CABINET
00ADQ265115 TRANSF. BCU (BQPS I STARTUP F08463S-D0906 0
Page 42 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
00ADQ265115 TRANSF. BCU (BQPS I STARTUP F08463S-D0906 0
1043 ADQ26-A-203 CURRENT INPUT (PHASE C) ACI 0-1A 0-125A X601:3 C4021 PANEL(PHASE I) TRANSFORMER 3)
1049 ADQ26-V-201 VOLTAGE INPUT (PHASE A) ACI 0-57.7V (0-264/√3)kV X701:1,2 A624
1050 ADQ26-V-202 VOLTAGE INPUT (PHASE B) ACI 0-57.7V (0-264/√3)kV X701:3,4 B624 220kV ST3 GIS LOCAL CONTROL CABINET
00ADQ265122 TRANSF. BCU (BQPS I STARTUP F08463S-D0906 0
1051 ADQ26-V-203 VOLTAGE INPUT (PHASE C) ACI 0-57.7V (0-264/√3)kV X701:5,6 C624 PANEL(PHASE I) TRANSFORMER 3)
1054 VOLTAGE INPUT (BUS I) (N) ACI 0-57.7V (0-264/√3)kV X701:29,30 N6402 00ADQ26701 220kV ST3 GIS LOCAL CONTROL CABINET F08463S-D0906 0
TRANSF. BCU (BQPS I STARTUP
1055 ADQ26-V-221 VOLTAGE INPUT (BUS II) (A) X701:31,32 A671 PANEL(PHASE I) TRANSFORMER 3)
ACI 0-57.7V (0-264/√3)kV
1056 VOLTAGE INPUT (BUS II) (N) X701:33,34 connect to
X701:30
1059 X901:3 PE
1062 X901:6 PE
1065 X901:9 PE
Page 43 of 44
WIRING TABLE OF NCS PANEL FOR BQPS-I G1,G2,G5,G6,ST1,ST2 F08643S-D0907
起端设备图号
序号 I/O点编号 I/O点名称 I/0类型 信号类型 量程范围 端子号 回路号 电缆编号 终端设备(BCU) 起端设备 版本 备注
Refer to Drawings of
No. ID Coding IO Description IO Type Signal Spec Range Terminal Circuit No. Cable No. Cable Ending (BCU) Cable Beginning Rev. Note
Cable Beginning
1068 X901:12 PE
1071 X901:15 PE
1072
1073
Page 44 of 44