1(3) DATA SHEET

 
I/O M 700 H
Part no. 5100077-01A

System: TERRA FIRE

General Description Certified according to


09
I/O M 700 provides eight programmable I/O 700 2531-CPR-232.1686
channels, used for either: DOP no. 6301900
• Programmable Inputs Protections against overload
• Outputs max* 700 mA for magnets, power Module protection Equipped with a fusible
supply etc cut-out
Use the I/O M 700 as an input module, or use it Adjustable protection, 4 A / system module
to monitor, control, and/or supply units such as max total
alarm devices, magnets. It can also provide Protection on each Normal current 0.7 A
constant power supply to other system modules output For short duration, 2 A
such as Control and Repetar Panels etc. electronic limit, before the
load is disconnected
For details on assembling a system and definitions
of common system terms, refer to the Installation
Manual. Settings
* It is possible to connect up to three outputs in The module is identified by a physical address on
parallel, if the power demand is greater than 700 the Backbone Bus. The address is set with an
mA. 8-pole DIP switch.

Data Address switch


Operating voltage range 19-30 VDC
The DIP switch value follows the binary system.
The address no. can be set from 1 to 126 using
Current consumption 17 mA DIP-switch poles 1 to 7.
(at 24 V)
Max. output current per 700 mA
channel
Max. total current 4.0 A
ELR input/output 30 kΩ (optional)
Cable terminals 2.5 mm2
Operating temperature -5 °C to +55 °C NOTE!
range -5 °C to +55 °C If DIP switch 8 is used output 5-8 will always
Weight (with housing) 130 g be active. In this case output 5-8 must be set
to "not used" in the configuration program to
Spare part no. 5100076-03A
(without housing) avoid a configuration fault in the system.
Certified according to
2531/yy
yy = year of production

The specifications described herein are subject to change without notice. Data sheet no. 5100077-01A_I-O M 700 H_I0_EN_2019_L

www.consiliumbuildingsafety.com
DATA SHEET 2(3)

Connections

Indicators

Indicator Colour, pattern Module status when Module status when


used as an output used as an input
Green The output is ON The input is activated
Channels 1 – 8 Yellow Output fault Input fault
None The output is OFF The input is not activated

The specifications described herein are subject to change without notice. Data sheet no. 5100077-01A_I-O M 700 H_I0_EN_2019_L

www.consiliumbuildingsafety.com
3(3) DATA SHEET

Indicator Colour, pattern Module status


Green Power OK
PS (Power Supply)
Yellow Power Fault
Green Communication OK
Green, flashing Communication OK, module not
COM (Communication)
configured
Yellow Communication fault
PS + COM PS = Yellow, flashing Boot-loader mode
COM = Green
PS + COM PS = Yellow, flashing Boot-loader mode, Firmware download in
(both flashing) COM = Yellow, flashing progress
PS = Yellow, flashing Safe State (module is not functional)
PS + COM
COM = None

Module Dimensions (mm)

Mounting
Mount the module on a horizontal 35 mm DIN rail.