Transformer Performance Data: EE112T2305H
Transformer Performance Data: EE112T2305H
Date: 31 Mar 14
Core Loss (No Load): 453 watts Insulation System Class: 220 ºC
Coil Loss (Load): 2123 watts Average Temperature Rise: 150 ºC
Total Losses: 2576 watts Hotspot Temperature Rise: 170 ºC
Efficiency: 1/4 Load 1/2 Load 3/4 Load Full Load 35% Load @ 75ºC
96.88% 97.38% 97.07% 96.57% 97.714%
Listed E6868