Point of ● Run CPU ● DI120-150

TCD - 159 SD3(U) OVER SPEED Application


Detection ○ Speed CPU ● DI180-420

[Meaning] Detecting over-speed at SD3U switch position. [Actions to take]

1. Check SD1U wiring connection(inferior) and input buffer status(Refer to TCD


119-SDS error).
1) Verify if voltage changes from 48V to 0V at emergence of SD1U.
2) Check the address value from NVRAM READ MODE of Ann. (It is normal if 0xFF
becomes x00 at the operation of IS_SD1U(ADDR:0x500F))
[Diagram]
*Current_Encoder_Value / PULSE_PER_METER cur_p
2508H / PULSE_PER_METER
2 . Check the positions of SD1U~7U (Refer to below SPEC DATA) - DI2~D 4 are same
JJH_Velocity cur_v Referring to below SDS SPEC DATA(EEPROM area), check actual fitting location
of SD1U~7U.

0
err_Detect

UP_RUN ADDRESS SDS OFFSET DATA


Floor_Height_Table[*Total_Fml_Int_No] start_enco
0x1130 Equivalent_Spec.Sds1_Offset 400
558DH cur_p - (start_enco/PULSE_PER_METER) delta_p
0x1132 Equivalent_Spec.Sds2_Offset 1400
Equ_Sds_Tot_No & SDS1
0x1134 Equivalent_Spec.Sds3_Offset 2800
check_on_history(XSD1U) = TRUE
0x1136 Equivalent_Spec.Sds4_Offset 5600

SDS1_V <= cur_v BIT OR(SD1U) 0x1138 Equivalent_Spec.Sds5_Offset 7600


err_Detect
0x113A Equivalent_Spec.Sds6_Offset 14000

0x113C Equivalent_Spec.Sds7_Offset 27000


(delta_p >= MAX_SDS1_ON_DIST *1.5)
BIT OR(SD1U)
err_Detect
ADDRESS SDS BOUND DATA

0x1150 Equivalent_Spec.Sds1_Bound 50
err_Detect & SD1U
TCD 157 0x1152 Equivalent_Spec.Sds2_Bound 50

0x1154 Equivalent_Spec.Sds3_Bound 50

0x1156 Equivalent_Spec.Sds4_Bound 50

0x1158 Equivalent_Spec.Sds5_Bound 50

※ Comparing E/L speed and speed check data(each reducing speed 0x115A Equivalent_Spec.Sds6_Bound 100
uniformly) after SD1U~7U operation, if E/L speed excesses speed
0x115C Equivalent_Spec.Sds7_Bound 400
check data error is detected.