Project Summary Report - Earthing Transformer
Project Summary Report - Earthing Transformer
Project Description:
Installed Plant/Equipment
Plant Identifier Manufacturer Serial Number Voltage Comments Year
Test Verifications
Earthing Insulation Winding
Transf. Resist- Resist- Z0 Imped- SAT SIT Commissioning
Identifier ance ance ance Ratio Checklist Checklist sign off
Insulation
Insulation Resistance Resistance
Test Report - Earthing Test Report
Transformer - Earthing Transformer
Customer: Substation: Transformer Identifier:
Plant Details
Manufacturer: Serial No:
Model: Insulation:
Voltage: kV Z0 Impedance: Ω
Signature Block:
Tested By: Name: Date:
Checked By: Name: Date:
Insulation
Insulation Resistance
Resistance Test Test Report
Report - Earthing/Local - Earthing/Local
Supply Transf. Supply Transf.
Customer: Substation: Transformer Identifier:
Plant Details
Manufacturer: Serial No:
Model: Insulation:
Pri Voltage: kV Z0 Impedance: Ω
Sec Voltage: V Rating: kVA
Insulation Resistance: (all values in MΩ) ###
Instrument Used: Serial Number: Temperature: °C###
Earthing Transformer Rated Voltage: kV ###
Insulation Resistance Test Voltage = kV (For HV windings only) ###
###
###
Test @1 min @5 min @10 min PI ###
HV - LV+E MΩ MΩ MΩ ###
HV - E MΩ MΩ MΩ PI will only be assessed if IR assessment
level = C3
LV - E @
1kV MΩ MΩ MΩ
Comments
Signature Block:
Tested By: Name: Date:
Checked By: Name: Date:
Winding
Winding Resistance
Resistance and Z0
and Z0 Impedance TestImpedance Test
Report - Earthing Report - Earthing
Transf. Transf.
Customer: Substation: Transformer Identifier:
Plant Details
Manufacturer: Serial No:
Model: Insulation:
Voltage: kV Z0 Impedance: Ω
Winding Resistance:
Instrument Used: Serial Number: Temperature: °C
Winding Material:
Corrected to 75ᵒC
Connection A-n B-n C-n A-n B-n C-n C-n
Test Test Test
Resistance mΩ mΩ mΩ Temp? mΩ Temp? mΩ Temp? mΩ mΩ
Zero Sequence Impedance:
Instrument Used: Serial Number:
Signature Block:
Tested By: Name: Date:
Checked By: Name: Date:
Winding
Winding Resistance
Resistance & Z0 Impedance
& Z0 Impedance Test ReportTest Report - Earthing/Local
- Earthing/Local SupplyTransf. SupplyTransf.
Customer: Substation: Transformer Identifier:
Plant Details
Manufacturer: Serial No:
Model: Insulation:
Pri Voltage: kV Z0 Impedance: Ω
Sec Voltage: V Rating: kVA
Winding Resistance:
Instrument Used: Serial Number: Temperature: °C
Winding Material: Winding M
ZigZag Winding ZigZag W
Measured Resistance Corrected to 75ᵒC
A-n B-n C-n A-n B-n C-n
Winding Test Test Test
Resistance mΩ mΩ mΩ Temp? mΩ Temp? mΩ Temp? mΩ
Zero Sequence Impedance:
Instrument Used: Serial Number:
Zigzag winding only
Test Configuration Applied Voltage Measured Current R X Z
3 Phase to Earth V ᵒ A ᵒ #DIV/0! Ω #DIV/0! Ω #DIV/0! Ω
A Phase to Earth V ᵒ A ᵒ #DIV/0! Ω #DIV/0! Ω #DIV/0! Ω
B Phase to Earth V ᵒ A ᵒ #DIV/0! Ω #DIV/0! Ω #DIV/0! Ω
C Phase to Earth V ᵒ A ᵒ #DIV/0! Ω #DIV/0! Ω #DIV/0! Ω
Comments
Signature Block:
Tested By: Name: Date:
Checked By: Name: Date:
Ratio
Ratio Test Report Test Report
- Earthing/Local - Earthing/Local
Supply Transformer Supply Transformer
Customer: Substation: Transformer Identifier:
Plant Details
Manufacturer: Serial No:
Model: Insulation:
Pri Voltage: kV Z0 Impedance: Ω
Sec Voltage: V Rating: kVA
Ratio: Ratio:
Instrument Used: Serial Number: Vector Group: Vector Gr
Upper HV Voltage limit expected: V Lower HV Voltage limit expected: V
A-Phase B-Phase C-Phase
Name
Tap plate HV Secondary Volts (V) Measured Secondary Volts (V) Measured Secondary Volts (V)
Pos winding Measured
Voltage Ratio Ratio Ratio
Upper Lower Upper Lower Upper Lower
1
2
3
4
5
6
7
8
Tap position selected for Service: Select Tap that provides voltage level between 226-254V
allowing for Voltage drop of connected circuits.
Comments
Signature Block:
Tested By: Name: Date:
Checked By: Name: Date:
Site Acceptance
Site Acceptance Testing
Testing Check Sheet Check
- Earthing Sheet -
Transformer Earthing Transformer
Customer: Substation: Transformer Identifier:
Plant Details
Manufacturer: Serial No:
Model: Insulation:
Voltage: kV Z0 Impedance: Ω
Site Testing
Site Integration Integration Testing
Check Sheet Check
- Earthing Sheet
Transformer - Earthing Transformer
Customer: Substation: Transformer Identifier:
Plant Details
Manufacturer: Serial No:
Model: Insulation:
Voltage: kV Z0 Impedance: Ω
Site Integration
Site Integration Testing
Testing Check SheetCheck Sheet - Earthing/Local
- Earthing/Local Supply Transformer
Supply Transformer
Customer: Substation: Transformer Identifier:
Plant Details
Manufacturer: Serial No:
Model: Insulation:
Pri Voltage: kV Z0 Impedance: Ω
Sec Voltage: V Rating: kVA
Site Integration Check List:
No. Check Item / test Comments Tested/Checked by Test Date
Confirm earthing transformer has been
1 included in transformer primary injection.