TECHNICAL CATALOGUE
AIR HANDLING UNITS
CONTENTS
UNIT SECTIONS
06.01-10 12
Schemes, overall and joined dimensions, weight
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development. www.tangra.bg
www.tangra.bg We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.
AIR HANDLING UNITS AHU–H / AHU-DD 06.01-01
Air handling units are modular built for indoor or outdoor installation. Intended to be build in general ventilation and air-
conditioning systems. Universal application: office buildings, stores, hotels and restaurants, swimming pools, industrial
buildings, etc. Depending of the air flow, they could be separated in nine standard sizes from 6000 m³/h to 45000 m³/h.
Model
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development. www.tangra.bg
3
06.01-02
AHU–H / AHU-DD AIR HANDLING UNITS
Construction
Supporting frame made of special aluminium profiles, Insulation panels made of extruded polystyrene XPS type
connected with aluminium corners. Construction sides with density 32 kg/m³, thermal conductivity λ=0.039 W/m K
are closed with thermo and acoustic insulated panels. In and combustibility class M1.
thus structure (UU universal section) are incorporated all Upon request panels could be made of compressed mineral
necessary elements for air treatment. wool with density 60-100 kg/m³, thermal conductivity
λ=0.037 W/m K and combustibility class M0.
The panels are fixed with self-tapping screws or metric bolts.
Side panels Sides which should be opened for inspection and
Panels made of galvanized sheet steel with powder coating maintenance are performed as doors, equipped with
at their external side (RAL7035) and heat and acoustic knuckles and special locks. Revision covers could be fixed to
insulated middle layer. the supporting frame with reamers – upon request.
Visual inspection is made through manhole incorporated in
Two versions of side panels are possible: the panel.
• Standard thickness of 25mm for model sizes from AHU 06 Sealing of the panels to the constructions is ensured by
to AHU 20 strips of self-adhesive cellular rubber.
• Standard thickness of 50mm for model sizes from AHU 24
to AHU 45H
• On request - for outdoor installation with thickness 50mm
(AHU06 – AHU20)
• ВU - Fan section
The section consists of centrifugal fan with forward or backward curved impeller. The type of fan is selected depending to the
specific requirements, according to the air flow and resistance of the installation:
• BDB - Belt-driven double inlet centrifugal fan with backward curved impeller, standard version (section 03.07)
• CBP - Belt-driven double inlet centrifugal fan with forward curved impeller (section 03.08) only for models AHU 06,
AHU 09, AHU 12
• BPF - Direct-driven single inlet centrifugal fan with backward curved impeller.
The impellers made by “Soler&Palau” are statically and dynamically balanced.
Mounted to the frame on anti-vibration mounts, equipped with flexible connection. This avoids the transmission of vibration
to the casing.
Fans are driven by electrical motor, using belt drive or directly incorporated to the fan. The belts which are used are type B or
SPB. Belt pulleys are with fixing bush (hub). For easier belt tension motors are installed on a slider.
All motors are three phase 400V/50Hz, protection class IP54, class F insulation and working mode S1 (continuous). Ambient
temperature: - 30°C ÷ +40°C.
Maximum working temperature +60°C and maximum altitude 1000m.
www.tangra.bg We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.
4
AIR HANDLING UNITS AHU–H / AHU-DD 06.01-03
• ТU - Thermal section
Include heating and/or cooling section (heat exchanger), drop separator and drain tray.
Types of sections (heat exchanger) that could be incorporated (section 02.05):
• Two-rows (2R) – basically used in heating mode.
• Four-rows (4R) – basically used in cooling mode.
• Six-rows (6R) and eight-rows (8R) could be produced upon request.
Heat exchangers “Water-air” (heating and cooling) are tubular-plate type, made of copper pipes with strung on them aluminium
fins with step 2.3mm. Good contact between pipes and fins is achieved by mechanical distension. Incorporated in the section
by guides (rails), ensuring the sealing by air.
Drop eliminator is a cassette of profiled blades, designed to retain the condensation after the cooling section. Made of special
polymer profiles. Drain tray with ½’’ connection, is mounted at the bottom of the cooling section.
Siphon must be ensured. He should be placed before condensation line is connected to the building installation.
Air filter section contains one or two consequently mounted air filters with different efficiency from lower to higher class from
G2 to F9, according BDS EN 779 (section 02.03).
For rough dust several air filter cassettes type AFC-V (class G3) or AFC-Z (class G4) are mounted together. The cassettes slide
into the section through glides (rails) and are fixed with profiles and bolt connection.
For fine purification filter wall made of several bad filters type AFC-B (class F6 – F8). The cassettes are fixed to the filter wall
through reamers.
Air filter cassettes are disposable, they are consumables for the air handling units.
In more specific the section could be completed with other type air filters: reusable metal filters, carbon or absolute filters,
class H10 – H13.
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development. www.tangra.bg
5
06.01-04
AHU–H / AHU-DD AIR HANDLING UNITS
Heat exchanger section RU-REC is equipped with by-pass damper type PRJ (section 02.09) at the fresh air stream and
drain tray at the exhaustion side. By-pass damper is used for defrosting of recuperator in winter and gave the possibility for
working in “free cooling” mode during transitional seasons. The heat exchanger transfer heat only, from the warm to the cold
air stream. Suitable for dehumidification of swimming pool installations.
Section RU-ROT is provided with rotary aluminium recuparator with motor and control panel. The recuperator transfer
heat and moisture between both streams. Suitable for air-conditioning installations at premises without large separation of
moisture.
Efficiency of heat exchangers depends on their type and specific parameters of the air. Calculated to each individual case.
REC-AL ROT
www.tangra.bg We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.
6
AIR HANDLING UNITS AHU–H / AHU-DD 06.01-05
Build in universal section baffles, placed parallel of the air stream. Baffles made of plates of fiber-glass, wrapped in glass
material to prevent atomization, protected by a safety metal grid and frame of galvanized steel sheet.
Standard version:
• SA 10/10 – baffles with thickness D=100 mm and distance between baffles S=100 mm – effective from 500 to 4000 Hz
(middle range frequency). Section length L=1000mm
On customers request:
• SA 10/6 – baffles with thickness D=100 mm and distance between baffles S=60 mm – effective in high range frequency.
• SA 20/12 – baffles with thickness D=200 mm and distance between baffles S=120 mm – effective in low range frequency.
• Different length of section and baffles: L=500, 1000, 1500 and 2000mm.
Sound attenuating section could be replaced by duct mounted sound attenuator type DSA (section 02.01).
Sections similar to those described above, equipped with one or more control valves (PJR) with build-in single-stage filter for
inlet section or EK-N duct type electric heater.
• Supporting frame
Made of aluminium corners and profiles of galvanized sheet steel with high 100mm. Mounted under each section of one-
storeyed units. In double deck version for top row section supporting frame is not provided. To ease the transportation and
installation in the supporting frame are provided openings for lift up with mechanization.
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development. www.tangra.bg
7
06.01-06
AHU–H / AHU-DD AIR HANDLING UNITS
Principle scheme
1. ВU - Fan section
2. ТU - Thermal section
3. AFU - Air filter section with two-stage cleaning
4. СМU - Mixing section
Note:
• Special sizes and combinations – on an individual project.
• Size L1 depends on type and position of fan.
• Size L2 is related to thermal section, consisting of COT+COX+ drop eliminator.
• Size L3 is related to air filter section with two stages filter G3 and F8
• For more information, please, see the corresponding sections in our catalogue.
www.tangra.bg We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.
8
AIR HANDLING UNITS AHU–H / AHU-DD 06.01-07
1. ВU - Fan section
2. TU - Thermal section with build in AFC air filter
3. InU - Inlet section with AFC-V air filter
4. CMU - Mixing section
5. UU - Universal section
6. SAU - Sound attenuating section
7. ExhU - Outlet unit with duct-type electric heater EK-N.
8. BU - Fan section – independent box
9. NJZ - External grille
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development. www.tangra.bg
9
06.01-08
AHU–H / AHU-DD AIR HANDLING UNITS
Principles schemes
1. BU - Fan section
2. TU - Thermal section
3. InU - Inlet section with AFC-V air
filter
4. RU-REC - Recuperative section with
plate heat exchanger
5. RU-ROT - Recuperative section with
rotary regenerative heat exchanger
6. InU - Inlet section with two stages of
cleaning
www.tangra.bg We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.
10
AIR HANDLING UNITS AHU–H / AHU-DD 06.01-09
1. U – Fan section
B
2. TU - Thermal section
3. InU - Inlet section with AFC-V air filter
4. RU-REC - Recuperative section with plate
heat exchanger
5. RU-ROT - Recuperative section with rotary
regenerative heat exchanger
6. SAU - Sound attenuating section
7. ExhU - Outlet unit with bag filter AFC-B
8. UU - Universal section
9. ExhU - Outlet unit with duct-type electric
heater EK-N
10. NJZ - External grille
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development. www.tangra.bg
11
06.01-10
AHU–H / AHU-DD AIR HANDLING UNITS
Unit sections
BU - Fan section
Possible schemes
www.tangra.bg We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.
12
AIR HANDLING UNITS AHU–H / AHU-DD 06.01-11
Unit sections
BU - Fan section
Note:
• Dimensions c/d of the inlet / outlet flange (PJR) are valid for all fan sections
• TM – total weight of fan section BU ** / 11(12) - R(L)
• Nominal power of three phase motor Nel.
• Aerodynamic and acoustic characteristics, see sections from 06.01–18 up to 06.01-25
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development. www.tangra.bg
13
06.01-12
AHU–H / AHU-DD AIR HANDLING UNITS
Unit sections
TU - Thermal section
Note:
• R(L) - Air direction from the supply side of water coil unit
• Weight of a single heat exchanger 2R or 4R
• TM – total weight of TU ** / 2R / 4R / K - R(L)
• Technical characteristics, see p.06.01-16
www.tangra.bg We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.
14
AIR HANDLING UNITS AHU–H / AHU-DD 06.01-13
Unit sections
Note:
• PJR - multiple leaf damper and electric motor (actuator) in section 02.09
• H1 – in double deck version AHU-DD, see p. 06.01 - 08
• TМ – tentative weight of sections with length L=1000mm
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development. www.tangra.bg
15
06.01-14
AHU–H / AHU-DD AIR HANDLING UNITS
Unit sections
Note:
Air stream direction from the inspection side:
fresh air:
• R – from left to right
• L – from right to left
exhausted air:
• R1 – from left to right
• L1 – from right to left
RU-REC RU-ROТ
Air flow V B Hdd
Model L4.2 h A0 MT L4.3 NEL. MT
[m³/h] [mm] [mm] REC AL ROT
[mm] [mm] [m2] [kg] [mm] [W] [kg]
RU-** 06 6000 1350 2000 2200 1200/9 840 0.83 446 600 1250 90 212
RU-** 09 9000 1600 2000 2000 1200/9 1080 1.04 512 600 1500 90 281
RU-** 12 12000 1850 2100 2000 1200/9 1280 1.24 569 600 1750 180 341
RU-** 16 16000 2100 2300 2000 1200/9 1580 1.55 644 600 2000 180 412
RU-** 20 20000 2360 2500 2000 1200/9 1920 1.86 744 600 2250 180 556
RU-REC 24 24000 2360 2850 2850 1800/9 1920 2.79 1359 - - - -
RU-ROT 24 24000 2600 2850 - - - - - 1200 2500 180 776
Note:
• Heat exchanger must be protected with air filters at both streams
• RU-REC 06 with incorporated air filter AFC-Z
• Inlet section of plate heat exchanger – А0 (m²)
• Drive motor of the rotary regenerative heat exchanger is single-phase with nominal power Nel.
• MT - weight of the recuperative section
• Efficiency of the recuperators, see p. 06.01-17
www.tangra.bg We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.
16
AIR HANDLING UNITS AHU–H / AHU-DD 06.01-15
Unit sections
UU - Universal section
UU ** / HxL - R(L)
Inlet section with air filter AFC-V G3 (G4) and one or two
dampers (PJR)
• InU *** / 1(2) / F+(F) / HxL - R(L)
Overall and joined dimensions, weight
B H H1 L5 L6 L7.1 L7.2 MT
Model
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [kg]
SAU 06 InU/ ExhU 06 1350 950 1050 600÷2000 500÷2000 600 800 217
SAU 09 InU/ ExhU 09 1600 1050 950 600÷2000 500÷2000 600 800 278
SAU 12 InU/ ExhU 12 1850 1150 950 600÷2000 500÷2000 600 800 327
SAU 16 InU/ ExhU 16 2100 1250 1050 600÷2000 500÷2000 600 1000 379
SAU 20 InU/ ExhU 20 2360 1350 1250 600÷2000 500÷2000 600 1000 435
SAU 24 InU/ ExhU 24 2360 1500 1350 600÷2000 600÷2000 800 1000 518
SAU 30 InU/ ExhU 30 2360 1700 - 600÷2000 600÷2000 800 1200 547
SAU 36 InU/ ExhU 36 2360 1900 - 600÷2000 600÷2000 800 1200 592
SAU 45 InU/ ExhU 45 2360 2300 - 600÷2000 600÷2000 800 1200 682
Note:
• For double deck version AHU-DD height of the section is H or H1
• MT - weight of the sound attenuating section SAU ** -10/10 - BxHxL=1000mm
• Dimensions of flange and dampers (PJR) have to be indicated in the order
• For weight of universal, inlet or outlet sections, please use approximate weight per meter (see р. 06.01-13)
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development. www.tangra.bg
17
06.01-16
AHU–H / AHU-DD AIR HANDLING UNITS
For some specific cases with different inlet parameters, please, contact us.
www.tangra.bg We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.
18
AIR HANDLING UNITS AHU–H / AHU-DD 06.01-17
RU-REC
Model
RU-ROT
Model
Note :
• E [%] - efficiency of fresh air
• For more specific cases and accurate determination of all parameters, please, contact us or use online software REC 01 on
our website.
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development. www.tangra.bg
19
06.01-18
AHU–H / AHU-DD AIR HANDLING UNITS
www.tangra.bg We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.
20
AIR HANDLING UNITS AHU–H / AHU-DD 06.01-19
BDB 710
Note :
• For determination of sound level pressure on frequency
bands - page 06.01-24
• For determination of the necessary motor power NEL. -
page 06.01-25
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development. www.tangra.bg
21
06.01-20
AHU–H / AHU-DD AIR HANDLING UNITS
BDB 1000
Note :
• For determination of sound level pressure on frequency
bands - page 06.01-24
• For determination of the necessary motor power NEL. -
page 06.01-25
www.tangra.bg We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.
22
AIR HANDLING UNITS AHU–H / AHU-DD 06.01-21
CBP - 18/18
Note :
• For determination of sound level pressure on frequency
bands - page 06.01-24
• For determination of the necessary motor power NEL. -
page 06.01-25
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development. www.tangra.bg
23
06.01-22
AHU–H / AHU-DD AIR HANDLING UNITS
www.tangra.bg We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.
24
AIR HANDLING UNITS AHU–H / AHU-DD 06.01-23
Note :
• For determination of sound level pressure on frequency
bands - page 06.01-24
• For determination of the necessary motor power NEL. -
page 06.01-25
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development. www.tangra.bg
25
06.01-24
AHU–H / AHU-DD AIR HANDLING UNITS
Acoustic characteristics
For all types of fans sound pressure level could be defined by the formula:
Lw = Lw (A) + K , where:
• Lw (A) read from the graphics of each fan for specific air flow and pressure (page. 06.01–18 ÷ 06.01-24)
• К [dB] factor of correction for sound pressure level on frequency bands
www.tangra.bg We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.
26
AIR HANDLING UNITS AHU–H / AHU-DD 06.01-25
Example:
BDB 500
Air flow Q=14760 m³/h The necessary motor power is determined by the formula:
Dynamic pressure Pd=62 Pa
Fan speed N=1900 min-1 Nel = K1 Wвен
K2
Efficiency η=78% , where:
Air velocity V=10.07 m/s
Total pressure Pt=1515 Pa • K1 – safety factor to overcome the starting torque
Absorbed power Wвен=8.0 kW • K2 – efficiency (for V-belt transmissions K2=0.9)
Sound pressure level Lw(A)=90.3 dB(A)
Absorbed power W [kW] < 0.5 0.5 ÷ 2.0 2.0 ÷ 5.0 5.0 ÷ 10.0 > 10.0
Safety factor K1 1.5 1.3 1.2 1.15 1.1
Model Fan Lw(A) 63 125 250 500 1000 2000 4000 8000
3.9 5.8 0.7 -2.9 -5.8 -8.8 -14.5 -20.8
BU ** BDB 500Т 90.3 dB
94.2 96.1 91.0 87.4 84.5 81.5 75.8 69.5
Order designation - BU 16 / 33 – R / (14760 / - ) (11,0kW)
• BU 16 - fan section type with fan BDB 500C, Nел=11.0kW / 380V
• 33 – performance scheme (see page 06.01-10); ending section; fan position 0°
• R – air stream direction the inspection side – from left to right
• 14760 m³/h - air flow 15500³/h and total pressure 1515 Pa
• (11.0kW) - absorbed power different from the nominal
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development. www.tangra.bg
27
06.01-26
AHU–H / AHU-DD AIR HANDLING UNITS
• Air handling unit is mounted over a leveled building site (foundation or construction). The site should be sized for the
specific camera.
• Sections are mounted one to another with sealing rubber between them. Connection between them is made with bolt
connection.
• When connect the air handling unit to duct system, flexible connections should be used to prevent transmissions of noise
and vibration.
• The supplying pipes for heating and cooling units should not prevent the unit maintenance. It is advisable to connect
them through flexible pipe-connections.
• The indicated directions of inlet and outlet of water sections and counter-flow between water and air must be observed.
• To prevention of freezing of water coil unit is recommended at the inlet section (fresh air) to mount multiple leaf damper
equipped with spring return actuator.
• Must be ensured siphon, placed before condensation line is connected to the building installation.
• To make a repair or maintenance of the unit, enough space in front of it must be ensured.
• The size of doors and entry of the technical room should be considered with the overall dimensions of the installed sec-
tions when mounted, repaired or maintained.
www.tangra.bg We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.
28
AIR HANDLING UNITS AHU–H / AHU-DD 06.01-27
Order designation
1. BU 16 / 32 – R / (15500/700) Fan section with BDB 500C,air flow 15500 m³/h and external pressure 700Pa,
position 270°, direction – R – from left to right; Nel. = 7.5kW/380V; ending section
according scheme 32;
2. BU 16B / 62 – L / (15500/550) Fan section with BPF 560, air flow 15500 m³/h and external pressure 550Pa,
direction – L – from right to left; Nel. = 7.5kW/380V; ending section according
scheme 62 with outlet flange 1200/700
3. TU 16 / 2R / 4R / K – R Thermal section with 2-rows heating and 4-rows cooling heat exchanger, drop
eliminator and drain tray. Direction from the supply side R – from left to tight
4. InU 16 / 1 / F / 1050х1000 - L Inlet section with air filter and damper, height – 1050mm and length 1000mm;
direction L – from right to left; multiple leaf damper with manual control PJR
1200/700+M; bag filters AFC-B (F7) (specify when ordering)
5. InU 16 / 1 / F+F / 1050x1150 - R Inlet section with two-stage cleaning and damper; height 1050mm and length
1115mmm, direction R – from left to right, damper PJR 1200/700+A with spring
return actuator; air filter AFC-V (G4), bag filter – AFC-B (F7). Type of filters and
actuator are specified when ordering
6. RU-REC 16 - R / L1 Recuperative section with plate heat exchanger type REC-Al, drain tray and by-
pass damper PJR-BP, direction of fresh air R – from left to right and direction of
exhausted air L1 - from right to left
Note :
• Fans total pressure, speed, absorbed power and belt drive are selected automatically.
• Actuator type is specified when ordering.
• Air filters types are specified when ordering.
• When ordering should be additionally specified control elements and automation, as well as other options and possibilities
(see p . 06.01-5)
• The scheme is viewed from the inspection side
• Implementation of the order is proceed after co-ordination of scheme and technical parameters of the unit.
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development. www.tangra.bg
29
06.01-28
AHU–H / AHU-DD AIR HANDLING UNITS
Exhaust air
Premises
Fresh air
Air handling unit with mixing section and pre-heating exchanger “water-air”
Exhaust air
Premises
Fresh air
Units
• BS - supply fan • COT1– pre-heating water exchanger
• BЕ - exhaust fan • COT – water heating section
• COX – water cooling section
www.tangra.bg We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.
30
AIR HANDLING UNITS AHU–H / AHU-DD 06.01-29
Fresh air
Premises
Exhaust air
Exhaust air
Premises
Fresh air
Units
• BS - supply fan • REC - plate heat exchanger
• BЕ - exhaust fan • ROT - rotary regenerative heat exchanger
• COT – water heating section
• COX – water cooling section
Control equipment and automation elements:
• DA1 - fresh air damper actuator • TP - temperature probe managing VAH/VAC
• DA2 - exhausted air damper actuator • TP1 - temperature probe managing DA3 (by-pass
• DA3 - by-pass damper actuator damper REC-AL - “free cooling”)
• DPS1 - differential pressure switch - rough filter for fresh • VAH - 3-way valve actuator - heating
air • VAC - 3-way valve actuator - cooling
• DPS2 - differential pressure switch - fine filter for fresh air • FIS - frequency inverter control of the supply fan
• DPS3 - differential pressure switch - air filter for exhaust- • FIE - frequency inverter control of the exhaust fan
ed air • FIR - frequency inverter control of rotary regenerative
• DPSB1 - differential pressure switch - torn belt of the heat exchanger
supply fan • CP1 – circulation pump - heating
• DPSB2 - differential pressure switch - torn belt of the • CP2 – circulation pump - cooling
exhaust fan
• DPSBP - pressure switch managing DA3 (defrosting REC-
AL - winter mode
• FP - frost protection of water section COT
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development. www.tangra.bg
31
www.tangra.bg We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.
32
Ruse
Shumen
Vratsa
Gorna Oriahovitsa
Varna
Gabrovo
Sofia Sliven
Kazanlak Burgas
Pernik
Stara Zagora
Blagoevgrad
Plovdiv Haskovo
Office Varna
West Industrial Range
behind printing house Varna - East
Head office Tel.: (00359 52) 611 767
174, Europa Blvd. e-mail: varna@tangra.bg
1331 Sofia, Bulgaria
www.tangra.bg
Tel.: (00359 2) 925 05 99; 925 06 10 Office Burgas
Tel.: (00359 2) 927 58 13; 972 71 80 6, Transportna Str.
Fax: (00359 2) 925 05 57 Tel.: (00359 56) 861 200
e-mail: office@tangra.bg e-mail: bourgas@tangra.bg