Maintenance
Note
siaao1ia,
Figure 210. Tag details for an digital channel.
Disable commissioning access
16 When finished push the System Info Display button,
17 _ Use the up/down arrow keys to select Commissioning and
push Enter.
= The prompt Enter 0 to disable commissioning access: is
displayed on the lower left side of the colour graphics,
display.
18 Type in O and push Enter.
- Commissioning status changes from Yes to No.
8.10.5 How to replace Distributed
Processing Units
Never replace more than one DPU unit at a time!
All DPUs look very similar. Make sure the replacement unit is of
exactly the same type as the failing unit. Type specification is
available on the label for each unit. Do the following:
1 Remove the screws for the termination bracket.
Disconnect all connectors.
2
3 Remove the mounting screws.
40sK-Chief 500 Instruction manual
406
ene ee TaN
Figure 211 Electrical disconnection,
CULL] tse sre oat re
BU
D Lacan eran de rah revo
Figure 212, Mechanical disconnection.
5 Install the replacement unit.
6 Use the up/down keys to select Replace Modules and push
Enter.
= The promt Enter Password is displayed.
7 Type in the password: *****
8 Under DPUs with COMM error, select the failed unit and
push Install Replacement DPU.
S12401/a,‘Maintenance
312401
‘After a few moments the system indicates Successfully
Replaced DPU. The alarm related to the failing unit
disappears.
Confirm that the DPU is Working Correctly.