Maintenance Note siaao1ia, Figure 210. Tag details for an digital channel. Disable commissioning access 16 When finished push the System Info Display button, 17 _ Use the up/down arrow keys to select Commissioning and push Enter. = The prompt Enter 0 to disable commissioning access: is displayed on the lower left side of the colour graphics, display. 18 Type in O and push Enter. - Commissioning status changes from Yes to No. 8.10.5 How to replace Distributed Processing Units Never replace more than one DPU unit at a time! All DPUs look very similar. Make sure the replacement unit is of exactly the same type as the failing unit. Type specification is available on the label for each unit. Do the following: 1 Remove the screws for the termination bracket. Disconnect all connectors. 2 3 Remove the mounting screws. 40s K-Chief 500 Instruction manual 406 ene ee TaN Figure 211 Electrical disconnection, CULL] tse sre oat re BU D Lacan eran de rah revo Figure 212, Mechanical disconnection. 5 Install the replacement unit. 6 Use the up/down keys to select Replace Modules and push Enter. = The promt Enter Password is displayed. 7 Type in the password: ***** 8 Under DPUs with COMM error, select the failed unit and push Install Replacement DPU. S12401/a, ‘Maintenance 312401 ‘After a few moments the system indicates Successfully Replaced DPU. The alarm related to the failing unit disappears. Confirm that the DPU is Working Correctly.