Professional Documents
Culture Documents
132Kv Bus: Transformer 132/X KV Ynynd11
132Kv Bus: Transformer 132/X KV Ynynd11
1. Introduction
Many distribution networks around the world have limited earth-fault current by a resistor located in
the LV winding neutral point of for example an 132/X kV infeed transformer. LV voltage level (i.e. X
kV) depends on a particular utility and country and can have different value. Some typical values
are 6.3kV, 13.8kV, 20kV and 35kV. Simplified single-line diagram of such distribution network and
the relevant fault points for the LV side low-impedance restricted earth-fault protection function (i.e.
REF) are shown in Figure 1.
Note that for such installations special attention regarding LV side low impedance REF protection
setting and ACT configurations shall be taken. This is even more important if only one single
grounding resistor is used for the entire LV network and at the same time the LV network consist
mainly of cable feeders. Namely the capacitance to ground of such cable network is quite large and
this can cause difficult operating condition for LV REF function in case of internal earth-fault as
described in this document.
132kV BUS
Transformer
132/X kV
YNynd11
F1
P2
P1
LV BUS (X kV)
F2
Extensive LV cable
network
Note that internal earth-fault location (i.e. F1) and external earth-fault location (i.e. F2) are also
marked in Figure 1.
IN_W2/3 Io_Net
LT LE
RE
3Io
3R1 CE
Uo
IN
Ground
Figure 2: Simplified equivalent circuit for the zero-sequence system during internal single phase-to-ground fault
The simplified, zero-sequence equivalent circuit during the external fault is shown in Figure 3.
External Fault
LV Busbar Point F2
IN_W2/3 Io_Net
LT LE
RE
3Io
3R1 CE
Uo
IN
Ground
Figure 3: Simplified equivalent circuit for the zero-sequence system during external single phase-to-ground fault
By looking into the equivalent circuits (i.e. above two figures) the following can be concluded:
1) IN_W2 current component will be slightly inductive due to dominant resistance (i.e. R1) in
that circuit branch (i.e. it will lag behind the Uo voltage for several degrees)
2) Io_Net current component will be dominantly capacitive due to dominant capacitance (i.e.
CE) in that circuit branch (i.e. it will lead the Uo voltage for almost 90°)
Conclusion: During an internal earth-fault, the angle between these two zero-sequence current
components will be around 90° or even somewhat bigger (see Figure 2). This can cause problems if
REF function utilizes directional measurement for its operation. Note that for external faults the REF
function will see 180° between two measured zero-sequence current components. The reason is that
IN_W2 component will be measured in both measurement points by the function (see Figure 3) due to
a fact that the fault location (i.e. F2 in Figure 1) will be outside of the protected zone.
Figure 5: Zoom into the instant when single phase-to-ground fault has happened
Figure 7: Phasor diagram for LV currents at t=+0,04s (see Figure 3 or 4 for time scale)
Figure 9: Used settings for W2 REF function (Base current was set to 2187A primary)
Conclusion: The LV REF function did not operate because the measured angle between IN_W2
and 3Io_W2 phasors was bigger than the set value of 60° which is the default value for the REF
function. The reasons why this angle had value of 93° is already explained in the Section 2 of this
document. Thus, this captured recording just confirms the previously given theory in this document.
1. Set parameter ROA to 90°. However please note that this will still not guaranty the secure
operation of the W2 REF function. Therefore the second point given below is as well
strongly recommended to be implemented in such installations.
2. Trip tripping logic for such REF function shall be arranged in ACT as shown in Figure 10.
Practically the START signal from the W2 REF function will be allowed to trip if there is no
start of the overcurrent protection on the LV side and no other protection function has
already given a trip signal. The trip will be also blocked by presence of the second
harmonic in the neutral point current. As additional security during switching operations in
the LV network this trip shall be also time delayed for two cycles. Note that above
configuration is given for RET650, but similar configuration shall be arranged even when
RET670 is used.
The above two corrective measures shall ensure proper operation of the low-impedance REF
function for an installation in such type of distribution network.