DESCRIPTIVE BULLETIN
Advance®
ANSI 5/8.25/15 kV switchgear
—
ABB Inc.
655 Century Point
Lake Mary, FL 32746
Phone: +1 407 732 2000 ext. 2510
+1 800 929 7947 ext. 5
customer.service.group@us.abb.com
abb.com/mediumvoltage
—
Advance® is ABB’s ANSI platform —
for 5, 8.25 and 15 kV rated metal- Table of contents
clad switchgear featuring a small
footprint and designed and tested
per IEEE C37.20.2. Using
004 – 005 Product overview and highlights
galvanized steel construction, hem 006 AMVAC breakers for the Advance
bending techniques, and Delrin platform
Product overview and highlights properties to provide for better instrument viewing.
Hem Bending
• Lift truck
• Manually and electrically operated Ground & Test
devices (25-50 kA ratings only)
The process of folding a single sheet of steel over
upon itself, is used throughout the construction of Advance Options
ABB’s ANSI platform for 5, 8.25 and 15 kV rated metal-clad switchgear Advance. This construction technique is the same • Outdoor non-walk-in and sheltered aisle
as that used in arc-resistant switchgear offering enclosures
featuring a small footprint and designed and tested per IEEE C37.20.2. increased rigidity, strength and reduced arc • Utility metering compartments
propagation beyond most competitor’s non-arc- • IR viewing ports; ground studs; lightning arresters
resistant switchgear designs. It also serves to • Generator circuit breakers
protect maintenance personnel and any LV wiring • Ultra Fast Earthing Switch (UFES™)
Using galvanized steel construction, hem bending Available configuration/competitive footprint
inside the switchgear, eliminating sharp edges and • Fault current limiting devices
techniques, and Delrin arc-quenching contacts, Advance features the most competitive footprint
burrs that are common in other techniques. • Digital switchgear with current and voltage
the Advance product line is designed with safety, in the market with available two-high
sensors and 61850-based communication
reliability and durability in mind. configurations. Standard frames measures 36
• SwitchgearMDTM 24x7 monitoring
inches wide, 95 inches tall and 85 inches deep,
Product Highlights regardless of one or two-high breaker
• Continuous current ratings of 1200, 2000, 3000 configurations. Even shallower depths are Characteristics Unit Rated maximum voltage level*
A, with 4000 A forced air cooled (FAC) available possible, depending upon ratings and devices 5 kV 8.25 kV 15 kV
for 25-63 kA ratings installed. 6.9, 7.2, 8.4, 11,
Rated nominal voltages 12, 12.47, 13.2,
• Interruption ratings of 25-63 kA kV 2.4, 4.16, 4.8 4.8, 6.9, 8.2 13.8, 14.4
• Fully compliant to IEEE C37.20.2-1999 for metal- When large additional equipment is needed in the Main bus continuous current A 1200, 2000, 3000, 4000**
clad switchgear construction rear, such as large CPTs and station class surge Short circuit current (rms) kA 25, 31.5, 40, 50, 63
• PT, CPT and CPT fuse auxiliary units feature arresters, depths of 92 inches, or greater can be Rated frequency Hz 50, 60
closed door racking provided. When extra space is needed on the
Low Frequency Withstand (rms) kV 19 36 36
• Available SmartRack remote racking system for front doors, a 10-inch extension can be installed
Impulse level (BIL, crest) kV 60 95 95
Breakers, PT and CPTs providing space for deeper relays and other
* Ratings given are for service conditions within temperature and altitude limitations as de-
• UL and CSA available control devices across most of the entire height
fined by IEEE C37.20.2-2015 metal-clad switchgear standard.
• Automatic secondary disconnects of the front doors. ABB can assist in optimizing ** 4000 A is forced-air cooled.
— Ratings shown are for usual service conditions. For 27 kV applications, reference Advance 27 documentation 1VAL107001-FL.
• Large Lexan viewing window for viewing design requirements.
01 Test cabinet
breaker status and position —
• Modular design and construction Indoor and outdoor enclosures 02Lift truck
—
• Available two-high construction Advance is provided in a standard indoor 03 SmartRack®
—
• Available top and bottom cable or bus duct enclosure, meeting or exceeding the
04 Test cabinet
entry requirements of ANSI C37.20.2, and is also
• Standard 36-inch wide, 95-inch tall frame with available in both the non-walk-in and single row
depths of 85 or 92 inches walk-in (sheltered aisle) type outdoor enclosures.
• Galvanized construction for superior rust
protection and illumination properties Delrin arc-quenching contacts
• Hem bending of 14 gauge steel for strength and For PT, CPT and CPT fuse contacts, ABB uses
rigidity Delrin arc-quenching contacts. Due to the unique
• Delrin arc-quenching contacts for auxiliary units properties of Delrin, which include self-
• ISO 9001 certified manufacturing facilities lubrication, arcs created during load break
conditions are extinguished by a gas emitted by
— the Delrin material as it heats. The recessed
Advance features the most contact design also eliminates the need for safety
shutters as access to live bus is very difficult.
competitive footprint in the
market with available two-high
configurations.
— — — —
01 02 03 04
6 A D VA N C E ® A N S I 5/ 8 . 2 5/ 1 5 K V S W I TC H G E A R DESCRIPTIVE BULLETIN 7
— —
AMVACTM breakers for the Advance platform ADVAC® breakers for the Advance platform
General overview General overview
The AMVAC TM breaker is a magnetically actuated The ADVAC® breaker is a spring mechanism
and latched breaker capable of a high number of breaker with modular, easy to maintain design.
operations due to its simplified design. Fully Fully compliant with IEEE Standards C37.04,
compliant with IEEE Standards C37.04, C37.06 C37.06 and C37.09, the ADVAC breaker is a great
and C37.09, the AMVAC breaker is a great fit for fit for many applications.
many applications.
Features
Features • Mechanical operations counter
• Mechanical operations counter • Open, closed, ready/not ready lights and push-
• Optional roll-on-floor design buttons
• Open, closed, ready/not ready lights and push- • Mechanical anti-pump
buttons
— —
Available AMVAC breaker ratings Available ADVAC breaker ratings
—
ADVAC® breakers for 63 kA applications
—
General overview Instrument transformers
The ADVAC series is a complete line of ANSI-rated
vacuum circuit breakers offering power distribu-
Current transformers
tion system customers the advantages of the lat-
est technology that reduces ownership costs
through improved reliability and maintainability.
Maintenance costs are further reduced due to Advance is designed and tested for use with the Product features
ABB vacuum interrupter and contact design, with ABB SAB-1/1D current transformers for 1200 and • 600 volt indoor
contacts that wear less than 1 mm during the life- 2000 A applications, and the SAB-2/2D current • 10 kV BIL
time of the breaker. transformers for 3000 A and 4000 A applications. • 25 through 400 Hertz
These CT’s are used for voltage ratings of 5, 7.5 and • 50-5000 primary amperes
15 kV and are located on the breaker primary • Mechanical rating:
bushings. - 180 x rated current
• Thermal rating:
— Each breaker primary bushing can accommodate - 80 x rated current, one second
Available ADVAC breaker ratings
up to two (2) standard accuracy CTs (SAB-1 or SAB- • Continuous current rating factor:
Low Cap switch 2), for a total possible four (4) current transformers - 50-4000 primary amperes:
Max wave Short circuit/ frequency rating (15
Continuous voltage withstand Close & latch withstand kA peak, Interrupt Closing time per phase. For high accuracy requirements the 1.33 @ 30°C ambient
Voltage class current (kV, rms) (2 sec) (kA, peak) BIL (kV) (Hi-pot) 2.0 kHz) time (cycles) (msec) bushings can accommodate one (1) CT, for a total 1.00 @ 55°C ambient
kV A kA, rms kA, peak kV, rms of two (2) CTs per phase. - 5000 primary amperes:
5/15 kV 1200 A 5/15 63 164 95 36 C1 (1600 A) 3 50-80 1.00 @ 30°C ambient
2000 A 5/15 63 164 95 36 C1 (1600 A) 3 50-80 SAB CTs are available in single and multi-ratio 0.50 @ 55°C ambient
3000 A 5/15 63 164 95 36 C1 (1600 A) 3 50-80 styles with primary ampere ratings from 50 to • UL Recognized Component; File No. E96461
5,000 amps. These current transformers are used
as a source of current for both relaying and
metering. The deeper case SAB-D is used when
high burden relaying and metering is required.
— —
Instrument transformers Instrument transformers
5 kV voltage transformers 15 kV voltage transformers
For 5 kV applications, Advance is designed and IEEE test reports are stored electronically and can For 8.25 – 15kV applications, Advance is designed IEEE test reports are stored electronically and can
tested for use with the ABB VIY-60 indoor voltage be emailed in various formats at the time of and tested for use with the ABB VIZ Indoor Voltage be emailed in various formats at the time of
transformers. shipment. Transformers. shipment.
The VIY-60 indoor voltage transformers are fused These units meet all applicable IEEE and NEMA The VIZ-75 and VIZ-11 indoor voltage transformers These units meet all applicable IEEE and NEMA
and used for metering or relaying applications. standards and are UL Recognized components. are fused and used for metering or relaying standards and are UL Recognized components.
applications. Both units are available in single,
Advance utilizes drawout trays for PTs that offer Product features double and tapped secondary designs with two Product features
closed-door racking for increased safety. These • 5 kV indoor accuracy and thermal rating options. • 8.25 and 15 kV indoor
trays are available in both single phase and three- • 60 kV BIL, 60 Hertz • 75 and 110 kV BIL, 60 Hertz
phase PT applications, and include both Wye-Wye • Primary volts: 2400 - 4800 Advance utilizes drawout trays for PTs that offer • Primary volts: 2400 - 14400
and Open Delta configurations. • UL Recognized Component, File No. E148620 closed-door racking for increased safety. These • UL Recognized Component, File No. E148620
trays are available in both single phase and three-
The primary and secondary coils are wound using phase, and include both Wye-Wye and Open Delta
special winding and shielding techniques for configurations.
improved voltage stress distribution. The coils are
designed to withstand continuous operation at 1.1 The primary and secondary coils are wound using
times the line-to-line voltage level and the line-to- special winding and shielding techniques for
ground voltage level for Y burden units. improved voltage stress distribution. The coils are
designed to withstand continuous operation at
Each coil is insulated with mylar film to provide a either 1.1 or 1.25 times the line-to-line voltage level
high dielectric strength between layers. The coils for Z burden units and 1.9 times the line-to-ground
and core are combined to create a complete voltage level for Y burden units.
winding structure that is assembled to a support
frame. The entire assembly is vacuum cast in Each coil is insulated with mylar film to provide a
polyurethane for added insulation and protection. high dielectric strength between layers. The coils
and core are combined to create a complete
winding structure that is assembled to a support
frame. The entire assembly is vacuum cast in
polyurethane for added insulation and protection.
12 A D VA N C E ® A N S I 5/ 8 . 2 5/ 1 5 K V S W I TC H G E A R DESCRIPTIVE BULLETIN 13
—
Distribution protection and control
ABB’s Relion® family of protection and control Relion 615R, 615 and 620 series relays include:
relays for distribution applications provides the • Comprehensive set of protection and metering
performance, safety, and ease-of-use that functions for feeders, transformers, and motors
switchgear specifiers and users demand. The • Draw-out design
Relion 615 and 620 series offer complete protection • Integrated Open/Close push buttons and Local/
and control for feeders, motors, and transformers Remote selector with indicating lights
— in switchgear applications and are characterized by • Protection and control for one and two breakers
01 Relion 615 series
—
their flexibility and performance in today’s and as well as breaker-and-a-half schemes
02 Relion 620 Series future distribution schemes. • Enhanced safety with optional arc fault protec-
—
03 COM600 Distribution
tion in all 615 and 620 series relays
automation controller The IEC 61850 implementation in Relion includes • Web browser based user interface accessible
fast peer-to-peer communication over the through an RJ45 front port
substation bus. GOOSE (Generic Object Oriented • Trip coil monitoring
Substation Events) communication is used • Monitoring of breaker health parameters such as
between Relion devices in switchgear to form a travel time, number of operations, wear and tear,
stable, reliable, and high-speed busbar protection and spring charging time
system, provide fast and dependable auto transfer • DNP3 and Modbus protocols included standard in
schemes and zone interlocking. Separate hard- all relays
wiring is not needed for the horizontal • Relion relays are fully IEC 61850 compliant for
communication between the switchgear cubicles. communication and interoperability of substa-
tion automation devices
Relion relays for feeder protection offer an optional • Fully ANSI and RoHS compliant as well as UL listed
cable fault detection function that can detect
extremely short duration underground faults. ABB’s COM600 Grid Automation Controller can be
These faults are typically undetectable by used as a local HMI to display switchgear single line
conventional protection where there is no diagrams and the status of devices such as
operation of the breaker. This feature helps users breakers and protection relays. COM600 also
to learn of these events faster, resulting in reduced provides gateway functionality to enable
down time. switchgear integration into SCADA systems. It can
be easily installed as part of the switchgear control
devices.
— — —
01 02 03