DETERMINATION OF SEISMIC LOADS

Seismic Factors: Seismic Deadloads at each floor:


Z 0.4 W1 3442.5 KN
I 1 W2 3442.5 KN
R 8.5 W3 3442.5 KN
Na 1 WT 10327.5 KN
Nv 1
Ca 0.44
Cv 0.96
Ct 0.0731
Hn 9.15

Area 450
DL (2F-3F) 7.65

BASE SHEAR COMPUTATION

Fundamental period of vibration, T


T = Ct(hn)3/4 0.385 sec

Total design base shear


V = CvIW/RT 3032.943 KN

A. The total design base shear need not exceed,


V = 2.50CaIW/R 1336.5 KN

B. The total design base shear shall be less than,


V = 0.11CaIW 499.851 KN

C. For seismic zone 4,


V = 0.80ZNvIW/R 388.8 KN

The value in () governs, V= 1336.5 KN


VERTICAL DISTRIBUTION OF LATERAL SEISMIC FORCES, where N=3
ft= .07TV 35.97909 KN
ft= 0.25V 334.125 KN
ft= 0(for t<0.70 sec) 0

Use ft = 35.97909 KN

The sumation Fi = V - Ft 1300.521 KN

A. Lateral force on each floor level


Floor level Wi hi Wihi fi fx fxhi
3 3442.5 9.15 31498.88 644.9738 680.9529 6230.719
2 3442.5 6.15 21171.38 433.507 433.507 2666.068
1 3442.5 3.15 10843.88 222.0402 222.0402 699.4265
Total 63514.13 1300.521 1336.5 9596.213

B. STORY DRIFTS OF THE BUILDING

Y-direction X-direction Ix Iy b
Floor level Fx or Fy Vx or Vy L (mm) kx Δy ky Δx
3 680.9529 680952.9 3300 7.039E-06 9.67E+10 7.039E-06 9.6746E+10 0.02000833 0.020008 0.7
2 433.507 1114460 3300 7.039E-06 1.58E+11 7.039E-06 1.5834E+11 0.02000833 0.020008
1 222.0402 1336500 3300 7.039E-06 1.9E+11 7.039E-06 1.8988E+11 0.02000833 0.020008
Total 1336.5 9900 4.45E+11 4.4496E+11

C. DIRECT LATERAL FORCE DISTRIBUTION ON EACH FRAMEOF THE BUILDING

TRANSVERSE FRAMES
Floor Level Fs A B C D E F G H
3 680.9529 51.07147 76.6072 68.09529 93.63102 85.11911 93.6310204 76.6071985 51.07147
2 433.507 32.51302 48.76953 43.3507 59.60721 54.18837 59.6072083 48.769534 32.51302
1 222.0402 16.65301 24.97952 22.20402 30.53052 27.75502 30.5305213 24.9795174 16.65301

LONGITUDINAL FRAMES
A B C D E F G H
42.55955 85.11911 85.11911 85.11911 85.11911 85.1191095 85.1191095 39.72225
25.28791 54.18837 54.18837 54.18837 54.18837 54.1883712 54.1883712 25.28791
12.95234 27.75502 27.75502 27.75502 27.75502 27.7550194 27.7550194 12.95234
D.) Torsional Lateral Force Distribution on each frame of the building

TRANSVERSE FRAMES
Floor Level Fs A B C D E F G H
3 680.9529 80 66.6 43.4 22.25 0 22.1 44.5 65.1
2 433.507 66.6 50.3 33.4 16.1 0 16.1 33.6 50.3
1 222.0402 33.1 24 15.8 8.3 0 8.3 16.5 25.1

LONGITUDINAL FRAMES
A B C D E F G H
88.86 66.65 43.4 22.21 0 22.21 44.52 65.2
67.2 50.5 34 16.1 0 16.1 33.6 50.4
33.1 24 15.8 8.3 0 8.3 16.5 25.2

E.) Resultant Lateral Force Distribution on each frame of the building

TRANSVERSE FRAMES
Floor Level Fs A B C D E F G H
3 680.9529 131.0715 143.2072 111.4953 115.881 85.11911 115.73102 121.107199 116.1715
2 433.507 99.11302 99.06953 76.7507 75.70721 54.18837 70.2883712 82.369534 82.81302
1 222.0402 49.75301 48.97952 38.00402 38.83052 27.75502 38.8305213 41.4795174 41.75301

LONGITUDINAL FRAMES
A B C D E F G H
131.4196 151.7691 128.5191 107.3291 85.11911 107.329109 129.639109 104.9223
92.48791 104.6884 88.18837 70.28837 54.18837 38.2 87.7883712 75.68791
46.05234 51.75502 43.55502 36.05502 112.8741 36.0550194 44.2550194 38.15234