Dead Load

Table 3.1

Dead Load Specification Reference Load (kPa)

Reinforced 4.13
Concrete
1. Slab weight Table 204-1
Thickness of Slab

175mm

2. Floor Finish Concrete fill finish 0.3


Table 204-2
13 mm

Total Uniform Dead Load (Roof deck) 4.43

3. Slab Weight Reinforced 4.13


Concrete
Table 204-1
Thickness of Slab

175 mm

4. Ceilings Gypsum Board 0.08


Table 204-2
9.5 mm

5. Floor Finish Concrete fill finish 0.3


Table 204-2
13 mm

6. Partition Windows, glass, 0.38


Table 204-2
(Exterior) frame and sash

7. Partition Hollow Concrete


(Interior) Masonry (plastered
on 2 sides), Wythe 3.32
Table 204-2
thickness = 100
mm, 21.2 kN/m3,
Full

Total Wall Dead Load (Interior) 7.83

Total Wall Dead Load (Exterior) 4.89

Total Uniform Dead Load (3rd floor) 8.21

8. Slab Weight Reinforced 4.13


Concrete
Table 204-1
Thickness of Slab

175 mm

9. Ceilings Gypsum Board 0.08


Table 204-2
9.5 mm

10. Floor Finish Concrete fill finish Table 204-2 0.3


13 mm

11. Partition Windows, glass, 0.38


Table 204-2
(Exterior) frame and sash

12. Partition Hollow Concrete


(Interior) Masonry (plastered
on 2 sides), Wythe 3.32
Table 204-2
thickness = 100
mm, 21.2 kN/m3,
Full

Total Wall Dead Load (Interior) 7.83

Total Wall Dead Load (Exterior) 4.89

Total Uniform Dead Load (2nd floor) 8.21

13. Slab Weight Reinforced 4.72


Concrete
Table 204-1
Thickness of Slab

200 mm

14. Floor Finish Concrete fill finish 0.3


Table 204-2
13 mm

15. Partition Windows, glass, 0.38


Table 204-2
(Exterior) frame and sash

16. Partition Hollow Concrete


(Interior) Masonry (plastered
on 2 sides), Wythe 3.32
Table 204-2
thickness = 100
mm, 21.2 kN/m3,
Full

Total Wall Dead Load (Interior) 7.83

Total Wall Dead Load (Exterior) 4.89

Total Uniform Dead Load (1st floor) 8.21

Total Uniform Dead Load (Total) 29.06

Live Load

Table 3.2

Live Load Specification Reference Load (kPa)

1. Minimum Design Live Load 4.8

2. Rain Flat with over 60 0.6


Table 205-3
m2 tributary area
Total Uniform Live Load (Roof deck) 5.4

Movable seats Table 205-1 4.8


3. Assembly areas
Stage areas Table 205-1 7.2

Total Uniform Live Load (3rd floor) 12

Call centers and 2.9


business processing Table 205-1
4. Office offices

Other offices Table 205-1 2.4

Total Uniform Live Load (2nd floor) 5.3

Retail 4.8
5. Stores Table 205-1

Total Uniform Live Load (1st floor) 4.8

Total Uniform Live Load (Total) 27.5

Earthquake Load

Seismic Load Computations based on NSCP 2015:

Table 3.29

Seismic Factors Description Reference Value

Z Zone 4 Table 208-3 0.4

I Standard Occupancy Table 208-1 1


Structures

Building Frame Table 208-11A 5.6


System (Ordinary
R reinforced concrete
shear walls or braced
frames)

Seismic Source Type (Table 208-5) 1.0


A with Greater than
Na 10km closest distance
to known seismic
source
Seismic Source Type (Table 208-6) 1.0
A with greater than
Nv 15 km closest
distance to known
seismic source

Ca = 0.44Na Stiff Soil Profile (Table 208-7) 0.44

Cv = 0.64Nv Stiff Soil Profile (Table 208-8) 0.64

Ct All other buildings (Section 208.5.2.2) 0.0488

Height of the Building (hn) 9.8 m

Base Shear Computations:

 Natural Period of building:

T = Ct(hn)3/4

= 0.0488 x(9.8)3/4

= 0.270296 secs

 Total design base shear

V = CVIW/RT

= 82893.125KN

A. The total design base shear need not exceed,

V = 2.50 CalW/R = 35825.606 KN

B. The total design base shear shall be less than,

V = 0.11CalW/R = 1576.3267 KN

C. For seismic zone 4,

V = 0.80ZNvlW/R = 10421.995 KN

The value that governs,

V = 35825.606 KN

For equilibrium of forces, the base shear V is equal to the dynamic force of the mass of the

structure:
Vertical distribution of lateral seismic forces, where n=3

ft= .07TV = 630.59993 KN

ft= 0.25V = 8956.4016 KN

ft= 0 (for t<0.70 sec)

Use ft = 630.59993 KN

Then ƩFi = V – Ft = 35825.606 KN

Lateral force on each floor level

Table 3.30 lists of earthquake loads per floor.

Table 3.30

Floor Wi, kN hi , m Wihi, kN-m Fi, kN Fx, kN Fxhi, kN-m


level

3 38522.29 8.9 342848.404 17442.31761 17442.31761 155236.6267

2 41533.82 5.8 240896.168 12255.52582 12255.52582 71082.04976

1 41533.82 2.9 120448.084 6127.762911 6127.762911 17770.51244

Total 121589.94 704192.656 35825.60634 35825.60634 244089.189

Story Drift of the Building

Table 3.31 lists of story drift per floor.

Table 3.31

Y-direction

Floor Fx or Fy Vx or Vy L Kx Δy
level
(m)

3 17442.31761 17442.31761 8.9 1.433506628 12167.5877

2 29697.84343 47140.15343 5.8 3.822222222 7769.784619

1 35825.60634 82965.75977 2.9 16.56632695 2162.555795


Total 22099.92811

X-direction Ix Iy

Floor ky Δx
level

3 3.669776969 4752.963943 0.00133333 0.000520833

2 9.784888889 3035.072117 0.00133333 0.000520833

1 42.40979699 844.7483573 0.00133333 0.000520833

Total 8632.784417

3.2.2.5 Total Factored Loads

The following are the major load combinations considered in the design of the structural

members:

1.4 DL (203-1)

1.2 DL + 1.6 LL (203-2)

1.2 DL + 1.6 (Lr or R) + (f1L or 0.5W) (203-3)

1.2DL + 1.0W + f1L + 0.5Lr (203-4)

1.2DL + 1.0E + f1L (203-5)

0.9DL + 1.0W (203-6)

0.9DL + 1.0E (203-7)

Where,

𝑓1 = 1.0 for floors in places of public assembly, for live loads in excess of 4.8 kPa, and for

garage live load

= 0.5 for other live loads


Where P is to be considered in design, the applicable load shall be added to the formulas

above, factored as 1.2P.