Professional Documents
Culture Documents
Modbus - MP15 A.c72-M4-V65
Modbus - MP15 A.c72-M4-V65
ADDRESS
DESCRIPTION NOTATION MODBUS FUNCTION
DEC. HEX. HR
0 0 40001 Stop Alarms (SA1) BINARY 03
1 1 40002 Stop Alarms (SA2) BINARY 03
2 2 40003 Stop Alarms (SA3) BINARY 03
3 3 40004 Stop Alarms (SA4) BINARY 03
4 4 40005 Preventive Alarms (PA1) BINARY 03
5 5 40006 Preventive Alarms (PA2) BINARY 03
6 6 40007 Preventive Alarms (PA3) BINARY 03
7 7 40008 Preventive Alarms (PA4) BINARY 03
8 8 40009 Commutation Alarms (CA1) BINARY 03
9 9 40010 Commutation Alarms (CA2) BINARY 03
10 A 40011 Commutation Alarms (CA3) BINARY 03
11 B 40012 Result of the Bit Formulas (RBF) BINARY 03
12 C 40013 Status (ST1) BINARY 03
13 D 40014 Status (ST2) BINARY 03
14 E 40015 Status (ST3) BINARY 03
15 F 40016 Status (ST4) BINARY 03
16 10 40017 Second:Minute BCD:BCD 03
17 11 40018 Hour:Day-of-week BCD:BCD 03
18 12 40019 Date:Month BCD:BCD 03
19 13 40020 Year:Null BCD:BCD 03
20 14 40021 Execution Function Word (EFWord1) UNSIGNED INT 03/06
21 15 40022
22 16 40023
23 17 40024
24 18 40025
25 19 40026
26 1A 40027
27 1B 40028
28 1C 40029
29 1D 40030
30 1E 40031
31 1F 40032
32 20 40033
33 21 40034
34 22 40035
35 23 40036
36 24 40037 Stop Alarms (SA5) BINARY 03
37 25 40038 Preventive Alarms (PA5) BINARY 03
38 26 40039 Status (ST5) BINARY 03
39 27 40040
40 28 40041
41 29 40042 Output Relays (OR1) BINARY 03
42 2A 40043
43 2B 40044
44 2C 40045
45 2D 40046
46 2E 40047 Input Optocouplers (IO1) BINARY 03
47 2F 40048 Input Optocouplers (IO2) BINARY 03
48 30 40049 Genset Frecuency x 100 (Hz) UNSIGNED INT 03
49 31 40050 Genset Voltage L1 (V) UNSIGNED INT 03
50 32 40051 Genset Voltage L2 (V) UNSIGNED INT 03
51 33 40052 Genset Voltage L3 (V) UNSIGNED INT 03
52 34 40053 Genset Voltage L12 (V) UNSIGNED INT 03
53 35 40054 Genset Voltage L23 (V) UNSIGNED INT 03
54 36 40055 Genset Voltage L31 (V) UNSIGNED INT 03
55 37 40056 Genset Current L1 (A) UNSIGNED INT 03
56 38 40057 Genset Current L2 (A) UNSIGNED INT 03
57 39 40058 Genset Current L3 (A) UNSIGNED INT 03
58 3A 40059 Genset Current by Neutral (A) UNSIGNED INT 03
59 3B 40060 Genset Power Phase L1 x10 (kW) UNSIGNED INT 03
60 3C 40061 Genset Power Phase L2 x10 (kW) UNSIGNED INT 03
61 3D 40062 Genset Power Phase L3 x10 (kW) UNSIGNED INT 03
62 3E 40063
63 3F 40064
64 40 40065
65 41 40066
66 42 40067 Genset Total Power x 10 (kW) UNSIGNED INT 03
67 43 40068
68 44 40069 Mains Frecuency x 100 (Hz) UNSIGNED INT 03
69 45 40070 Mains Voltage L1 (V) UNSIGNED INT 03
70 46 40071 Mains Voltage L2 (V) UNSIGNED INT 03
71 47 40072 Mains Voltage L3 (V) UNSIGNED INT 03
72 48 40073 Mains Voltage L12 (V) UNSIGNED INT 03
73 49 40074 Mains Voltage L23 (V) UNSIGNED INT 03
74 4A 40075 Mains Voltage L31 (V) UNSIGNED INT 03
75 4B 40076 Mains Current L1 (A) UNSIGNED INT 03
76 4C 40077 Mains Current L2 (A) UNSIGNED INT 03
77 4D 40078 Mains Current L3 (A) UNSIGNED INT 03
78 4E 40079 Mains Current by Neutral (A) UNSIGNED INT 03
79 4F 40080 Mains Power Phase L1 x10 (kW) UNSIGNED INT 03
80 50 40081 Mains Power Phase L2 x10 (kW) UNSIGNED INT 03
81 51 40082 Mains Power Phase L3 x10 (kW) UNSIGNED INT 03
82 52 40083
83 53 40084
84 54 40085
85 55 40086
86 56 40087 Mains Total Power x10 (kW) UNSIGNED INT 03
87 57 40088
88 58 40089 Genset Power Phase L1 x10 (kVA) UNSIGNED INT 03
89 59 40090 Genset Power Phase L2 x10 (kVA) UNSIGNED INT 03
90 5A 40091 Genset Power Phase L3 x10 (kVA) UNSIGNED INT 03
MEMORY MAP
Electra Molins S.A MODBUS_MP15 A.C72-M4-V65
2 / 13
ADDRESS
DESCRIPTION NOTATION MODBUS FUNCTION
DEC. HEX. HR
256 100 40257 Execution Function Bit (EFBit1) BINARY 03/06/10
257 101 40258 Execution Function Bit (EFBit2) BINARY 03/06/10
258 102 40259 Execution Function Bit (EFBit3) BINARY 03/06/10
259 103 40260 Execution Function Bit (EFBit4) BINARY 03/06/10
260 104 40261 Execution PLC Bit (EPBit1) BINARY 03/06/10
261 105 40262 Execution PLC Bit (EPBit2) BINARY 03/06/10
262 106 40263 Execution PLC Bit (EPBit3) BINARY 03/06/10
263 107 40264 Execution Function Bit (EFBit5) BINARY 03/06/10
STOP ALARMS
Electra Molins S.A MODBUS_MP15 A.C72-M4-V65
3 / 13
ADDRESS
BIT Stop Alarms (SA1)
DEC. HEX. HR
00 Failure to start
01 Alternator voltage too low
02 Alternator voltage too high
03 Voltage phase imbalance
04 Engine underspeed
05 Engine overspeed
06 Overcurrent
07 Short-circuit
0 0 40001
08 Failure to start bat charging alternator
09 Low oil pressure
10 High engine temperature
11 High oil temperature Shutdown
12 Low fuel level
13 Low coolant level
14 Engine overpower
15 Earth leakage
ADDRESS
BIT Stop Alarms (SA2)
DEC. HEX. HR
00 Open power cabinet
01 Deconfigured system clock
02 Neutral overcurrent (51N)
03 Neutral Short-circuit (50N)
04 Negative phase sequence (46)
05 Reverse reactive power (32Q)
06 Excitation failure in electrical axis
07 Alternator excitation failure
1 1 40002
08 Engine diagnosys
09 Tension in bars
10 Load step too high
11 Emergency stop
12 Active power inverse
13 Oil sensor failure
14 Temperature sensor failure
15 Sensor temperatura d'oli
ADDRESS
BIT Stop Alarms (SA3)
DEC. HEX. HR
00
01
02
03
04
05
06
07
2 2 40003
08 Electric axis synchronism failure
09
10
11
12
13
14
15
ADDRESS
BIT Stop Alarms (SA4)
DEC. HEX. HR
00 OPTIONAL ALARM 09
01 OPTIONAL ALARM 10
02 OPTIONAL ALARM 11
03 OPTIONAL ALARM 12
04 OPTIONAL ALARM 13
05 OPTIONAL ALARM 14
06 OPTIONAL ALARM 15
07 OPTIONAL ALARM 16
3 3 40004
08 OPTIONAL ALARM 01
09 OPTIONAL ALARM 02
10 OPTIONAL ALARM 03
11 OPTIONAL ALARM 04
12 OPTIONAL ALARM 05
13 OPTIONAL ALARM 06
14 OPTIONAL ALARM 07
15 OPTIONAL ALARM 08
STOP ALARMS
Electra Molins S.A MODBUS_MP15 A.C72-M4-V65
4 / 13
ADDRESS
BIT Stop Alarms (SA5)
DEC. HEX. HR
00 OPTIONAL ALARM 25
01 OPTIONAL ALARM 26
02 OPTIONAL ALARM 27
03 OPTIONAL ALARM 28
04 OPTIONAL ALARM 29
05 OPTIONAL ALARM 30
06 OPTIONAL ALARM 31
07 OPTIONAL ALARM 32
36 24 40037
08 OPTIONAL ALARM 17
09 OPTIONAL ALARM 18
10 OPTIONAL ALARM 19
11 OPTIONAL ALARM 20
12 OPTIONAL ALARM 21
13 OPTIONAL ALARM 22
14 OPTIONAL ALARM 23
15 OPTIONAL ALARM 24
PREVENTIVE ALARMS
Electra Molins S.A MODBUS_MP15 A.C72-M4-V65
5 / 13
ADDRESS
BIT Preventive Alarms (PA1)
DEC. HEX. HR
00 Open circuit breaker
01 Electronic battery charger
02 Low battery voltage
03 High battery voltage
04 Low battery voltage 2
05 High battery voltage 2
06 Fuel level sensor failure
07 Low engine preheating
4 4 40005
08 Battery charging alternator
09 Oil pressure pre-alarm
10 Temperature pre-alarm
11 Oil Temperature pre-alarm
12 Low fuel level pre-alarm
13 Coolant level pre-alarm
14 Pre-alarm engine power
15 Earth leakage
ADDRESS
BIT Preventive Alarms (PA2)
DEC. HEX. HR
00
01 Deconfigured system clock
02
03
04
05
06
07
5 5 40006
08 Engine diagnosys
09 Average load last 24 hours
10 Preventive maintenance
11 Battery weak to crank
12 Mains power inverse
13 Clogged oil filters
14 Low load long time
15 Battery 2 weak to crank
ADDRESS
BIT Preventive Alarms (PA3)
DEC. HEX. HR
00
01
02
03
04
05
06
07
6 6 40007
08
09
10
11
12
13
14
15
ADDRESS
BIT Preventive Alarms (PA4)
DEC. HEX. HR
00 OPTIONAL ALARM 09
01 OPTIONAL ALARM 10
02 OPTIONAL ALARM 11
03 OPTIONAL ALARM 12
04 OPTIONAL ALARM 13
05 OPTIONAL ALARM 14
06 OPTIONAL ALARM 15
07 OPTIONAL ALARM 16
7 7 40008
08 OPTIONAL ALARM 01
09 OPTIONAL ALARM 02
10 OPTIONAL ALARM 03
11 OPTIONAL ALARM 04
12 OPTIONAL ALARM 05
13 OPTIONAL ALARM 06
14 OPTIONAL ALARM 07
15 OPTIONAL ALARM 08
PREVENTIVE ALARMS
Electra Molins S.A MODBUS_MP15 A.C72-M4-V65
6 / 13
ADDRESS
BIT Preventive Alarms (PA5)
DEC. HEX. HR
00 OPTIONAL ALARM 25
01 OPTIONAL ALARM 26
02 OPTIONAL ALARM 27
03 OPTIONAL ALARM 28
04 OPTIONAL ALARM 29
05 OPTIONAL ALARM 30
06 OPTIONAL ALARM 31
07 OPTIONAL ALARM 32
37 25 40038
08 OPTIONAL ALARM 17
09 OPTIONAL ALARM 18
10 OPTIONAL ALARM 19
11 OPTIONAL ALARM 20
12 OPTIONAL ALARM 21
13 OPTIONAL ALARM 22
14 OPTIONAL ALARM 23
15 OPTIONAL ALARM 24
COMMUTATION ALARMS
Electra Molins S.A MODBUS_MP15 A.C72-M4-V65
7 / 13
ADDRESS
BIT Commutation Alarms (CA1)
DEC. HEX. HR
00 Mains breaker connection failure
01 Mains breaker disconnection failure
02 Mains unexpected circuit breaker tripping
03 Mains circuit breaker intensity relay
04 Mains circuit breaker extracted
05
06
07
8 8 40009
08 Genset breaker connection failure
09 Genset breaker disconnection failure
10 Genset unexpected circuit breaker tripping
11 Genset circuit breaker intensity relay
12 Genset circuit breaker extracted
13
14
15
ADDRESS
BIT Commutation Alarms (CA2)
DEC. HEX. HR
00 CAN1 communication failure
01 CAN2 communication failure
02 Without data reception CAN1
03 Without data reception CAN2
04
05
06
07
9 9 40010
08 Incorrect phase sequence
09 Genset synchronization failure
10 Ground fault of the neutral
11 Maximum running time in parallel
12 Fault frequency running in parallel
13 Fault voltage running in parallel
14 Electric axis synchronism failure
15
ADDRESS
BIT Commutation Alarms (CA3)
DEC. HEX. HR
00 OPTIONAL ALARM 09
01 OPTIONAL ALARM 10
02 OPTIONAL ALARM 11
03 OPTIONAL ALARM 12
04 OPTIONAL ALARM 13
05 OPTIONAL ALARM 14
06 OPTIONAL ALARM 15
07 OPTIONAL ALARM 16
10 A 40011
08 OPTIONAL ALARM 01
09 OPTIONAL ALARM 02
10 OPTIONAL ALARM 03
11 OPTIONAL ALARM 04
12 OPTIONAL ALARM 05
13 OPTIONAL ALARM 06
14 OPTIONAL ALARM 07
15 OPTIONAL ALARM 08
STATUS
Electra Molins S.A MODBUS_MP15 A.C72-M4-V65
8 / 13
ADDRESS
BIT Status (ST1)
DEC. HEX. HR
00 Genset manual start
01 Genset priority enabled
02 Genset in stopping cycle
03 Genset running
04 Genset not stopped
05 Alarm service activated
06 Genset available
07 Genset in service
12 C 40013
08 System out of service
09 Manual service
10 Automatic service
11 Test mode operation
12 Lock of shutdown alarms
13 Electronic battery charger ON
14 Correct mains voltage
15 Correct genset voltage
ADDRESS
BIT Status (ST2)
DEC. HEX. HR
00 Synchronize to close group
01 Synchronize to close mains
02 Manual permanent parallel order ON
03 Automatic permanent parallel order ON
04 Genset in permanent parallel with mains
05 Mains power greater than genset power
06 Switching with cut
07 Parallel power >70%
13 D 40014
08 Starting due to mains failure
09 External starting signal activated
10 Mains failure due to low voltage
11 Mains failure due to maximum voltage
12 Mains failure due to phase imbalance
13 Mains failure due to micro-cuts
14 Mains available
15 Mains in service
ADDRESS
BIT Status (ST3)
DEC. HEX. HR
00 Start of the engine start cycle
01 Rest cycle
02 Heating cycle
03 Activated motor contact
04 Starter motor activated
05 Configuration saved
06 Alarm reset
07 Fuel filling activated
14 E 40015
08 Start order for weekly maintenance
09 Start order for monthly maintenance
10 Blocking of genset start. Daily
11 Blocking of genset start. Weekly
12 Parallel power limitation activated
13 Automatic start lock activated
14 Mains breaker locked (Opening forced)
15 Genset breaker locked (Opening forced)
ADDRESS
BIT Status (ST4)
DEC. HEX. HR
00 Correct genset frequency
01 Priority key locked
02 Wait for all started gensets
03 Continuous excitation activated – K99
04 Alternate excitation activated - K100
05 Open/Close the switch – SCR
06 Parallel gensets manual start (This Genset)
07 Parallel gensets manual start (Some Genset)
15 F 40016
08 Without permission to close mains breaker
09 Without permission to close genset breaker
10 Start order gensets in parallel
11 Gensets running in parallel
12 Manual voltage control activated
13 Manual frequency control activated
14 Circuit breaker maneuver is frozen
15 Power level lock activated
STATUS
Electra Molins S.A MODBUS_MP15 A.C72-M4-V65
9 / 13
ADDRESS
BIT Status (ST5)
DEC. HEX. HR
00
01
02
03
04
05
06
07
38 26 40039
08 Peak shaving activated
09
10 Non-priority genset activated. SP
11
12
13
14
15
WORD EXECUTION
Electra Molins S.A MODBUS_MP15 A.C72-M4-V65
10 / 13
ADDRESS
BIT Result of the Bit Formulas (RBF)
DEC. HEX. HR
00 RESULT FORMULA 09
01 RESULT FORMULA 10
02 RESULT FORMULA 11
03 RESULT FORMULA 12
04 RESULT FORMULA 13
05 RESULT FORMULA 14
06 RESULT FORMULA 15
07 RESULT FORMULA 16
11 B 40012
08 RESULT FORMULA 01
09 RESULT FORMULA 02
10 RESULT FORMULA 03
11 RESULT FORMULA 04
12 RESULT FORMULA 05
13 RESULT FORMULA 06
14 RESULT FORMULA 07
15 RESULT FORMULA 08
ADDRESS
BIT Output Relays (OR1)
DEC. HEX. HR
00 K1 - Electric interlocking lock
01 K2 - Opening output circuit breaker
02 K3 - Starting motor
03 K4 - Motor contact
04 K5 - Opening mains breaker
05 K6 - Opening genset breaker
06 K7 - Close mains breaker
07 K8 - Close genset breaker
41 29 40042
08 K9 - Not available for automatic service
09 K10 - Fuel level alarm
10 K11 - Continuous excitation - K99
11 K12 - Alternate excitation - K100
12 K13 - Ground neutral opening
13 K14 - Boiler temperature control
14 K15 - Grouping shutdown alarms
15 K16 -Grouping preventive alarms
ADDRESS
BIT Input Optocouplers (IO1)
DEC. HEX. HR
00 IN_17 - Emergency stop
01 IN_18 - Remote signal
02 IN_19 - Coolant level stop alarm
03 IN_20 – Output circuit breaker
04
05
06
07
46 2E 40047
08
09
10
11
12
13
14
15
ADDRESS
BIT Input Optocouplers (IO2)
DEC. HEX. HR
00 IN_01 – Mains circuit breaker
01 IN_02 – Genset circuit breaker
02 IN_03 - Switching (With/Without) Cut
03 IN_04 - Busbar voltage
04 IN_05 – Mains breaker intensity
05 IN_06 – Genset breaker intensity
06 IN_07 - Mains breaker locked (Opening forced)
07 IN_08 - Genset breaker locked (Opening forced)
47 2F 40048
08 IN_09 – Excitation of the alternator
09 IN_10 - Motor contact in test mode (VOLVO)
10 IN_11 - Earth leakage
11 IN_12 - Ground neutral breaker
12 IN_13 – Operation in test mode
13 IN_14 - Battery charging alternator
14 IN_15 - Electronic battery charger
15 IN_16 - Starting motor in test mode (VOLVO)