This mechanical technical schedule provides specifications for piping, ductwork, and air ducts including:
1) Refrigeration pipes will be copper and condensate pipes will be uPVC.
2) Kitchen, fire rated pressure, and toilet/fresh air ducts will be galvanized iron and meet various thickness and jointing standards.
3) The schedule provides manufacturers, materials, standards, and other details for refrigeration, condensate, kitchen, fire rated pressure, and toilet/fresh air ducts.
Original Description:
Original Title
H9BC -Technical Schedule - Mechanical_2020.07.24_Thickness air duct
This mechanical technical schedule provides specifications for piping, ductwork, and air ducts including:
1) Refrigeration pipes will be copper and condensate pipes will be uPVC.
2) Kitchen, fire rated pressure, and toilet/fresh air ducts will be galvanized iron and meet various thickness and jointing standards.
3) The schedule provides manufacturers, materials, standards, and other details for refrigeration, condensate, kitchen, fire rated pressure, and toilet/fresh air ducts.
This mechanical technical schedule provides specifications for piping, ductwork, and air ducts including:
1) Refrigeration pipes will be copper and condensate pipes will be uPVC.
2) Kitchen, fire rated pressure, and toilet/fresh air ducts will be galvanized iron and meet various thickness and jointing standards.
3) The schedule provides manufacturers, materials, standards, and other details for refrigeration, condensate, kitchen, fire rated pressure, and toilet/fresh air ducts.
BẢNG THÔNG SỐ KỸ THUẬT PHẦN CƠ KHÍ H9BC PIPING & DUCTWORK SPEC DIVISION REFER: M-104 REV: 01 REFRIGERATION PIPE CONDENSATE PIPE Manufacturers ref UBZ, Hailiang De Nhat, Tien Phong, Dong Nai Location - Under & Above ground Material Copper uPVC Standard ASTM B280 BSEN1329-1:2000/ BS4514:2001 Pressure / Thickness ASTM B280 ≥ PN10 Jointing method Flared joints or brazed joints Glue KITCHEN AIR DUCT FIRE RATED, PRESSURE AIR DUCT TOILET, FRESH AIR - AIR DUCT Manufacturers ref Hoa Sen, Phuong Nam, Viet Nhat Hoa Sen, Phuong Nam, Viet Nhat Hoa Sen, Phuong Nam, Viet Nhat Location - - - Material GI (not insulation) GI GI Standard Z27(275g/m2 both size) Z27(275g/m2 both size) Z27(275g/m2 both size) - Apartment kitchen exhausted duct: GI Pressure / Thickness 0.8mm Duct: GI 1.2mm Duct: minimum GI 0.48mm - Retail kitchen exhuasted duct: GI 1.2mm Jointing method Base on SMACNA Base on SMACNA Base on SMACNA NOTES: