Choice of the Type of Foundation

The choice of the appropriate type of foundation is governed by some important factors such as

1. The nature of the structure


2. The loads exerted by the structure
3. The subsoil characteristics
4. The allotted cost of foundations
Therefore to decide about the type of foundation, subsoil exploration must be carried out. Then the soil characteristics within the
affected zone below the building should be carefully evaluated. The allowable bearing capacity of the affected soil strata should
then be estimated.

After this study, one could then decide whether shallow foundations or deep foundations should be used.

Shallow foundations, such as footings and rafts, cost less and easier to execute. They could be used if the following two conditions
are fulfilled;

1. The superimposed stress (Dp) caused by the building lies within the allowable bearing capacity diagram of different
soil strata as shown in Fig.1.
This condition is fulfilled when , in Fig.1, is smaller than and smaller than and smaller than and smaller than and so on.
2. The building could withstand the expected settlement estimated for that type of foundation
If one or both of these two conditions cannot be fulfilled the use of deep foundations should be considered.

Deep foundations are used when top layers of the soil are soft and there exists a good bearing stratum at a reasonable depth. Soil
strata lying beneath the bearing stratum should be of ample strength to resist the superimposed stresses (Dp) due to the loads
transmitted to the bearing stratum, as shown in Fig.2.
Deep foundations are usually piles or piers which transmits the load of the building to the good bearing stratum. They usually cost
more and require well trained engineers to execute.
If the explored soil layers are soft for considerable depth and no bearing stratum is found at a reasonable depth, floating
foundations could be used.

To build a floating foundation, a mass of soil, approximately equal to the weight of the proposed building, is to be removed and
replaced by the building. In this case, the bearing stress under the building will be equal to the weight of the removed earth (γD)
which is less than

(qa = γD +2C)

and Dp will be equal to zero. This means that the bearing capacity under the building is less than ( qa ) and the expected settlement
equals theoretically to zero.

Finally, the engineer should prepare an estimate of the cost of the most promising type of foundation which represents the most
acceptable compromise between performance and cost.

Shallow Foundations
Shallow foundations are those executed near the ground surface or at shallow depths. As mentioned before in the previous
chapter, shallow foundations are used when subsoil exploration proves that all soil strata affected by the building could resist the
superimposed stresses (Dp) without causing excessive settlements.

Shallow foundations are either footings or rafts.

Footings
Footing foundation is one of the oldest and most popular type of shallow foundations. A footing is an enlargement of the base of a
column or wall for the purpose of distributing the load on the supporting soil at a pressure suiting its properties.

Types of Footings
There are different types of footings to suit the nature of the structure. Footings could be classified into three main classes

Wall or Strip footing


It runs underneath the wall by its full length as shown in Fig.3. it is usually used in the bearing wall type structures.
Isolated column footing
It acts as a base for a column. It is usually used for reinforced concrete Skelton type of buildings. It can take any shape such as
square, rectangular or circular as shown in Fig.4.

Fig.4 Typical spread footings

Combined Column Footing


It is a combined base for an exterior and interior columns of a building, Fig.5. It is also used when two adjacent columns of a
building are close to each other that their footings overlap
Distribution of stresses under footings
The distribution of stresses under footings is considered linear although it is not the case in reality, The error involved in this
assumption is small and could be overlooked.

Load Compilations
Loads affecting the usual types of buildings are:

1. Dead Load (D.L)


2. Live Load (L.L)
3. Wind Load (W.L)
4. Earthquake Load (E.L)

Dead Load
The full dead load acting on the elements of the structures should be considered in the design.

Live Load

It is not probable that the full intensity of the live load will be acting at the same time on all the floors of a multi-storey building.
Consequently, the codes of practice allow a certain reduction in the intensity of live load. According to the Egyptian Code of
practice the following reduction in live load is allowed:

No. of floors Reduction in live load %


Ground floor zero %

1st floor zero %

2nd floor 10.0 %

3rd floor 20.0 %

4th floor 30.0 %

5th floor and above 40.0 %

The live load should not be reduced for ware houses and public buildings such as schools, cinemas, and hospitals.

Wind and Earthquake Loads


When the buildings are high and narrow the wind pressure and the earthquake load must be taken into consideration.

Assumption used in the Design of Spread Footings


Theory of elasticity analysis indicates that the stress distribution beneath footings, symmetrically loaded, is not uniform. The actual
stress distribution depends on the type of material beneath the footing and the rigidity of the footing. For footings on loose
cohesion-less material, the soil grains tend to displace laterally at the edges from under the load, whereas in the center the soil is
relatively confined. This results in a pressure diagram somewhat as indicated in Fig.6. For the general case of rigid footings on
cohesive and cohesion-less materials, Fig.6 indicates the probable theoretical pressure distribution. The high edge pressure may
be explained by considering that edge shear must take place before settlement can take place.

Because the pressure intensities beneath the footing depend on the rigidity of the footing, the soil type and the condition of the soil,
the problem is generally indeterminate. It is common practice to use a linear pressure distribution beneath the footings and this
procedure will be followed in this text. In any case little difference in design results by using a linear pressure distribution
Allowable Bearing Stresses under Footings
The factor of safety in the calculating of the allowable bearing capacity under the footing should not be less than 3 if the loads
considered in the design is equal to the dead load + the reduced live load. The factor of safety should not be less than 2 when the
severest condition of loading is considered, which is, dead load + full live load + wind load or earthquake loads.

The loads of the superstructure are usually calculated at ground level. If the net allowable bearing pressure is given, it should be
reduced by the volume of concrete below ground surface per unit area of the footing multiplied by the difference between the unit
weight of concrete and soil. If we assume equal to the average density of soil and concrete Fig.7, then should be reduced by

Structural design of spread footings


For spread footing the following items should be considered

1-Shear
Shear stresses ate usually control the depth of spread footings. The critical section for wide beam shear is shown in Fig.8-a. It is at
a distance d from the column or wall face. The values of the shear stresses are given in table 1.The critical section for punching
shear (Two-way diagonal shear) is shown in Fig.8-b. It is at distance of d/2 from the face of the column. This assumption is
according to the American Concrete Institute (A.CI) Code.
Table(1): allowable stresses in concrete and reinforcement:-

Types of stresses symbol Allowable stresses in kg/cm 2


Cube strength fcu 180 200 250 300
Axial comp. fco 45 50 60 70
Simple bending and eccentric fc 70 80 95 105
forces with big eccentricity
Shear stresses
Slabs and footings without reinf. q1 7 8 9 9
Other members q1 5 6 7 7
Members with reinforcement q2 15 17 19 21
Punching shear qcp 7 8 9 10
Reinforcement
Mild steel 240/350 1400 1400 1400 1400
Steel 280/450 fs 1600 1600 1600 1600
Steel 360/520 2000 2000 2000 2000
Steel 400/600 2200 2200 2200 2200
Punching shear will generally control the depth of the spread footings. From principles of statics Fig.8-b , the force on the critical
section for shear is equal to the force on the footing beyond the shear section caused by the net soil pressure fn.

where qp = allowable punching shear stress


= 8 kg/cm2 (for cube strength =160)

fn = net soil pressure

b = Side of column

d =depth of punching shear

It can be assumed that the critical section for punching shear is at the column face and in this case the allowable punching shear
stress can be taken as 10.0 kg/cm2 (for cube strength = 160).

The footing is usually designed to ensure that the depth is great enough to resist the shear by concrete with out web
reinforcement..

2- Bond

Bond stress is computed as

where the shear force Q is taken at the same critical section for bending moment, or where changes in concrete cross section or
steel reinforcement occur. For footings of constant section, the section for bond is at the face of column or wall. The reinforcing bar
should have enough length dd , Fig.9 to avoid the pull-out (bond failure) or a splitting of the concrete. The value of dd is computed
as follows:
For the first computation take
fs equal to allowable working stress. If the calculated dd is larger than the available dd then
recalculate d by taking
d fs equal to the actual steel stress.
The allowable values of bond stress qb are as follows

3- Bending moment

The critical sections for bending moment are determined from Fig.10 as follows:
For concrete wall and column, this section is taken at the face of the wall or the column Fig.10-a.

For masonry wall this section is taken halfway between middle and the edge of the wall Fig.10-b.

For steel column, this section is located half way between the edge of base plate and the face of the column Fig.(10-c).

The depth required to resist bending moment is

4- Bearing on top of footing


When a reinforced concrete column transmits its load to the footing, the steel of the column, which is carrying a portion of the load,
cannot be terminated on top of footing since this may overstress the concrete in column contact area. Therefore it is necessary to
transmit the portion of load carried by the column steel by bond stress into the footing by either extending the column steel or by
dowels. From Fig.11:

where
fs is the actual steel stress
5- Plain Concrete Footing Beneath R.C. Footing
It is common practice to place a plain concrete layer beneath the reinforced concrete footing. This layer is about 20 cm. to 40 cm.
The projection C of the plain concrete layer depends on its thickness t. Referring to Fig.12 , the maximum bending moment per unit
length at section a-a is given by

Where fn = the net soil pressure.


The maximum tensile stress at the bottom of section a-a is:

DESIGN OF R.C. WALL FOOTING:


The wall footing is a strip of reinforced concrete wider than the wall. Fig.13 shows the different types of wall footings. The type
shown in Fig.13-a is used for footings carry light loads and placed on uniform soil of good bearing capacity. The type shown in
Fig.13-b is used when the soil under the footing is not uniform and of different bearing capacities. The type shown in Figs.13-c and
13-d is used for heavy loadings.
Design Procedure:

Consider 1.0 meter length of the wall.

1. Find P at ground level.

2. Find if is given then it is reduced by or compute PT .

3. Compute the area of footing


If the bond stress is not safe, we either increase by using steel bars with smaller diameter, or increase ∑ O the depth
d. Bending up the steel reinforcement at the edges of the footing helps in resisting bond stresses. The diameter of the
main steel reinforcement should not be less than 12 mm. To prevent cracking due to uneven settlement below the wall
itself, additional reinforcement is used as shown in Fig.13-c and d. It is taken as 1.0% of the concrete cross section under
the wall and distributed equally at top and bottom.
19. Check the anchorage bond

Design of Single Column Footing


The single column footings are usually square in plan, Rectangular footings are used if there restriction in one direction or If the
supported columns are of too elongated .rectangular cross section. In the simplest form, they consist of a single slab FIg.15-a.
Fig.15-b shows a pedestaled column footing, the pedestal provides depth for a more favorable transfer of load and in many cases
is

required in order to provide the necessary length for dowels. Sloped footings such as those in Fig.15-c

Design Procedure for Square Column Footing


American Codes of Practice is equal to the moment about the critical section y-y of the net stress acting on the hatched .area abcd
Fig. 16-a. According to the Continental Codes of practiceMmax. is equal to either; the moment of the net stresses acting on the
hatched area abgh, shown in Fig.16-b, about the critical section y-y or 0.85 the moment of the net stresses acting on the area abcd
in Fig.16-a about y-y.

8. Determine the depth required to resist punching dp.

9. Calculate dm, the depth to resist

b = B, the side of the footing according to the American Codes of Practice


b = (bc + 20) cm where bc is the side of the column according to the Continental Codes of Practice.

It should be noted that dm computed by continental method is larger than that compute by American code. The larger depth will
decrease the amount of steel reinforcement and usually satisfies the depth required for punching. American code gives smaller dm
with higher value of steel reinforcement but by using high tensile, steel, the area of the steel reinforcement can be reduced. In this
text, the bending moment will be calculated according to the American Code while b is taken either equal to bc + 20 when the
ordinary steel is used or equal to B when high tensile steel is used.

The footing depth d may be taken any value between the two values computed by the two above methods. It should be mentioned
that, for the same bending moment, a large depth will require smaller area of reinforcement steel which may not satisfy the
minimum percentage of steel . Also a small depth will require a large area of steel especially when using ordinary mild steel.

10. Choose the greater of dm or dp

11. Check dd, depth of column dowel.

Design Procedure for Rectangular Footing

The procedure is the same as square footing. The depth is usually controlled by punching shear except If the ratio of length to width
is large, the wide beam shear may control the depth. The critical sections for shear are at distance d from both sides of the column
Fig.17-a. The bending moment is calculated for both directions, about 1-1 axis and about b-b axis as shown in Fig.17.b and c.
The reinforcement in the long direction (Side L) is calculated from the bending moment , and is uniformly distributed over the width
B. The reinforcement in the short direction (Side B) is calculated from the bending moment . In locating the bars in the short
M11
direction one has to consider that the support provided to the footing by the column is concentrated near the middle, consequently
the area of footing adjacent to the column is more effective in resisting bending. For this reason an adjustment of steel in the short
direction is made. This adjustment place a percentage of the steel in a zone centered on the column with a width equal to the length
of the short direction of the footing. The remainder of the reinforcement shall be uniformly distributed in two end zones, Fig.18.
According to the American Concrete Institute, the percentage of steel in the central zone is given by:

where S = ratio of long side to short side, L/B .


SEMELLES

Single footings should be tied together by beams known as semelles as shown in Fig.19.a. Their function is to carry the ground
floor walls and transfer their loads to the footings. Semelles can prevent relative settlement if they are of very stiff section and
heavily reinforced.

The semelle is designed as continuous reinforced concrete rectangular beam carrying the weight of the wall. The width of the
semelle is equal to the width of the wall plus 5 cm and it should not be less than 25 cm. It should resist the shearing forces and
bending moments to which it is subjected, semelles must

be reinforced at top and bottom to counteract the differential settlements. by the equal reinforcement As.

The top level of the semelle should be 20 cm below the level of the platform surrounding the building. If the level of the ground floor
is higher than that of the platform, the level of the inner semmelle can be taken 20 cm below the ground floor level
Footings subjected to Moment
Introduction

Many foundations resist, in addition to the concentric vertical load, a moment about one or both axis of the footing. The
moment may result from a load applied off the centre of the footing . Examples of foundations that must resist moment are those for
retaining walls, abutments , bridge piers, and the columns of the foundations of tall buildings where wind pressure causes
appreciable bending moments at the base of columns.

The soil-pressure resultant under eccentrically loaded footing is assumed to coincide with the axial load P, but not with the
centroid of the footing, which results in a linear non-uniform pressure distribution. The maximum pressure must not exceed the
maximum allowable pressure on the soil. Tilting of the footing due to the higher intensity of soil pressure at the toe is possible to
occur . This can be reduced by using a large safety factor when computing the allowable soil pressure. Chapter 1, Section
"Footings with Eccentric or Inclined Loads" provide for a reduction in allowable soil pressure for eccentrically loaded footings.

Footings with Moments or Eccentricity about One Axis


where P = vertical load or resultant force

e = eccentricity of vertical load or resultant force

q = intensity of soil pressure (+ = compression)

and should not be greater than the allowable

soil pressure qa
c-The Load P is Outside Middle

When the load P is outside the middle third, that is e > L/6, Eq.7 indicates that tension will occur under the footing. However, no
tension can develop between the soil and the footing, thus the tension stresses are neglected, and the area of the footing which is
in tension is not considered effective in carrying load. Therefore the pressure diagram on the soil should be always in
compression as shown in Fig.21-.c. For the eccentricity e > L/6 with respect to one axis only, one can drive equations for the
maximum soil pressure q1 by finding a compressive pressure diagram whose resultant should be equal and on the same line of
action of load P. This diagram will take the shape of triangle whose side = q1 and base =

Footings with Moments or Eccentricity about both Axis

For footings with moments or eccentricity about both axis Fig 22, the pressure may be computed by the following equation
a- The Neutral Axis Outside the Base :

If the neutral axis is outside the base, then all the pressure q is in compression and equation (9) is valid. The location of the
maximum and minimum pressures on soil may be determined readly by observing the directions of the moments. The maximum
pressure q1 is at point (1)

Fig.22-a and the minimum pressure q2 is at point (3). The pressure q1 and q2 are determined from Eq.(9).

b- The Neutral Axis Cuts the Base

If the neutral axis cuts the base, then a certain area of the base is subjected to tension Fig.22. As the soil is not likely to grip the
footing to hold it in place , therefore the diagram shown in Fig.22-b and Eq.(9) cannot be used. The computation of the maximum
pressure on soil must be based on the area actually in compression. The compressive diagram is to be found in such a way that its
resultant should be equal and on the same line of action of the force P. The simplest way to get this diagram is by trial and error as
follows:
1- Find soil pressure at all corners by applying Eq.(9).

2- Determine the position of the neutral axis N-A (the line of zero pressure). This is not a straight line, but for the problem it is
assumed to be . Therefore it is only necessary to find two points, one on each adjacent side of the footing.

3- Select another neutral axis (N'-A') parallel to (N-A) but somewhat closer to the location of the resultant load P acting on the
footing.

4- Compute the moment of inertia of the area in compression with respect to the N'-A' . The simplest procedure is to draw the
footing to scale and divide the area into rectangles and triangles

4.4 STRUCTURAL DESIGN OF FOOTINGS SUBJECTED TO MOMENT

The principle problem in the design of eccentrically loaded footings is the determination of the pressures distribution under the
footings. Once they have been determined, the design procedure will be similar to the concentrically loaded footings, the critical
sections are selected and computations of the stresses due to moment and shear are made.

Where the bending moments on a column come from any direction, for example from wind loads, a square footing-; is preferable
unless the space restrictions dictate the choice of rectangular footing. If the bending moments always act in the same direction, as
in columns supporting rigid framed structures, the footing can be lengthed in the direction of the eccentricity

The dimensions of the footing B and L are proportioned in such a way that the maximum pressure at the toe does not exceed the
allowable soil pressure .

If a column carries a permanent bending moment, for example a bracket carrying a sustained load, it may be advantage to place
the column off centre on the footing so that the eccentricity of the resultant loading is zero In this case the distribution of the
pressure on the base will be uniform. The long toe section of the footing should be designed as a cantilever about a section
through the face of the column, Calculation of the depth to resist punching shear and wide beam shear is the same as in footings
support concentric loads

Since the bending moment at the base of the column is likely to be large for this type of footing, the column reinforcement should be
properly tied into the footing., Reinforcement details for this type of footings are shown in Fig.24.

For square footing it is generally most convenient to keep bar diameter and spacing the same in both directions in order to avoid
confusion in steel fixing.
Combined Footings

Introduction

The preceding section presented elements of the design of spread and wall footings. This section considers some of the more
complicated shallow-foundation problems. Among these are footings supporting more than one column in a line (combined footings),
which may be rectangular or trapezoidal in shape, or two pads connected by a beam, as for a strap footing. Eccentrically loaded
footings and un-symmetrically shaped footings will also be considered.

Rectangular Combined Footings

When property lines, equipment locations, column spacing, or other considerations limit the footing clearance at the column locations,
a possible solution is the use of a rectangular-shaped footing. This type of footing may support two columns, as illustrated in Fig.25
and 26, or more than two columns with only slight modification of the design procedure. These footings are commonly designed by
assuming a linear stress distribution on the bottom of the footing, and if the resultant of the soil pressure coincides with the resultant of
the loads (and center of gravity of the footing), the soil pressure is assumed to be uniformly distributed, The linear pressure
distribution implies a rigid footing on a homogeneous soil. The actual footing is generally not rigid, nor is the pressure uniform
beneath it, but it has been found that solutions using this concept are adequate. This concept also results in a rather conservative
design.
The design of a rigid rectangular footing consists in determining the location of the center of gravity (cg) of the column loads and using
length and width dimensions such that the centroid of the footing and the center of gravity of the column loads coincide. With the
dimensions of the footing established, a shear

and moment diagram can be prepared, the depth selected for shear (again it is conventional to make the depth adequate for shear
without using shear reinforcement to satisfy rigidity requirements implicitly), and reinforcing steel selected for bending requirements.
Critical sections for shear, both diagonal-tension and wide-beam, should be taken as indicated in the previous section. The maximum
positive and negative moments are used to design the reinforcing steel and will result in steel in both bottom and top of the beam.

In the short direction, obviously, the entire length is not going to be effective in resisting bending. That zone closest to the column will
be most effective for bending, and it is recommended that this approach be used. This is basically what the ACI Code specifies in
Art. 15.4.4 for rectangular footings

If it is accepted that the zone which includes the columns is most effective, what should this zone width be? Certainly, it should be
something greater than the width of the column. Probably it should be no greater than the column width plus d to 1.5d, depending on
the column location based on the author's analytical work, lack of Code guidance, and recognizing that extra steel will "stiffen" the
zone and increase the moments in this zone and reduce the moment out of the zone. An effective width using this method is illustrated
in Fig.27 For the remainder of the footing in the short direction, the ACI Code requirement for minimum-percentage steel (Art. 10.5 or
7.13) should be used.
In selecting dimensions for the combined footing, the length dimension is somewhat critical if it is desired to have shear and moment
diagrams mathematically close as an error check. This means that unless the length is exactly the computed value from the location of
the cg of the columns, an eccentricity will be introduced into the footing, resulting in a nonlinear earth-pressure diagram. The actual
as-built length, however, should be rounded to a practical length, say, to the nearest 0.25 or 0.5 ft (7.5 to 15 cm).

The column loads may be taken as concentrated loads for computing shear and moment diagrams. For design the shear and
moment .values at the edge (face) of the column should be used. The resulting error, using this approach, is negligible.Fig.(28)
If the footing is loaded by more than two columns, the problem is still statically determinate; the reactions (column loads) are known as
well as the distributed loading, i.e. the soil pressure.

Design Procedure of rectangular combined footing:-

Referring to Fig.29, the steps of the design can be summarized as follows :

1- Find the line of application of the resultant R. This fix L/2 since y is known and limited. It should be indicated that unless the
length L is exactly the computed value, an eccentricity will be introduced into the footing, resulting in a nonlinear soil pressure
diagram. The actual as-built length, however, should be rounded to a practical length, say, to the nearest 5 cm or 10cm.

maximum +ve moment at point K where the shearing force = zero


6- Determine the depth for shear. It is conventional to make the depth adequate for shear without using shear reinforcement. The
critical section for shear is at distance d from the face of column having maximum shear, Fig.30

7-Determine the depth for punching shear for both columns. According to ACI the critical section it at d/2 from column face.
Fig.30.

9-d is chosen the greatest of

t = d + 5 to 8 cm.

11- Check the bond stresses and anchorage length d.

12- Short direction :

The column loads are distributed crosswise by transverse beams (hidden), one under each column. The length of the beams
are equal to the width of the footing B. The effective width of the transverse beam may be taken the least of the following:

a- Column width a + 2 d or column width a + d + the projection of the footing beyond the column y, Fig.31.

b- The width of the footing

It should be noted that ACI code consider that the effective width of the transverse beam equal to column width a + d or
column width a + d/2 + y The Transverse bending moment MT1 at column (1) is equal to

The transverse reinforcement should be distributed over the effective width of the transverse beam. For the remainder
of the footing, minimum percentage steel should be used. The bond stresses and anchorage length dd, should be
checked.
Combined trapezoidal footing:-
Combined trapezoidal footing for two columns as used when column carries the largest load is near the property line where the
projection is limited or when there is restriction on the total length of the footing. Referring to Fig.32 ,

The position of the resultant of columns loads R locates the position of the centriod of the trapezoid. The length L is determined and
the area A is computed from:

The design procedure is the same as rectangular combined footing except that the shear diagram will be a second degree curve and
bending moment is a third degree curve.
Design of Strap or Cantilever Footings

A strap footing may be used where the distance between columns is so great that a combined or trapezoid footing becomes quite
narrow, with resulting high bending moments, or where as in previous section.

A strap footing consists in two column footings connected by a member termed a strap, beam, or cantilever which transmits the
moment from the exterior footing. Fig.33 illustrates a strap footing. Since the strap is designed for

moment, either it should be formed out of contact with the soil or the soil should be loosened for several inches beneath the strap
so that the strap has no soil pressure acting on it. For simplicity of analysis, if the strap is. not very long, the, weight of the strap may
be neglected.

In designing a strap footing, it is first necessary to proportion the footings. This is done by assuming a uniform soil pressure
beneath the footings; that is, R1 and R2 (Fig.33) act at the centroid of the footings.
The strap must be a massive member for this solution to be valid. The development of Eq.1 implies rigid body rotation; thus, if the
strap is not able to transmit the eccentric moment from column 1 without rotation, the solution is not valid. To avoid exterior footing
rotation it is recommended to be .

Istrap/Ifooting > 2

It is desirable to proportion both footings so that B and q are as nearly equal as possible to control differential settlements.

Design Procedure for Strap Footing

reaction under the interior footing will be decreased by the same value, referring to Fig.33

1- The design begins with trial value of e

6- Check that the centroid of the areas of the two footings coincide with the resultant of column loads.

7- Calculate the moments and shear at various parts of the strap footing.

8- Design of the strap


The strap represents a single-span beam loaded upward by the loads transferred to it by the two footings and supported by
downward reactions at the centre lines of the two columns. Thus the upward load over the length L is equal to R1/L t/m'. The
location of the maximum moment is obtained by equating the shear force to zero. The moment decreases toward the
interior column and is zero at the center line of that column. Hence half the strap reinforcement is discontinued where no
longer needed and the other half is continued through the interior column. Check shear stresses and use stirrups, and bent
bars if necessary.

9- Design of the exterior footing

The exterior footing acts exactly like a wall footing of a length equal to L. Even though the column is located at the edge the
balancing action of the strap is such as to transmit the reaction R1 uniformly over the length L1 thus resulting in the desired
uniform soil pressure. The design is carried out exactly as for a wall footing.

10- Design of the interior footing

The interior footing may be designed as a simple single column footing. The main difference is that the punching shear
should be checked along the perimeter fghj, Fig.33.

RAFT FOUNDATIONS

Introduction

The raft foundation is continuous footing that cover the entire area beneath a structure and supports all the walls and columns. The
term mat is also used for foundation of this type. It is used generally on soil of low bearing capacity and where the area covered by
spread footings is more than half the area covered by the structure. Raft foundation is also used where the soil mass contains
compressible lenses or the soil is sufficiently erratic so that differential settlement would be difficult to control. The raft tends to
bridge over erratic deposits and reduces the differential settlement.

Bearing Capacity of Rafts on Sand


Beating capacity of foundations on sand increases as the width increases. Owing to the big width of raft compared to the width of
an ordinary footing, the allowable bearing capacity under the raft will be much greater than that of the footing.

It was noticed in practice that using an allowable bearing capacity under the raft equal to twice the allowable bearing capacity
determined for an ordinary footing. resting on the same sand will give a reasonable and acceptable amount of settlement.

If the water table lies at a depth equal to or greater than B, the width of the raft, the allowable bearing capacity, determined for dry
condition, should not be reduced. If there is a possibility that the water table rises up till it floods the site, the allowable bearing
capacity should be reduced by 50%. If the water table is at a depth intermediate between B and the base of the raft, an appropriate
reduction between zero and 50% should be made.

Bearing Capacity of Rafts on Clay.

In clays, the bearing capacity is not affected with the width of the foundation Therefore, the bearing capacity under a raft will be the
same as that under an ordinary footing.

If the estimated differential settlement under the raft is more than tolerable or if the weight of the building divided by its area gives a
bearing stress greater than the allowable bearing capacity, floating or partially floating foundation should be considered.

To execute a floating foundation, excavation is to be carried out till a depth D is reached where the weight of the excavated soil
equals to the weight of the structure, figure 2. In this case, the excess superimposed stress Δp at foundation level equals to zero
and consequently, the building will suffer no settlement.

If the full weight of the building =Q

and the weight of soil removed =Ws

and the excess load at foundation level =Qe

\Qe=QWs

In case of floating foundation ;

Q = Ws and therefore Qe = Zero

In case of partially floating foundation, Qe has a certain value which when divided by foundation area gives the allowable bearing
capacity of the soil ;

Design of Raft Foundations ;

Rafts may be designed as rigid structures (so called conventional analysis) whereby soil pressure acting against the raft slab is
assumed uniformly distributed and equal to the total weight of the building divided by the area of the raft. This is correct if the
columns are more or less equally loaded and equally spaced, but it is difficult to fulfill this requirement in practice so it is allowed
that the column loads and spacings to be varied within 20%. However if the downward loads on some areas are much heavier than
on others, it is advisable to divide the raft into different areas and design each area on its corresponding average pressure.
Continuity of the slab between such areas is commonly provided, although for the areas of great differences in pressure it is
advisable to construct vertical construction joint through the slab and the superstructure to allow for differential settlement.
In flexible raft foundation the design cannot be based only on the strength requirements but it is necessary to be subjected due to
the predicted settlement. The thickness and the amount of reinforcement of the raft should be selected in a such way to prevent
development of cracks in the slab. As the differential settlement is not considered in the structural design it is customary to
reinforce the raft with twice its theoretical amount of reinforcement. The quantity of the steel may be taken as 1% of the cross
sectional area divided at top and bottom. The thickness of the slab should not be greater than 0.01 of the radius of curvature. The
thickness may be .increased near columns to prevent shear failure.

There are two types of raft foundations:

1- Flat slab raft which is an inverted flat slab Fig.34-a. If the thickness of the slab is not enough to resist punching shear under
columns, pedestals may be .used above the slab Fig.34-.b or, below the .slab, by thickening the flat slab under the columns
as shown in Fig.34-c.

2- Slab and girder raft which, is. an inverted R.C. floor, composed of slabs and beams extending along column, rows in both
directions, Fig.34-d, it is also, termed ribbed mat. If a continuous floor is desired in the basement, the ribs (beams) may be
placed beneath the slab,Fig.34-e.

Design of Flat Slab Raft

The raft, which is of uniform thickness, is divided into column strips and middle strips as shown in Fig.35-a. The width of column
strip is equal to b + 2d, where b = column side. The depth of the raft d may assumed approximately equal to 1/10 the clear span
between columns. Also, the width of column strip may be taken equal to 3 b.

The column strips are design as continuous beams loaded with triangular loads as shown, in Fig.35-b. The net intensity of the
uniform upward pressure fn under any area, for example the area DEFG may be assumed equal to one fourth of the total loads on
the columns at D,E,F and G divided by the area DEFG.
The total loads acting upon the column strip BDEQ, Fig.35-a are assumed as triangular loading diagrams shown in Fig.35-b. The
total load on part DE, PDE, is assumed to be the net pressure acting upon the area DHEJ.

Design of Rigid Raft (Conventional Method)

The raft dimension is established and the resultant of all loads is found and the soil pressure is computed at various locations
beneath the base from Eq.

The raft is subdivided into a series of continuous strips (beams) centered on column rows as shown in Fig.37.
The shear and moment diagrams can be established, using either combined footing analysis or beam moment coefficient The
beam moment coefficients.The beam moment coefficient PI2 / 10 for long directions and PI2 / 8 for short directions may be
adopted. The negative and positive moments will be taken as equal. The depth is selected to satisfy shear requirements without
using stirrups and the tensile reinforcement is selected. The depth will usually be constant but the steel requirements may vary from
strip to strip. The perpendicular direction is analyzed similarly.

Design of Slab and Girder Raft (Ribbed Mat)

If the column loads and spacings are equal or vary within 20%, the net upward pressure fn acting against the raft is assumed to be
uniform and equal to Q/A.

where

Q = weight of building at ground level, and

A = area of raft (along the outside of the exterior columns).

If this pressure is greater than the net allowable soil pressure, the area of the raft should be increased to an area large enough to
reduce the uniform pressure to the net allowable value. This can be achieved by projecting the slab beyond the outside face of
exterior columns.

Referring to Fig. 38 , the various elements of the raft can be designed as follows:

Design of slab:

1-Design of transverse beams B1 and B2

The uniform distributed load/m' on


Let R1 and R2 be the central reaction of beams B1 and B2 on the central main beam B3 respectively. The end beams B1 carries
only part of the load carried by the beam B2 and hence the central reaction R1 is assumed to be equal to

KR2 where K is a factor based on comparative area, then

Also it is assumed that the sum of the central reactions from the transverse beams B1 and B2 is equals to the total loads from
central columns, thus

2R1+8R2 =2P1 + 2 P2 (2)

Solving Eqs. (1) and (2), R1 and R2 can be determined.

The bending moment and shearing force diagrams can be drawn as shown in Fig.39. The reactions R1 and R2 can be
determined by equating the sum of vertical forces to zero. The central section of the beams at positive bending moment can be
designed as T-beam as the slab is on the compression side. The sections of the beams below central beam B3 is to be designed
as rectangular section.

2- Design of central main beam B3

The loading, shearing force, and bending moment diagrams are shown in Fig.40-a. The section can be designed as T-beam.

3- Design of central main beam B4

The loading, shearing force, and bending moment diagrams are shown in Fig.40-b The section can be designed as T-beam