0-7803-6338-8/00/$10.00(~)2000IEEE 173
surge flashover of phase to earth and phase to line is different from conventional line. The
phase. The test results show many specific calculation of relay protection set value must
characteristics, which are different from the be based on the measurement of power
conventional line due to the decrease of frequency parameter. The measurement was
clearance of phase to phase. For example, performed in 7 Nov. 1999. Table 1 is the
switching surge flashover voltage to earth is measured results.
much influenced by the voltage and polarity of
the other phases. As compared with
conventional line, under the same clearance to
earth, the switching surge flashover voltage is
reduced 10%. Type of line Compact line Conventional
line
Positive sequence inductance 0 664 090
(m") L,
Zero sequence inductance 3 33 24
(m") Lo
Positive sequence 0 0207 0 032
capacitance (yF/km) C,
Zero sequence 0 00798 0 00892
capacitance(pFlkm) CO
Positive sequence resistance 0 0207 0 032
(Qkm)R,
Zero sequence resistance 0 143 03
(Qkm)%
----(F1)
C is the capacitance per unit length
From table 1 , the surge impedance can be
calculated (see table 2).
174
conventional line. Hence, the natural cycle by 5 times, single phase opening-
transmission power will be increased more closing-opening cycle 3 times.
than 30% by F2. Fangshan substation as power source,
switching no-load transmission line with
3. SWITCHING OPERATION TEST ON breaker 5041. The reactor is out of
COMPACT LINE operation. The switching operation is
closing, opening and closing-opening
From table 1, the positive sequence cycle 5 times separately, single phase
capacitance of compact line is larger than opening-closing-opening cycle 3 times.
conventional line, so Ferrite effect of compact Fangshan substation as power source,
line should be more serious than conventional switching no-load transmission line, the
line. In order to reduce the power frequency reactor is out of operation.
overvoltage of the line, a reactor is installed in Fangshan substation as power source,
Changping substation. A MOA (metal oxide switching no-load transmission line with
arrester) is installed on both sides of the line. breaker 5041, the reactor is put into
The rated voltage of MOA is 444kV. The operation. The switching operation is
circuit breakers on both sides of the line are closing, opening and closing-opening 5
SF6 breakers without closing resistor. times separately, single phase opening-
closing-opening 3 times.
The switching test was performed in 15
Nov. 1999. Four different switching operation The test results according to operation modes
modes are considered. The one-line diagram mentioned above are shown in table 3 and
of transmission line and related equipment is table 4.
shown in fig.2. Table 3. Test result switching in Changping
3tion
0
times.
Changping substation as power source,
switching no-load transmission line with
breaker 5013. The reactor is put into
operation. The switching operation is
U2
1.22
1.21
175
Table 4. Test results switching in Fangshan the line is energized
:ation
Phase to earth Phase to phase
2. IO
176
length of compact line exceeds hundreds The measurement is performed on 22 Nov.
kilometers. This is also beneficial to the 1999. The measuring point is selected at a
calculation of relay protection. point that is 15m away from transmission line.
An important problem is the rush current The distribution of audible noise at different
when the transmission line is energized. 10 frequencies is shown in fig.7. The noise level
times of energized current with high frequency under the transmission line is about 39.6 dB
is recorded in the test. However, it is (A). The audible noise level meets the
attenuated quickly and lasts only 2 power requirement of design and some standard. The
frequency period (see fig.3). measurement of radio interference is due to
The capacitance of compact line higher than the regulations of CISPR. The distribution of
conventional line is the major reason for big radio interference is shown in table 5 .
rush current. If closing resistor of circuit
breaker on both sides of transmission line, the
rush current could be small due to the
damping of resistor. The influence of rush
current to relay protection sensitivity should
be considered when the length of compact line
is somewhat long.
4. MEASUREMENT OF ELECTRIC
FIELD
"
The electric field under transmission line is a
very important performance. The measuring
region is selected at the mid-point of a span. Fig.7 Audible noise distribution at
The measuring points are 1 m above the differentfrequencies
ground along the vertical direction of the line.
The measured electric field distribution is
shown in figure 6.
Interference level
177
operation. [2] Yafang Liu, etc., Study of 500kV compact
transmission technology (CIGRk, 1998
The ROW of compact line can be greatly session).
reduced due to the shrink of high field region. [3] Zhangkui Zhang, etc,. Commissioning
report of Changping-Fangshan 500kV
7.REFERENCES compact transmission line (2000-3).
[4] Yichao Yuan, etc., Report of 500kV
[l] R.H.Behucke etc., 500kV compact line compact test line (1 997-3).
designs for the greater Bangkok area
(CIGRk, 1998 session).
178