MOMENT CONNECTION DESIGN

PROJECT : PROPOSED JORGE BUAN SUPERMARKET


LOCATION : ARAYAT, PAMPANGA
DESIGNED BY : BER

DESIGNATION : BEAM (B-1) TO COLUMN (C-1) CONNECTION : BUANF06

I. DESIGNED LOADS

MOMENT = -112.3 KN m
AXIAL (TENSION) = -11.24 KN
SHEAR = 32.16 KN

II. DESIGNED CRITERIA

Fy = 248 MPa
Fv = 144.80 MPa
PROPERTIES OF MEMBER 1 : COLUMN (BU 350x250x22x7.94)
Total depth, d1 = 350 mm k = 37.88 mm
bf1 = 250 mm k1 = 17.47 mm
tf1 = 22 mm T1 = 274.24 mm
tw1 = 7.94 mm Af = 5,500 mm²
Aw = 2,430 mm²

PROPERTIES OF MEMBER 2 : BEAM B-2 (BU 425x250x22x7.94)


Total depth, d2 = 425 mm k = 37.88 mm
bf2 = 250 mm k1 = 17.47 mm
tf2 = 22 mm T2 = 349.24 mm 0.625
tw2 = 7.94 mm Af = 5,500 mm²
Aw = 3,025 mm²
spacing of bolts = 90 mm
g = 90 mm bp = 250 mm

III. DETERMINED SIZE OF BOLTS

At = V / Fv = 111 mm²
Try 22 mm Ø bolt N= 0.3
Abolt = 380 mm² Therefore use 4 bolts

IV. ACTUAL SHEARING STRESS, fv


fv = 10.58 MPa

V. ACTUAL TENSILE STRESS, ft

Tt = T + M / d1 = 348.00 KN
ft = 228.87 MPa

VI. ALLOWABLE TENSILE STRESS, Ft

Ft = 380 - 1.8 fv = 360.96 MPa > 300 MPa


Therefore , Ft = 300.00 MPa > ft ; O.K. !!!