Power Circuit Breaker 242 KV Type PMI: Standard Features
Power Circuit Breaker 242 KV Type PMI: Standard Features
33-403B
242 kV Type PMI
Standard Features
• dead tank design
• ASME pressure vessel certification for unfired
pressure vessels
• two-cycle interrupting time
• One HMB-4 hydraulic spring operating mechanism
per phase
• single state-of-the-art puffer interrupter per phase
• three-tank construction
• exterior bushing current transformers
• exceeds ANSI standards
• porcelain or composite bushings meet or exceed all
applicable ANSI and NEMA design specifications
• continuous current ratings up to 5000A
The 242PMI power circuit breaker is shipped assembled. By extending the breaker legs, mounting the
breaker on the pad and adding the required quantity of SF6 gas, the breaker is ready for testing and service.
A
L
B
M
C D K N
O
E
U
J
I
H
G
V
R
Q
S
F
T
DIMENSION IN INCHES
A B C D E F G H I J K
198½ 111 97¾ 97¾ 85 44½ 125-5/8 179 189½ 204 23
DIMENSION IN INCHES
L M N O P Q R S T U V
150 108¼ 99¼ 84¾ 61½ 94½ 59½ 54½ 37-5/8 162 227¼
60 Hz BIL Chopped
Maximum Continuous Interrupting Freq. KV Wave kV Crest
Breaker kV, RMS A, RMS kA, RMS kV Crest 2m 3m
1200
40
2000
50 425 900
242PMI 242 3000 1160 1040
63 460* 1050*
4000
80
5000
* IEC performance option.
ABB Inc.
125 Theobold Avenue
Greensburg, PA 15601
Phone: (724) 838-5204
Fax: (724) 838-5299
www.abbhvsg.com December 2002