The document describes the safety interlock system for a gas processing system. It lists 15 fault conditions and specifies which systems will shutdown or send alarm messages in response to each fault. Most faults result in the shutdown of waste gas valves, fuel gas valves, and the circulation pump, as well as alarm messages. Some faults only trigger shutdowns after a cool down period or multiple restarts.
The document describes the safety interlock system for a gas processing system. It lists 15 fault conditions and specifies which systems will shutdown or send alarm messages in response to each fault. Most faults result in the shutdown of waste gas valves, fuel gas valves, and the circulation pump, as well as alarm messages. Some faults only trigger shutdowns after a cool down period or multiple restarts.
The document describes the safety interlock system for a gas processing system. It lists 15 fault conditions and specifies which systems will shutdown or send alarm messages in response to each fault. Most faults result in the shutdown of waste gas valves, fuel gas valves, and the circulation pump, as well as alarm messages. Some faults only trigger shutdowns after a cool down period or multiple restarts.
Shutdown Fault condition waste gas fuel gas circulation water valves* message message after valves valves pump* immediately 3 restarts Cabinet exhaust pressure low Y Y Y Natural gas leak Y Y Y Water in safety tank Y Y Y Y Y Water in drain pan Y Y Y Y Y EMO Y Y Y Y Y Flame sensor does not detect flame Y Y Y Cabinet door open Y Y Y Temperature Circulation tank to high Y Y Y Temperature Scrubber to high Y Y Y Temperature Waste gas nozzle to high Y Y Y Waste gas valve not in position reactor Y Y Fuel gas not stable Y Y Y Process exhaust pressure low Y Y Y Y Y Scrubbing water flow low Y Y Y High pressure waste gas inlet Y Y Y * Circulation Tank and water valves will be shut after 5 ~ 10 minutes cool down time, based on cool down time setting in PLC. ** Hardware Interlock with blue color