Mteq Io&m

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 44

EQ

MicroTrans
Signal Processor
Operation & Maintenance Manual
Engineered for accuracy, applicability,
durability and simplicity in HVAC air systems
and industrial process control loops
MicroTransEQ Operation & Maintenance Manual

TABLE OF CONTENTS
TABLE OF CONTENTS ............................................................................................................................. i 
1.  INTRODUCTION .............................................................................................................................. 1 
1.1.  DESCRIPTION ............................................................................................................................ 1 
1.2.  BASIC OPERATION .................................................................................................................. 1 
1.3.  SPECIFICATIONS ...................................................................................................................... 1 
1.3.1.  Power Supply ........................................................................................................................ 1 
1.3.2.  Power Consumption .............................................................................................................. 1 
1.3.3.  Accuracy ............................................................................................................................... 1 
1.3.4.  Temperature Input Options ................................................................................................... 1 
1.3.5.  Process Output Options......................................................................................................... 1 
1.3.6.  High/Low Alarm Relay Outputs ........................................................................................... 2 
1.4.  SAFETY ....................................................................................................................................... 2 
1.4.1.  Electrical Connections .......................................................................................................... 2 
1.4.2.  Static Electricity .................................................................................................................... 2 
2.  PRODUCT DIMENSIONS ................................................................................................................ 3 
2.1.  NEMA 1 MECHANICAL DIMENSIONS .................................................................................. 3 
2.2.  NEMA 4 MECHANICAL DIMENSIONS .................................................................................. 4 
3.  INSTALLATION ............................................................................................................................... 5 
3.1.  ELECTRICAL & PNEUMATIC INSTALLATION ................................................................... 5 
3.2.  TEMPERATURE TRANSMITTER CONNECTION ................................................................. 6 
3.2.1.  4-20mA Output/2-Wire Loop Powered Temperature Transmitter ....................................... 6 
3.2.2.  0-10VDC Output/24VAC Power 3-Wire Temperature Transmitter .................................... 6 
3.2.3.  0-10VDC Output/24VDC Power 3-Wire Temperature Transmitter .................................... 7 
3.2.4.  0-10VDC or 4-20mA from a Building Management System (BMS) ................................... 7 
4.  INPUT/OUTPUT SET-UP ................................................................................................................. 8 
4.1.  PROCESS OUTPUT .................................................................................................................... 8 
4.2.  TEMPERATURE INPUT (OPTION) .......................................................................................... 8 
5.  COMMON STARTUP CONFIGURATION CHANGES.................................................................. 9 
5.1.  AREA FACTOR .......................................................................................................................... 9 
5.2.  OPERATING RANGE .............................................................................................................. 10 
5.3.  TEMPERATURE COMPENSATION FOR AIR DENSITY .................................................... 11 
5.3.1.  Temperature Input Signal Selection.................................................................................... 11 
5.3.2.  Temperature Units .............................................................................................................. 11 
5.3.3.  Temperature Values ............................................................................................................ 11 
5.3.4.  Temperature Input ............................................................................................................... 13 
5.3.5.  Fixed Value ......................................................................................................................... 13 
6.  ACTIVE DISPLAYS & KEY FUNCTIONS ................................................................................... 14 
6.1.  POWER-UP INITIATION DISPLAY ....................................................................................... 14 
6.2.  PROCESS DISPLAY DESCRIPTIONS ................................................................................... 14 
6.3.  KEY FUNCTIONS .................................................................................................................... 15 
7.  DISPLAY MENUS ........................................................................................................................... 16 
7.1.  FIELD SETUP & TECH. CONFIGURATION MENUS .......................................................... 16 
8.  FIELD SETUP MENUS ................................................................................................................... 17 
8.1.  OPERATING RANGE .............................................................................................................. 17 
8.2.  ZERO PRESSURE CALIBRATION......................................................................................... 17 
8.3.  ENGINEERING UNITS ............................................................................................................ 18 
8.4.  LOCKDOWN............................................................................................................................. 18 
8.4.1.  Lockdown Value ................................................................................................................. 18 
Paragon Controls Incorporated i Revision Level 012
MicroTransEQ Operation & Maintenance Manual

8.4.2.  Lockdown Delay ................................................................................................................. 19 


8.5.  FLOW CORRECTION .............................................................................................................. 19 
8.5.1.  Flow Correction (K-Factor) ................................................................................................ 19 
8.5.2.  Flow Correction (K-Factor Calculator) .............................................................................. 19 
8.6.  AUTOZERO .............................................................................................................................. 20 
8.6.1.  AutoZero Status .................................................................................................................. 20 
8.6.2.  AutoZero Interval................................................................................................................ 20 
8.6.3.  AutoZero Test Interval ........................................................................................................ 21 
8.7.  TEMPERATURE COMPENSATION ...................................................................................... 21 
8.7.1.  Temperature Units .............................................................................................................. 21 
8.7.2.  Temperature Values ............................................................................................................ 22 
8.7.3.  Temperature Input ............................................................................................................... 23 
8.7.4.  Fixed Value ......................................................................................................................... 23 
8.8.  DISPLAY FILTER .................................................................................................................... 23 
8.9.  PROCESS OUTPUT FILTER ................................................................................................... 24 
8.10.  HIGH/LOW ALARM OPTIONS........................................................................................... 24 
8.10.1.  Alarm Status .................................................................................................................... 24 
8.10.2.  Alarm Values................................................................................................................... 25 
8.10.3.  Alarm Delay .................................................................................................................... 25 
8.11.  DP DISPLAY FORMAT ....................................................................................................... 25 
8.12.  FACTORY DEFAULTS ........................................................................................................ 26 
9.  TECH CONFIGURATION MENUS ............................................................................................... 27 
9.1.  AREA FACTOR ........................................................................................................................ 27 
9.2.  MINIMUM CALIBRATION ..................................................................................................... 28 
9.3.  50% CALIBRATION ................................................................................................................ 29 
9.4.  SPAN CALIBRATION.............................................................................................................. 29 
9.5.  TEMPERATURE FIXED VALUE ........................................................................................... 29 
9.6.  ALTITUDE ................................................................................................................................ 30 
9.7.  PROCESS OUTPUT CALIBRATION ...................................................................................... 31 
9.7.1.  Minimum Calibration.......................................................................................................... 31 
9.7.2.  Span Calibration.................................................................................................................. 31 
9.8.  CORRECTION COEFFICIENT ................................................................................................ 31 
9.8.1.  Probe Coefficient ................................................................................................................ 32 
9.8.2.  Piezometer Ring Coefficient ............................................................................................... 32 
9.9.  FOUR POINT FLOW CORRECTION...................................................................................... 33 
9.10.  MAC ADDRESS (BACNET COMMUNICATION OPTION)............................................. 34 
9.11.  INSTANCE NUMBER (BACNET COMMUNICATION OPTION) ................................... 34 
9.12.  MODBUS ID (MODBUS COMMUNICATION OPTION).................................................. 34 
9.13.  BAUD RATE (BACNET & MODBUS COMMUNICATION OPTIONS) .......................... 35 
10.  WARNING MESSAGES .............................................................................................................. 36 
10.1.  INPUT PRESSURE OVERRANGE MESSAGE .................................................................. 36 
10.2.  TRANSDUCER CALIBRATION MESSAGE ...................................................................... 36 
10.3.  OPERATING RANGE MESSAGE ....................................................................................... 36 
10.4.  NEW OPERATING RANGE MESSAGE ............................................................................. 36 
11.  TROUBLESHOOTING GUIDE ................................................................................................... 37 

Paragon Controls Incorporated ii Revision Level 012


MicroTransEQ Operation & Maintenance Manual

1. INTRODUCTION
1.1. DESCRIPTION
The MicroTransEQ Signal Processor employs current state-of-the-art digital microprocessor technology
to produce highly stable and accurate differential pressure and air flow measurements. The
MicroTransEQ is factory configured and calibrated to the exact specification determined at time of order.
Simple field configuration of engineering units, operating range, process noise filtering, alarm set points,
etc., are performed via password protected intuitive menus that are accessed through the integral six
button touch pad. Device monitoring and configuration can also be performed by a building
management system through a LonWorks®, BACnet®-MS/TP Master, or Modbus® Slave
communication network. Optional features include AutoZero; High/Low Remote Alarms; Temperature
Compensation; and LonWorks®, BACnet®-MS/TP Master, and Modbus® Slave communication.

1.2. BASIC OPERATION


The transducer receives a differential pressure signal from the pressure or flow sensing element. This
signal is scaled and linearized before being displayed and transmitted out as a 4-20mA, 0-5VDC, or 0-
10VDC signal.
The AutoZero option detects and corrects any zero offset caused by large ambient temperature changes.
The Temperature Compensation option compensates the flow and velocity signal for density changes
caused by variations in the process air temperature. An external temperature transmitter or input signal
from the building management system is required.

1.3. SPECIFICATIONS
1.3.1. Power Supply
20 to 28 VAC/DC

1.3.2. Power Consumption


Standard Unit: 216mA at 24VAC
150mA at 24VDC
Full Options: 250mA at 24VAC
175mA at 24VDC

1.3.3. Accuracy
±0.25% full scale (Standard)
±0.10% full scale (Optional)

1.3.4. Temperature Input Options


0-10VDC
4-20mA

1.3.5. Process Output Options


0-5VDC
0-10VDC
4-20mA (700Ω maximum load)

Paragon Controls Incorporated 1 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

1.3.6. High/Low Alarm Relay Outputs


Two single (1 form C) dry contacts rated for:
5 amps at 30VAC/DC
10 amps at 120VAC

1.4. SAFETY
1.4.1. Electrical Connections
Before any electrical connections are made, ensure the POWER SWITCH is in the OFF position.

1.4.2. Static Electricity


The circuit board contains components which are susceptible to damage caused by static electrical
discharge. Should it be necessary to remove the circuit board from the enclosure, appropriate
precautions must first be taken to ensure that the operator and the circuit board are at the same electrical
potential.

Paragon Controls Incorporated 2 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

2. PRODUCT DIMENSIONS
2.1. NEMA 1 MECHANICAL DIMENSIONS
4.625"
3.500"
I.D./DATA LABEL

75 F *
1,225
ACFM

MicroTrans EQ
SIGNAL PROCESSOR

8.250"
7.625"

PARAGON
PCI CONTROLS
INCORPORATED

1.4"

0.20" DIA (TYP OF 4)


PG21(3/4")

2.265"
1.2"

PG13.5(1/2") - TYP OF 3

Paragon Controls Incorporated 3 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

2.2. NEMA 4 MECHANICAL DIMENSIONS


MOUNTING SCREW DIA. UP TO 1/4".
(TYP OF 2)

I.D./DATA LABEL

75 F *
1,225
ACFM

7.0"
MicroTrans EQ 8.2" 9.56"
SIGNAL PROCESSOR

PARAGON
PCI CONTROLS
INCORPORATED

PG13.5(1/2")
PG13.5(1/2")

5.0"

STANDARD 1/4" COMPRESSION OPTION

PG21(3/4")

3.12"

PG13.5(1/2")

Paragon Controls Incorporated 4 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

3. INSTALLATION
3.1. ELECTRICAL & PNEUMATIC INSTALLATION
- NEMA 1 & 4 Option - Remove the cover by turning each corner cover mounting screw
counter clockwise.
- Both NEMA 1 & NEMA 4 enclosures incorporate three 1/2 inch conduit connections and
one 3/4 inch conduit connection to interface all electrical wiring and pneumatic tubing to the
device. Determine which conduit connection will be used and remove the black plug and
install the appropriate conduit fitting (By Others).
- The three electrical connectors (J1, J2, and J3) located on the MicroTransEQ board have
removable terminal blocks for ease of installing the interface wiring. (Caution - All electrical
connections must be made with the MicroTransEQ power switch in the OFF position).
RP1

J1
1 24VAC / DC
2
POWER
SWITCH 3 EARTH GROUND
ON
S3 ESC S2 S4 ENTER LON J2
S1 mA 10V mA
+ 24VDC OUTPUT POWER
OFF 4
TEMP. PROC.
INPUT OUTPUT 5 + TEMPERATURE INPUT
SWITCH POSITIONS J1 V 5V V
J2 J3 (ALARM OPTION)
6 - TEMPERATURE INPUT(GND)
SHOWN IN BLACK
S1 POSITION 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 7 + ANALOG PROCESS OUTPUT
INDICATING 4-20mA
8 - ANALOG PROCESS OUTPUT(GND)
TEMPERATURE INPUT
S2 AND S4 POSITIONS 9 + NETWORK COMMUNICATIONS
INDICATING 0-10VDC
PROCESS OUTPUT 10 - NETWORK COMMUNICATIONS

POWER SUPPLY
- ANALOG RECEIVING DEVICE
J3 (ALARM OPTION)
11
(24VAC/DC) + PROCESS OUTPUT
12
PURGE HOLD

13 COM

14 NO HIGH ALARM

REFER TO SECTION 2.4 FOR 15 NC


PROPER TEMPERATURE
TRANSMITTER CONNECTION
16 COM

17 NO LOW ALARM
18 NC

Tp CONNECTION

TOTAL (HIGH) STATIC (LOW)


PRESSURE PRESSURE FE-1000
CONNECTION CONNECTION
Sp CONNECTION

TYPICAL FLOW ELEMENT CONNECTION

Paragon Controls Incorporated 5 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

3.2. TEMPERATURE TRANSMITTER CONNECTION


Shielded cable is recommended for all connections between the MicroTransEQ and the Temperature
Transmitter.

3.2.1. 4-20mA Output/2-Wire Loop Powered Temperature Transmitter

POWER
SWITCH
ON
ESC S2 S4 ENTER LON
S1 mA 10V mA
OFF
TEMP. PROC.
INPUT OUTPUT

S1 SET TO J1 V 5V V
J2 J3 (ALARM OPTION)
mA POSITION
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

J2
4 + 24VDC OUTPUT POWER

5 + TEMPERATURE INPUT

6 - TEMPERATURE INPUT(GND)

7 + PROCESS OUTPUT
- TEMPERATURE
TRANSMITTER 8 - PROCESS OUTPUT(GND)
(4-20mA LOOP
+ POWERED) 9 + NETWORK COMMUNICATIONS

10 - NETWORK COMMUNICATIONS

3.2.2. 0-10VDC Output/24VAC Power 3-Wire Temperature Transmitter

POWER
SWITCH
ON
ESC S2 S4 ENTER LON
S1 mA 10V mA
OFF
TEMP. PROC.
INPUT OUTPUT
J1 V 5V V
J2 J3 (ALARM OPTION)
S1 SET TO
V POSITION 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

J2
4 + 24VDC OUTPUT POWER

5 + TEMPERATURE INPUT

6 - TEMPERATURE INPUT(GND)

7 + PROCESS OUTPUT
O
TEMP. TRANSMITTER
- + +24VAC - 8 - PROCESS OUTPUT(GND)

POWER 9 + NETWORK COMMUNICATIONS


(24VAC POWERED
SOURCE
/ 0-10VDC OUTPUT) 10 - NETWORK COMMUNICATIONS

Note: If the MicroTransEQ power source is 24VAC, the same power source can be used to power the
Temperature Transmitter.

Paragon Controls Incorporated 6 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

3.2.3. 0-10VDC Output/24VDC Power 3-Wire Temperature Transmitter

POWER
SWITCH
ON
ESC S2 S4 ENTER LON
S1 mA 10V mA
OFF
TEMP. PROC.
INPUT OUTPUT
J1 V 5V V
J2 J3 (ALARM OPTION)
S1 SET TO
V POSITION
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

J2
4 + 24VDC OUTPUT POWER

5 + TEMPERATURE INPUT

6 - TEMPERATURE INPUT(GND)

7 + PROCESS OUTPUT

+ O
TEMP. TRANSMITTER
- 8 - PROCESS OUTPUT(GND)

9 + NETWORK COMMUNICATIONS
(24VDC POWERED
/ 0-10VDC OUTPUT) 10 - NETWORK COMMUNICATIONS

3.2.4. 0-10VDC or 4-20mA from a Building Management System (BMS)

POWER
SWITCH
ON
ESC S2 S4 ENTER LON
S1 mA 10V mA
OFF
TEMP. PROC.
INPUT OUTPUT

J1 V 5V V
J2 J3 (ALARM OPTION)
VERIFY CORRECT
S1 POSITION. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
S1 UP=mA
S1 DOWN=V

J2
4 + 24VDC OUTPUT POWER

5 + TEMPERATURE INPUT

6 - TEMPERATURE INPUT(GND)

7 + PROCESS OUTPUT

8 - PROCESS OUTPUT(GND)
TEMPERATURE. SIGNAL
FROM BMS SYSTEM
+ 9 + NETWORK COMMUNICATIONS
(0-10VDC / 4-20mA)
- 10 - NETWORK COMMUNICATIONS

Note: Verify Temperature Input switch (S1) position matches the input signal type (refer to Section 4.2).

Paragon Controls Incorporated 7 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

4. INPUT/OUTPUT SET-UP
EQ
The MicroTrans has been configured and calibrated at the factory for the specific application. Refer
to the MicroTransEQ Set-Up label located on the left side of unit to verify correct Input/Output
configuration for the application. If input or output configuration changes are required refer to the tables
in the sections below and the figure in Section 3.1.

4.1. PROCESS OUTPUT


To change the output configuration, set the S2 & S4 switches as follows:

Process Output Range S2 S4


Current 4-20mA NA mA
Voltage 0-10VDC 10V V
Voltage 0-5VDC 5V V

4.2. TEMPERATURE INPUT (OPTION)


To change the input configuration, set the S1 switch as follows:

Temperature Input S1 Switch Selection


4-20mA mA
0-10VDC V

Paragon Controls Incorporated 8 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

5. COMMON STARTUP CONFIGURATION CHANGES


5.1. AREA FACTOR
The Area Factor can be entered or modified as follows:
Step 1. From the active display, enter the Tech. Configuration Menu by pressing the Up/Down
keys simultaneously.
Step 2. Enter password number 1000 and press the Enter key.
Step 3. Press the Enter key once to access the Area Factor Menu.
Step 4. Enter the new Area Factor using the Up/Down/Left/Right keys.
Step 5. Press the Enter key once.
Step 6. Press the ESC key twice.
Step 7. The active display should now be displayed.

Tech. Config.
Password: 1000

Area Factor  Area Factor
Min Calibration (FT2)
Span Calibration
Altitude (001.000)

If the new Area Factor causes the existing Operating Range Value to be outside the new calculated
Minimum or Maximum Full Scale Value, the below Warning Message will appear and the Operating
Range will be reset to the new Maximum Full Scale Value by pressing Enter. The display will
automatically jump to the Op Range Menu allowing the user to enter a new Operating Range Value.
This can be accomplished by performing the steps under Section 5.2. See Area Factor Example below.

Warning Message:
Op Range Outside
Allowable Value
Reset to MAX F.S.
(Press Enter)

Paragon Controls Incorporated 9 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

-Area Factor Example-


Op Range value within
New Min/Max values Area Factor
(FT2)
Accepted
(001.200)

Area Factor
(FT2)

(001.000)

Entering a new Area Warning Message


Factor and pressing
the Enter button will Op Range Outside Operating Range
calculate new Min & Allowable Value. (ACFM)
Max Op Range values. Reset to Max F.S. (6,000 - 12,000)
Op Range value exceeds (Press Enter) (12,000)
New Min/Max values
Pressing the Enter button The Op Range value can be
will reset the current Op changed and will represent
Range value to the new 100% of the process output
calculated Max. F.S value signal (5vdc, 10vdc, or 20mA).
which will represent 100%
of the process output value.

5.2. OPERATING RANGE


The Operating Range allows the user to enter a value which will represent 100% of the process output
signal (5VDC, 10VDC, or 20mA). The menu will display the Maximum Full Scale Value possible for
the user to enter as the Operating Range. The Operating Range can be changed using the following
steps:
Step 1. From the active display, enter the Field Menu by pressing and holding the Enter key for
3 seconds.
Step 2. Press the Enter key once to access the Operating Range Menu.
Step 3. Enter the new Operating Range using Up/Down/Left/Right keys.
Step 4. Press the Enter key once.
Step 5. Press the ESC key twice.
Step 6. The active display should now be displayed.
Step 7. The Process Output is automatically rescaled to the new Operating Range.

Field Setup
Menu

Operating Range  Operating Range
Zero Calibration ( ACFM )
Engineering Units (6,000-12,000)
Lockdown (010,000)

Paragon Controls Incorporated 10 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

5.3. TEMPERATURE COMPENSATION FOR AIR DENSITY


The Temperature Compensation option compensates the flow and velocity signal for density changes
caused by variations in the process air temperature. The following menus for configuration of
Temperature Compensation are only available if the Temperature Compensation option is purchased.
Additionally, an input signal from an external temperature transmitter or the building automation system
is required; see Section 3.2 for proper temperature transmitter connection.

5.3.1. Temperature Input Signal Selection


To change the input configuration, set the S1 switch as follows:
(Refer to Section 3.1 for S1 location on board)

Temperature Input S1 Switch Selection


4-20mA mA
0-10VDC V

5.3.2. Temperature Units


The Temperature Units Menu allows the user to select the appropriate temperature units for the job.

Field Setup
Menu

Flow Correction Temperature Units  Units
AutoZero Temperature Values (ºF / ºC)
Temp Comp.  Temperature Input
Display Filter Fixed Value (ºF)

5.3.3. Temperature Values


The Temperature Values Menu allows the factory or user to set the minimum and maximum temperature
range values that represent the input signal from the external temperature transmitter or the building
automation system.

Field Setup
Menu

Flow Correction Temperature Units Minimum Value
AutoZero Temperature Values  (-030)
Temp Comp.  Temperature Input Maximum Value
Display Filter Fixed Value (130)

Paragon Controls Incorporated 11 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

If the new temperature values cause the existing Operating Range Value to be outside the new calculated
Minimum or Maximum Full Scale Value, the below Warning Message will appear and the Operating
Range will be reset to the new Maximum Full Scale Value by pressing Enter. The display will
automatically jump to the Op Range Menu allowing the user to enter a new Operating Range Value.
This can be accomplished by performing the steps under Section 5.2. See Temperature Range Example
below.

Warning Message:
Op Range Outside
Allowable Value
Reset to MAX F.S.
(Press Enter)

-Temperature Range Example-


Op Range value within
New Min/Max values Minimum Value
(-000)
Accepted
(100)

Minimum Value
(-000)
Maximum Value
(000)

Entering a new Min & Warning Message


Max Temperature
value and pressing the Op Range Outside Operating Range
Enter button will Allowable Value. (ACFM)
calculate new Min & Reset to Max F.S. (6,000 - 12,000)
Op Range value exceeds (Press Enter) (12,000)
Max Op Range values. New Min/Max values
Pressing the Enter button The Op Range value can be
will reset the current Op changed and will represent
Range value to the new 100% of the process output
calculated Max. F.S value signal (5vdc, 10vdc, or 20mA).
which will represent 100%
of the process output value.

Paragon Controls Incorporated 12 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

5.3.4. Temperature Input


The Temperature Input Menu allows the user to select between three temperature input options (Fixed,
Variable, and Net) for the flow calculations. If Fixed is selected the default temperature value entered in
the Fixed Value Menu (see Section 5.3.5) is used. The Standard Fixed Value is 68˚F. If Variable is
selected an external temperature input signal is required (see Sections 5.3.1 through 5.3.3). If Net is
selected, the temperature input signal is obtained through network communications. The Net option is
only available if one of the communication options is ordered (see Sections 9.11 through 9.13). The
temperature value is only displayed on the LCD screen, if the Temperature Input is set to Variable or
Net.

Field Setup
Menu

Flow Correction Temperature Units Temp. Input
AutoZero Temperature Values (Fix/Var/Net)
Temp Comp.  Temperature Input 
Display Filter Fixed Value (Variable)

5.3.5. Fixed Value


The Fixed Value Menu allows the user to enter a temperature value other than the standard value of 68˚F
for the flow calculations. This value will not be displayed on the LCD screen.

Field Setup
Menu

Flow Correction Temperature Units Fixed Value
AutoZero Temperature Values (˚F)
Temp Comp.  Temperature Input
Display Filter Fixed Value  (+068)

Paragon Controls Incorporated 13 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

6. ACTIVE DISPLAYS & KEY FUNCTIONS


6.1. POWER-UP INITIATION DISPLAY
Upon initial power-up, Software Revision information will be displayed on the graphic display for
approximately 5 seconds.
EQ-1
Software Rev. XX.XXX

Module Rev. XX.XXX

6.2. PROCESS DISPLAY DESCRIPTIONS


After power-up initialization, the following information will appear on the graphic display depending
upon the options purchased.

2 3
1
* 75˚F * 75˚F *

0.0000 000,000 000,000


AutoZero Inch w.c. High Alarm ACFM Low Alarm ACFM
5 Pressure Monitoring with an 4 Flow Monitoring with a Flow Monitoring with a
Auto Zero Cycle High Alarm Condition 7 Low Alarm Condition
6

Number Description
1 Process value
2 Air Flow temperature units in degree F or C (Temperature Compensation Option)
3 Flashing Asterisk indicates the CPU is functioning
4 Engineering units
5 Displayed during an AutoZero cycle (AutoZero Option)
6 Indicating High Alarm Value has been exceeded (High/Low Alarm Option)
7 Indicating Low Alarm Value has been exceeded (High/Low Alarm Option)

Paragon Controls Incorporated 14 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

6.3. KEY FUNCTIONS


The following figure and description identify the function of each Key.
RP1 9

2
5 3 1 8
6
POWER
SWITCH 7
ON
ESC S2 S4
ENTER LON
S1 mA 10V mA
OFF
TEMP.
INPUT
PROC.
OUTPUT
4
J1 V 5V V
J2 J3 (ALARM OPTION)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Number Description
Enter Key - Allows a user to enter into the Field Menu, enter into a selected menu item, or
1
store into memory changes made to the program.
Up Key - Allows the user to scroll up in the menu list to a selected item or increase digits when
2
making value changes.
Right Key - When making changes to user values the Right Key allows the user to scroll to the
3
correct digit for changes.
Down Key - Allows the user to scroll down in the menu list to a selected item or decrease digits
4
when making value changes.
Left Key - When making changes to user values the Left Key allows the user to scroll to the
5
correct digit for changes.
Escape Key - The Escape Key allows the user to back out of the menu to the Active Display. If
6 a user starts to make a change and decides to cancel the change, the Escape Key will allow the
user to return to the Active Display without making the change.
Power Switch – Allows a user to turn power off to the Signal Processor during field wiring or
7
modifications to the device.
Lon Switch – Allows a user to send a unique Neuron device ID when connecting to a
8
LonWorks communication network.
9 RP1 – Allows a user to adjust the display contrast.

Paragon Controls Incorporated 15 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

7. DISPLAY MENUS
7.1. FIELD SETUP & TECH. CONFIGURATION MENUS
The following table shows the Field Setup and Tech. Configuration Menus for devices set to monitor
Flow, Velocity, and Pressure. The display will vary depending upon the options purchased.

MicroTransEQ Setup for Flow or Velocity


Field Setup Menu Tech. Configuration Menu
(Press ENTER Key) (Press UP/DOWN Keys simultaneously)
(Enter Password number 1000)
(Press ENTER Key)
Operating Range Area Factor
Zero Calibration Min Calibration
Eng. Units Span Calibration
Lockdown Temp Fixed Value
Flow Correction Altitude
AutoZero (Optional) Output Calibration
Temp Comp. (Optional) Correction Coeff.
Display Filter 4PT Flow Corr
Output Filter MAC Address (Optional)
Alarm Options (Optional) Instance Number (Optional)
Factory Defaults Modbus ID (Optional)
Baud Rate (Optional)
EQ
MicroTrans Setup for Pressure
Field Setup Menu Tech. Configuration Menu
(Press ENTER Key) (Press UP/DOWN Keys simultaneously)
(Enter Password number 1000)
(Press ENTER Key)
Operating Range Min Calibration
Zero Calibration 50% Calibration
Eng. Units Span Calibration
AutoZero (Optional) Output Calibration
Display Filter MAC Address (Optional)
Output Filter Instance Number (Optional)
Alarm Options (Optional) Modbus ID (Optional)
DP Display Format Baud Rate (Optional)
Factory Defaults

Paragon Controls Incorporated 16 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

8. FIELD SETUP MENUS


To set parameters under the Field Setup Menus refer to the following procedure, below subsections, and
Section 6.3 for Key functions.
Step 1. Enter the Field Setup Menu by depressing and holding the Enter Key for 5
seconds.
Step 2. Once in the Field Setup Menu, use the Up/Down Keys to highlight the required
parameter for configuration as shown in Sections 8.1 through 8.12. Press the Enter
Key once to access the highlighted parameter Menu.
Step 3. Once in the parameter menu, the parameter can be changed using
Up/Down/Left/Right Keys. After the parameter has been changed, press the Enter
Key once. Then Press the ESC Key once to return to the Field Setup Menu.
Step 4. After all of the required parameters have been configured, exit the Field Setup
Menu by pressing the ESC Key. The Process Display (see Section 6.2) will then
be displayed.

8.1. OPERATING RANGE


The Operating Range allows the user to enter a value which will represent 100% of the process output
signal (5VDC, 10VDC, or 20mA). The menu will display the Maximum Full Scale Value possible for
the user to enter as the Operating Range.

Field Setup
Menu

Operating Range  Operating Range
Zero Calibration ( ACFM )
Engineering Units (6,000-12,000)
Lockdown (010,000)

8.2. ZERO PRESSURE CALIBRATION


The Zero Calibration Menu allows the user to perform a zero transducer calibration to eliminate any
transducer zero shift.
(Caution: Before performing a zero calibration, disconnect the Total (High) and Static (Low)
pressure connections, perform a zero calibration and then reconnect the Total and Static pressure
connections).

Field Setup
Menu

Operating Range Input Value CPU Taking
Zero Calibration  (0.000) Inch w.c.  Samples
Engineering Units
Lockdown (Press Enter) (Please Wait)

Paragon Controls Incorporated 17 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

8.3. ENGINEERING UNITS


A list of engineering units are available for the user to select from for display purposes to meet customer
requirements. Changing the engineering units will affect the process display and the alarm value menus.

Field Setup
Menu

Operating Range Eng. Units
Zero Calibration
Engineering Units  (ACFM)
Lockdown
Standard Actual Standard Actual
Flow Flow Velocity Velocity Pressure
Units Units Units Units Units
SCFM ACFM SFPM AFPM Inch w.c.
SCFH L/S Sm/s Am/s Pa
SL/S Am3/S % % KPa
Sm3/S Am3/M mm w.c.
Sm3/M Am3/HR %
Sm3/HR %
%

8.4. LOCKDOWN
Due to the high square root gain associated with very low delta p values, the display and process output
are locked to a zero value until the input value reaches the specified Lockdown Value that was entered.
Above the Lockdown Value the output is linear to air flow. The following menus are only available if
the MicroTransEQ is configured by Paragon at the time of order for flow or velocity.

8.4.1. Lockdown Value


The Lockdown Value can be changed from 0 to 20% of Operating Range Value. Lockdown Values can
be changed in 1% increments. The recommended standard is 10%.

Field Setup
Menu

Operating Range Lockdown (0-20%)
Zero Calibration (10)%
Engineering Units Delay (0-20 sec)
Lockdown  (2) Sec

Paragon Controls Incorporated 18 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

8.4.2. Lockdown Delay


The Lockdown Delay Menu allows the user to enter a lockdown time delay (0-20 seconds) that will
delay the display and output lockdown from occurring until the flow value or output value has remained
below the lockdown value for that duration.
Field Setup
Menu

Operating Range Lockdown (0-20%)
Zero Calibration (10)%
Engineering Units Delay (0-20 sec)
Lockdown  (2) Sec

8.5. FLOW CORRECTION


The Flow Correction Menu was incorporated into the MicroTransEQ to give the user an easy way to
make corrections to the display and output without changing the Op. Range Value entered by the factory
or user. The Flow Correction Menu would be used to correct for a constant error from zero to the
entered Op Range Value. The following menus are only available if the MicroTransEQ is configured by
Paragon at the time of order for flow or velocity.

8.5.1. Flow Correction (K-Factor)


If the user knows the % change required to match the balancers reading, select the K-Factor Menu and
enter this value for the K-Factor. The minimum and maximum allowable K-Factor Value is displayed in
the K-Factor Menu.
Field Setup
Menu

Flow Correction  Flow Correction
AutoZero K-Factor  K-Factor Range
Temp Comp. (0.85 / 1.3)
Display Filter K-Factor Calc. K=(01.000)

8.5.2. Flow Correction (K-Factor Calculator)


If the new K-factor Value needs to be calculated, select the K-Factor Calc. Menu, enter the
MicroTransEQ Displayed Value and actual Measured Value, press Enter and the % change will be
calculated and stored as the new K-Factor Value.
Field Setup
Menu

Flow Correction  Displayed Value
AutoZero K-Factor (000,000)
Temp Comp. Measured Value
Display Filter K-Factor Calc.  (000,000)

Paragon Controls Incorporated 19 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

-FLOW CORRECTION EXAMPLE-


The balancer is consistently measuring a value of 9,500 CFM, which is 500 CFM less than the 10,000
CFM value on the MicroTransEQ display. The user would then perform the following math function:
Measured Value / Displayed Value = K-Factor so 9,500 CFM / 10,000 CFM = 0.950. The user would
enter 0.950 for the K-Factor Flow Correction. If the K-Factor Calculator is used, the K- Factor Flow
Correction would automatically update the K Factor.

8.6. AUTOZERO
The AutoZero option detects and corrects any zero offset caused by large ambient temperature changes.
The following menus for configuration of AutoZero are only available if the AutoZero option is
purchased.

8.6.1. AutoZero Status


The AutoZero Status Menu allows the user to turn the AutoZero function ON or OFF.

Field Setup
Menu

Flow Correction AZ Status  AZ Status
AutoZero  AZ Interval (ON/OFF)
Temp Comp. AZ Test Interval
Display Filter (ON)

8.6.2. AutoZero Interval


The AutoZero Interval Menu allows the user to select the AutoZero Interval from once an hour to once a
day in 1 hour increments. Use the UP/DOWN keys to select the interval value. Upon device power up,
an AutoZero cycle will occur after 20 seconds.

Field Setup
Menu

Flow Correction AZ Status AZ Interval
AutoZero  AZ Interval  (1 TO 24HR)
Temp Comp. AZ Test Interval
Display Filter (1)HR

Paragon Controls Incorporated 20 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

8.6.3. AutoZero Test Interval


For troubleshooting or testing the AutoZero function, the AutoZero Test Interval Menu allows the user
to select an Auto Zero test frequency of once a minute to once every 30 minutes in 1 minute increments.
Use the UP/DOWN keys to select the interval value. If AutoZero Test Interval is turned ON for more
than 60 minutes, it will automatically default to OFF and the AutoZero Interval (see Section 8.6.2) will
be reactivated.

Field Setup
Menu

Flow Correction AZ Status AZ Test Interval
AutoZero  AZ Interval (OFF)
Temp Comp. AZ Test Interval  Interval
Display Filter (1)Min

8.7. TEMPERATURE COMPENSATION


The Temperature Compensation option compensates the flow and velocity signal for density changes
caused by variations in the process air temperature. The following menus for configuration of
Temperature Compensation are only available if the Temperature Compensation option is purchased.
Additionally, an input signal from an external temperature transmitter or the building automation system
is required; see Section 3.2 for proper temperature transmitter connection and Section 4.2 for
temperature input signal configuration.

8.7.1. Temperature Units


The Temperature Units Menu allows the user to select the appropriate temperature units for the job.

Field Setup
Menu

Flow Correction Temperature Units  Units
AutoZero Temperature Values (ºF / ºC)
Temp Comp.  Temperature Input
Display Filter Fixed Value (ºF)

Paragon Controls Incorporated 21 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

8.7.2. Temperature Values


The Temperature Values Menu allows the factory or user to set the minimum and maximum temperature
range values that represent the input signal from the external temperature transmitter or the building
automation system.
Field Setup
Menu

Flow Correction Temperature Units Minimum Value
AutoZero Temperature Values  (-030)
Temp Comp.  Temperature Input Maximum Value
Display Filter Fixed Value (130)

If the new temperature values cause the existing Operating Range Value to be outside the new calculated
Minimum or Maximum Full Scale Value, the below Warning Message will appear and the Operating
Range will be reset to the new Maximum Full Scale Value by pressing Enter. The display will
automatically jump to the Op Range Menu allowing the user to enter a new Operating Range Value.
This can be accomplished by performing the steps under Section 5.2. See Temperature Range Example
below.
Warning Message:
Op Range Outside
Allowable Value
Reset to MAX F.S.
(Press Enter)

-Temperature Range Example-


Op Range value within
New Min/Max values Minimum Value
(-000)
Accepted
(100)

Minimum Value
(-000)
Maximum Value
(000)

Entering a new Min & Warning Message


Max Temperature
value and pressing the Op Range Outside Operating Range
Enter button will Allowable Value. (ACFM)
calculate new Min & Reset to Max F.S. (6,000 - 12,000)
Op Range value exceeds (Press Enter) (12,000)
Max Op Range values. New Min/Max values
Pressing the Enter button The Op Range value can be
will reset the current Op changed and will represent
Range value to the new 100% of the process output
calculated Max. F.S value signal (5vdc, 10vdc, or 20mA).
which will represent 100%
of the process output value.

Paragon Controls Incorporated 22 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

8.7.3. Temperature Input


The Temperature Input Menu allows the user to select between three temperature input options (Fixed,
Variable, and Net) for the flow calculations. If Fixed is selected the default temperature value entered in
the Fixed Value Menu (see Section 5.3.5) is used. The Standard Fixed Value is 68˚F. If Variable is
selected an external temperature input signal is required (see Sections 5.3.1 through 5.3.3). If Net is
selected, the temperature input signal is obtained through network communications. The Net option is
only available if one of the communication options is ordered (see Sections 9.11 through 9.13). The
temperature value is only displayed on the LCD screen, if the Temperature Input is set to Variable or
Net.
Field Setup
Menu

Flow Correction Temperature Units Temp. Input
AutoZero Temperature Values (Fix/Var/Net)
Temp Comp.  Temperature Input 
Display Filter Fixed Value (Variable)

8.7.4. Fixed Value


The Fixed Value Menu allows the user to enter a temperature value other than the standard value of 68˚F
for the flow calculations. This value will not be displayed on the LCD screen.

Field Setup
Menu

Flow Correction Temperature Units Fixed Value
AutoZero Temperature Values (˚F)
Temp Comp.  Temperature Input
Display Filter Fixed Value  (+068)

8.8. DISPLAY FILTER


The Display Filter Menu allows the user to adjust the Display Filter rolling average algorithm by setting
the Sample Interval Time value in seconds and the number of rolling average Sample Counts. The
adjustment range of the Sample Interval Time is 0.10 to 65.5 seconds in 0.10 increments. The Sample
Count range is 0 to 150 Sample Counts. The Display Filter is independent of the Process Output Filter
Value (See Section 8.10).

Field Setup
Menu

Flow Correction Sample Interval Time
AutoZero (00.5)sec.
Temp Comp. (0-150) Sample Count
Display Filter  (010)

Paragon Controls Incorporated 23 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

8.9. PROCESS OUTPUT FILTER


The Process Output Filter Menu allows the user to adjust the Process Output Filters rolling average
algorithm by setting the Sample Interval Time value in seconds and the number of rolling average
Sample Counts. The adjustment range of the Sample Interval Time is 0.10 to 65.5 seconds in 0.10
increments. The Sample Count range is 0 to 150 Sample Counts. The Process Output Filter is
independent of the Display Filter Value (See Section 8.8).

Field Setup
Menu

Output Filter  Sample Interval Time
Alarm Options (00.5)sec.
DP Display Format (0-150) Sample Count
Factory Defaults (010)

8.10. HIGH/LOW ALARM OPTIONS


The following menus for configuration of High/Low Alarms are only available if the High/Low Alarm
option is purchased.

8.10.1. Alarm Status


The Alarm Status allows the user to independently turn each alarm ON or OFF.

Field Setup
Menu

Output Filter Alarm Status  Low Alarm
Alarm Options  Alarm Value (On)
DP Display Format Alarm Delay High Alarm
Factory Defaults (On)

Paragon Controls Incorporated 24 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

8.10.2. Alarm Values


The Alarm Value Menu allows the user to enter the Low or the High flow or pressure alarm value.
Alarm values will be displayed in the same engineering units selected in the Eng. Units Menu (see
Section 8.3).
- High Alarm Function: The High Alarm activates if the flow or pressure exceeds the High
Alarm value and resets when the flow or pressure drops below the High Alarm Value.
- Low Alarm Function: The Low Alarm activates if the flow or pressure drops below the Low
Alarm Value and resets when the flow or pressure exceeds the Low Alarm Value.

Field Setup
Menu

Output Filter Alarm Status Lo Alarm Value
Alarm Options  Alarm Value  (000,000)
DP Display Format Alarm Delay Hi Alarm Value
Factory Defaults (100,000)

8.10.3. Alarm Delay


The Alarm Delay Menu allows the user to enter an alarm delay of 0 to 999 seconds before an alarm will
be activated. The alarm will be reset without a delay.

Field Setup
Menu

Output Filter Alarm Status Lo Alarm Delay
Alarm Options  Alarm Value (000)Seconds
DP Display Format Alarm Delay  Hi Alarm Delay
Factory Defaults (000)Seconds

8.11. DP DISPLAY FORMAT


The DP Display Format Menu is only available when the MicroTransEQ is configured by Paragon at the
time of order for pressure; it allows the user to change the number of digits shown to the right of the
decimal point. Selections are 0 to 4 digits. Use the UP/DOWN keys to move the decimal point to the
left or right.

Field Setup
Menu

Output Filter Number of Digits
Alarm Options After Decimal
DP Display Format  Point.
Factory Defaults (00.000)

Paragon Controls Incorporated 25 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

8.12. FACTORY DEFAULTS


If pressure calibration changes have been made incorrectly to the MicroTransEQ program, all pressure
calibration values and device settings can be restored to the original factory settings by selecting YES
and pressing Enter in both the Set To Factory Defaults Menu and the Verify Set To Factory Defaults
Menu (See Factory Defaults table below for a list of Saved Settings).

Field Setup
Menu

Output Filter Set To Verify Set To
Alarm Options Factory Defaults  Factory Defaults
DP Display Format
Factory Defaults  (No) (No)

FACTORY DEFAULTS
ITEM SAVED SETTING ITEM SAVED SETTING
1 All Factory Calibration Points (12) 14 MAC Address
2 Area Factor 15 Instance Number
3 Operating Range 16 Engineering Units
4 4 Pt Flow Correction 17 Display Filter Values
5 Altitude 18 Output Filter
6 K-Factor 19 DP Display Format
7 Lockdown & Delay Values 20 Output Calibration
8 Flow Correction 21 AutoZero Status
9 Flow Coefficient 22 AutoZero Interval
10 Min. & Max. Temp Range Values 23 Temp. Units
11 Alarm Status 24 Temp. Input
12 Alarm Values 25 Temp. Fixed Value
13 Alarm Delay 26 Baud Rate

Paragon Controls Incorporated 26 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

9. TECH CONFIGURATION MENUS


To set parameters under the Tech Configuration Menu, refer to the procedure below, associated
subsections and Section 6.3 for Key functions.
Step 1. Enter the Tech Configuration Menu by pressing and holding the Up/Down Keys
simultaneously for 5 seconds.
Step 2. Using the Up/Down/Left/Right Keys, enter password number 1000 and press the
Enter Key.
Step 3. Once in the Tech Configuration Menu, use the Up/Down Keys to highlight the
required parameter for configuration as shown in Sections 9.1 through 9.13. Press
the Enter Key once to access the highlighted parameter Menu.
Step 4. Once in the parameter menu, the parameter can be changed using the
Up/Down/Left/Right Keys. After the parameter has been changed, press the Enter
Key once. Then Press the ESC Key once to return to the Tech Configuration
Menu.
Step 5. After all of the required parameters have been configured, exit the Tech
Configuration Menu by pressing the ESC Key. The Process Display (see Section
6.2) will then be displayed.

9.1. AREA FACTOR


The Area Factor Menu allows the user to enter or modify an existing Area Factor. The Area Factor
Menu is only available if the MicroTransEQ is configured by Paragon at the time of order for flow or
velocity and for input from a non-amplified Pitot-type flow sensor.

Tech. Config.
Password: 1000

Area Factor  Area Factor
Min Calibration (FT2)
50% Calibration
Span Calibration (001.000)
If the new Area Factor causes the existing Operating Range Value to be outside the new calculated
Minimum or Maximum Full Scale Value, the below Warning Message will appear and the Operating
Range will be reset to the new Maximum Full Scale Value by pressing Enter. The display will
automatically jump to the Op Range Menu allowing the user to enter a new Operating Range Value.
This can be accomplished by performing the steps under Section 5.2. See Area Factor Example below.
Warning Message:
Op Range Outside
Allowable Value
Reset to MAX F.S.
(Press Enter)

Paragon Controls Incorporated 27 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

-Area Factor Example-


Op Range value within
New Min/Max values Area Factor
(FT2)
Accepted
(001.200)

Area Factor
(FT2)

(001.000)

Entering a new Area Warning Message


Factor and pressing
the Enter button will Op Range Outside Operating Range
calculate new Min & Allowable Value. (ACFM)
Max Op Range values. Reset to Max F.S. (6,000 - 12,000)
Op Range value exceeds (Press Enter) (12,000)
New Min/Max values
Pressing the Enter button The Op Range value can be
will reset the current Op changed and will represent
Range value to the new 100% of the process output
calculated Max. F.S value signal (5vdc, 10vdc, or 20mA).
which will represent 100%
of the process output value.

9.2. MINIMUM CALIBRATION


The Minimum Calibration Menu allows a user to perform a minimum transducer calibration. This value
will be placed in a different memory location and used until a Return to Factory Defaults is selected (see
Section 8.12). (Caution: Before performing a minimum calibration, disconnect the Total (High)
and Static (Low) Pressure connections, perform a minimum calibration and then reconnect the
Total and Static Pressure connections).

Tech. Config.
Password: 1000

Area Factor Input Value CPU Taking
Min Calibration  (0.0000) Inch W.C.  Samples
50% Calibration
Span Calibration (Press Enter) (Please Wait)

Paragon Controls Incorporated 28 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

9.3. 50% CALIBRATION


The 50% Calibration Menu is only available when the MicroTransEQ is configured by Paragon at the
time of order for pressure; it allows a user to perform a 50% transducer calibration to eliminate zero drift
in a bipolar transducer. This value will be placed in a different memory location and used until a Return
to Factory Defaults is selected (see Section 8.12).

Tech. Config.
Password: 1000

Area Factor Input Value CPU Taking
Min Calibration (0.0285) inch w.c. Samples
50% Calibration  
Span Calibration (Press Enter) (Please Wait)

9.4. SPAN CALIBRATION


The Span Calibration Menu allows the user to perform a span transducer calibration to eliminate any
possible transducer drift. This value will be placed in a different memory location than the Factory Span
memory location and used until a Return to Factory Defaults is selected (see Section 8.12).

Tech. Config.
Password: 1000

Area Factor Input Value CPU Taking
Min Calibration (0.0570) Inch w.c. Samples
50% Calibration 
Span Calibration  (Press Enter) (Please Wait)

9.5. TEMPERATURE FIXED VALUE


When the Temperature Compensation option (see Section 8.7) is not ordered, the Fixed Value Menu
allows the user to enter a temperature value other than the standard value of 68˚F for the density
calculations. This value will not be displayed on the LCD screen.

Tech. Config.
Password: 1000

Temp. Fixed Value  Temp. Fixed Value
Altitude ºF
Output Calibration (+068)
Correction Coeff.

Paragon Controls Incorporated 29 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

9.6. ALTITUDE
The Altitude Menu allows user to enter the specific altitude for the job other than the standard value of 0
feet above mean sea level for the density calculations.

Tech. Config.
Password: 1000

Temp. Fixed Value Altitude
Altitude 
Output Calibration (0000)Ft
Correction Coeff.

If the new Altitude causes the existing Operating Range Value to be outside the new calculated
Minimum or Maximum Full Scale Value, the below Warning Message will appear and the Operating
Range will be reset to the new Maximum Full Scale Value by pressing Enter. The display will
automatically jump to the Op Range Menu allowing the user to enter a new Operating Range Value.
This can be accomplished by performing the steps under Section 5.2. See Altitude Example below.
Warning Message:
Op Range Outside
Allowable Value
Reset to MAX F.S.
(Press Enter)

-Altitude Example-
Op Range value within
New Min/Max values Altitude
Accepted
(0100)Ft

Altitude

(0000)Ft

Entering a new Altitude Warning Message


and pressing the Enter
button will calculate Op Range Outside Operating Range
new Min & Max Op Allowable Value. (ACFM)
Range values. Reset to Max F.S. (6,000 - 12,000)
Op Range value exceeds (Press Enter) (12,000)
New Min/Max values
Pressing the Enter button The Op Range value can be
will reset the current Op changed and will represent
Range value to the new 100% of the process output
calculated Max. F.S value signal (5vdc, 10vdc or 20mA).
which will represent 100%
of the process output value.

Paragon Controls Incorporated 30 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

9.7. PROCESS OUTPUT CALIBRATION


9.7.1. Minimum Calibration
The Minimum Calibration Menu allows the user to make output zero adjustments. Monitor the output
and with each Up or Down key depression, the output will increase or decrease by 0.01VDC or 0.01mA
depending on output selection.

Tech. Config.
Password: 1000

Temp. Fixed Value Min Calibration  Use Up/Down
Altitude Span Calibration Buttons
Output Calibration  Adjust Output
Correction Coeff. (Press Enter)

9.7.2. Span Calibration


The Span Calibration Menu allows the user to make output span adjustments. Span adjustments require
a low pressure air source adjusted to the Full Scale Value shown on the side label. Monitor the output
and with each Up or Down key depression, the output will increase or decrease by 0.01VDC or 0.01mA
depending on output selection.

Tech. Config.
Password: 1000

Temp. Fixed Value Min Calibration  Use Up/Down
Altitude Span Calibration Buttons
Output Calibration  To Adjust Output
Correction Coeff. (Press Enter)

9.8. CORRECTION COEFFICIENT


The Correction Coefficient Menu is only available if the MicroTransEQ is configured by Paragon at the
time of order for flow or velocity. If the MicroTransEQ is configured for input from a non-amplified
Pitot-type flow sensor (such as those manufactured by Paragon) the menu in Section 9.8.1 will be
displayed. If the MicroTransEQ is configured for input from a piezometer ring or amplified differential
pressure flow sensor (manufactured by others) the menu in Section 9.8.2 will be displayed.

Paragon Controls Incorporated 31 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

9.8.1. Probe Coefficient


The Probe Coefficient Menu allows the user to modify the formula constant of 1096.70 for a non-
amplified Pitot-type flow sensor.
Tech. Config.
Password: 1000

Temp. Fixed Value Correction Coeff.
Altitude Probe
Output Calibration (1096.70)
Correction Coeff.  (001,096.70
EQ
The probe coefficient entered into the MicroTrans is based on the following equation:

Where:
= Velocity (afpm)
= Non-amplified Pitot-tube Coefficient, 1096.70
∆ = Differential Pressure Measured by the Pitot-tube (in. w.c.)
= Actual Density (lb/ft3)

9.8.2. Piezometer Ring Coefficient


The Piezometer Ring Coefficient Menu allows a user to enter the correction coefficient associated with
the piezometer ring or amplified differential pressure flow sensor. Correction coefficients should be
obtained from the sensor or air handling unit manufacturer.
Tech. Config.
Password: 1000

Temp. Fixed Value Correction Coeff.
Altitude Piezometer Ring
Output Calibration (000000.00)
Correction Coeff. 
The piezometer ring coefficient entered into the MicroTransEQ is based on the following equation:

Where:
= Flow (acfm)
= Piezometer Ring Coefficient
∆ = Differential Pressure Measured by the Piezometer Ring (in. w.c.)
= Actual Density of Air (lb/ft3)

Paragon Controls Incorporated 32 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

Since is known for a given job site, some sensor and air handling unit manufacturers will include this
value (or the value for standard air density 0.075 lbm/ft3) in the factor F supplied, simplifying the above
equation to:
√∆
Where:

or 0.075 (standard density) depending on the sensor or air handling unit manufacturer equation
for converting differential pressure to flow.
If a F value has been supplied by the fan or air handling unit manufacturer, this value will need to be
modified before entering the coefficient into the MicroTransEQ as shown below.

9.9. FOUR POINT FLOW CORRECTION


The Four Point Flow Correction Menu allows the user to make corrections to the display and output
signal at 20% increments between 20% and 80% of Operating Range Value entered. The Displayed
Value is a fixed value determined by the percentage of Operating Range. The Measured Value is the
value determined by an independent balancer’s reading. The Four Point Flow Correction Menu is only
available if the MicroTransEQ is configured by Paragon at the time of order for flow or velocity.

Tech. Config.
Password: 1000

4PT Flow Corr  80,000 CFM Displayed Value
MAC Address 60,000 CFM 80,000
Instance Number 40,000 CFM  Measured Value
20,000 CFM 79,500

80,000 CFM Displayed Value


60,000 CFM 60,000
40,000 CFM  Measured Value
20,000 CFM 60,500

80,000 CFM Displayed Value


60,000 CFM 40,000
40,000 CFM  Measured Value
20,000 CFM 40,100

80,000 CFM Displayed Value


60,000 CFM 20,000
40,000 CFM  Measured Value
20,000 CFM 19,500

Paragon Controls Incorporated 33 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

9.10. MAC ADDRESS (BACNET COMMUNICATION OPTION)


When the BACnet Communication option is ordered, the MAC Address Menu allows the user to set a
unique device address when connecting to a BACnet network. The default is 02. For additional
information refer to the Communication O&M.

Tech. Config.
Password: 1000

4PT Flow Corr MAC Address
MAC Address  (Range = 02 to 254)
Instance Number
Modbus ID (002)

9.11. INSTANCE NUMBER (BACNET COMMUNICATION OPTION)


When the BACnet Communication option is ordered, the Instance Number Menu allows the user to set a
unique device address when connecting to a BACnet network. The default is 1002. For additional
information refer to the Communication O&M.

Tech. Config.
Password: 1000

4PT Flow Corr Instance Number
MAC Address (Default = 1002)
Instance Number 
Modbus ID (01002)

9.12. MODBUS ID (MODBUS COMMUNICATION OPTION)


When the Modbus Communication option is ordered, the Modbus ID Menu allows the user to set a
unique device address when connecting to a Modbus network. The default is 02. For additional
information refer to the Communication O&M.

Tech. Config.
Password: 1000

4PT Flow Corr Modbus ID
MAC Address (Range = 01 to 254)
Instance Number
Modbus ID  (002)

Paragon Controls Incorporated 34 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

9.13. BAUD RATE (BACNET & MODBUS COMMUNICATION OPTIONS)


The Baud Rate Menu allows the user to set a unique network baud rate. The current BACnet protocol
supports 9.6, 19.2, 38.4 and 76.8 Kbps baud rate. Modbus communications supports 9.6, 19.2, 38.4,
57.6 and 115.2 Kbps baud rate. The default is 38.4 Kbps. For additional information refer to the
Communication O&M.

Tech. Config.
Password: 1000

Baud Rate  Baud Rate
(9.6, 19.2, 38.4, 76.8)

(38.4) Kbps

Paragon Controls Incorporated 35 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

10. WARNING MESSAGES


10.1. INPUT PRESSURE OVERRANGE MESSAGE
If the input pressure exceeds the entered Operating Range Value, the following message will appear on
the display. It will alternate between the process display and the error message until the input falls
below the Operating Range Value.
- Caution -
Input Beyond
Operating Range
Selected

10.2. TRANSDUCER CALIBRATION MESSAGE


If during a transducer zero or span calibration process, the transducer output pressure value measured
exceeds ±20% of the expected value, the following message will appear on the display. Once the Enter
key is pressed, the display returns to the previous calibration menu.
Value entered is
Outside Factory
set limits
(Press Enter)

10.3. OPERATING RANGE MESSAGE


If the new values entered for Temperature Compensation, Area Factor, or Altitude (see Sections 8.7, 9.1,
and 9.6) causes the Operating Range Value to exceed the new calculated Maximum Full Scale Value,
the following message will appear on the display.
Op Range Outside
Allowable Value.
Reset to MAX F.S.
(Press Enter)5

10.4. NEW OPERATING RANGE MESSAGE


If a user enters a new Operating Range Value, the following message will appear on the display
notifying the user that if any 4 PT Flow Correction Values (see Section 9.9) were previously entered,
they will be reset. The message allows the user to confirm that the Operating Range change should be
made. To complete the Operating Range change, the user must use the UP/Down keys to change the
NO to a YES and press the ENTER key.
Value will
Reset 4PT
Flow Correction
Values
Make the Change
(NO)

(Press Enter)

Paragon Controls Incorporated 36 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

11. TROUBLESHOOTING GUIDE


TROUBLESHOOTING TABLE

SYMPTOM SOLUTION

1. No Display or Back Light 1. Verify ON/OFF switch is in ON position

2. Verify correct input power and connection at 3 pin


connector J1

3. Contact Factory

2. Display background is too dark or 1. Adjust RP1 Display potentiometer located in the
characters are too light. upper left hand corner of the board. See
Section 6.3

3. Display does not respond to input 1. Reset the unit by turning the ON/OFF switch OFF
pressure changes and Key pad and back ON.
functions.
2. Contact Factory

4. Display does not respond to input 1. Verify pneumatic input lines are not reversed at the
pressure changes but does respond to MicroTransEQ ports or the sensing element.
Key pad functions.
2. Use a pneumatic gauge to measure the pneumatic
signal input to the MicroTransEQ. Verify the
signals are within the Op. Range Value shown on
the label located on the side of the enclosure.

3. Contact Factory

5. Display does not respond to Key Pad 1. Reset the unit by turning the ON/OFF switch to
functions OFF and then ON.

2. Contact Factory

6. CAUTION INPUT OVERRANGE 1. Verify data on ID Label located on side of


message on Display MicroTransEQ is correct for the application.

2. Remove pneumatic signal lines. If display returns


to 0 reading, use a pneumatic gauge to measure the
pneumatic signal. Verify input signal is equal to or
less then the Op. Range D.P. Value on the ID
Label. If the display does not return to 0, a
pneumatic tube may be plugged by moisture
underneath the PC board. Consult the factory.

3. Verify menu selections are set correctly:


Operating Range, Flow Correction, Temperature
Compensation, Area Factor, and Altitude

Paragon Controls Incorporated 37 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

TROUBLESHOOTING TABLE

SYMPTOM SOLUTION
6. Continued
4. If the Temperature Compensation Option is
installed, verify correct temperature input signal.
Verify that the temperature input is connected
correctly.

5. Contact Factory

7. Incorrect Temperature Reading 1. Verify Temperature Transmitter specifications


match with MicroTransEQ ID Label
(Current/Voltage, Temperature Range)

2. Verify Temperature Transmitter is connected


correctly to the MicroTransEQ (see Section 3.2).

3. Verify Temperature Transmitter signal at the


MicroTransEQ connector J2 is correct.

4. Contact Factory

8. No Output signal or Incorrect Output 1. Verify Process Output S2 & S4 switches are in the
signal. Display is reading correct correct position for the application (see Section 4.1
value. and the figure in Section 3.1.

2. Disconnect Output signal wires and verify output


signal at MicroTransEQ connector J2 is correct.

3. Verify correct Operating Range (see Section 5.2)

4. Perform Output Cal (see Section 9.7)

5. Contact Factory

9. Incorrect Process Output Values after 1. Re-Enter Operating Range Value in Field Menu
changing Area Factor, Altitude, or (see Section 5.2)
Temperature Value. Display readings
are correct. 2. Contact Factory

10. Unstable Display and Process Output 1. Increase Display and Process Filter
at very low flow.
2. Decrease Lockdown Value

3. Increase Lockdown Delay Value

4. Contact Factory

11. “AZ Error” text on display 1. Turn Power Switch S3 Off and On to reset the
AutoZero valve

Paragon Controls Incorporated 38 Revision Level 012


MicroTransEQ Operation & Maintenance Manual

TROUBLESHOOTING TABLE

SYMPTOM SOLUTION
11. Continued
2. Check for a pinched tube beneath the main board.
(Caution: Remove power before removing board)

3. Contact Factory

Paragon Controls Incorporated 39 Revision Level 012


Paragon Controls Incorporated
P.O. Box 99, Forestville, CA 95436
http://www.paragoncontrols.com
Phone 707 / 579-1424
Revision Level 012

You might also like