INSPECTION & TESTING REQUIREMENTS REVISION: 07/25/2018 CODE NUMBER: PAGE:

SAUDI ARAMCO FORM-175 REPLACES: 04/10/2018 IR012000 1 of 2


SCOPE: PIPE & FITTINGS: Fiberglass; RTRP (glass-fiber-reinforced thermosetting resin) & RPMP (glass-fiber-reinforced plastic-mortar) &
Fire-Retardant RTR

TEST AND INSPECTION PER: 01-SAMSS-034 & AWWA C950 & API-15LR & ASTM D-3754, and Specifications As Noted Below.

(1).VISUAL INSPECTION BY BUYER INSPECTION REPRESENTATIVE


(2) REVIEW AND VERIFICATION OF MATERIAL CERTIFICATES AND INSPECTION RECORDS
(3) SUBMISSION OF MANUFACTURING, INSPECTION AND QUALITY RECORDS
0010
0010
***
H X
Pre-Fabrication/Production Requirements
Pre -Inspection meeting
Specification Details / Notes:
Verify Company approval of Manufacturer Inspection and test
Plan

0020 R Product Design Drawing Check for approval by company engineer.

0030 Design Type Tests: Witnessed and certified by independent agency.

0040 R a) Hydrostatic Design Stress & Pressure Ratings Hydrostatic strength shall be determined in accordance with
ASTM D2992 procedure A or B. Pressure rating calculations
per AWWA-C950-01.

0050 R b) Chemical Resistance Determination Shall be carried out per ASTM D3754.

0060 R c) Long Term Ring Bending Strength Shall be determined in accordance with AWWA C950-01.

0070 R d) Flange Pressure Rating Shall be rated and marked in accordance with ASTM D4024.

0080 R e) Joint Integrity Test Shall be in accordance with AWWA C950-01 and ASTM D4161.

0090 R f) Beam Strength Test Shall be in accordance with ASTM D2925.

0100 R Material Test Reports Per the requirements detailed in 01-SAMSS-034.

0020
0010
***
W
In process inspection & test requirement
Pipe Stiffness, Axial Tensile Strength, Hoop Tensile Strength
Specification Details / Notes:
Per 01-SAMSS-034. Shall be determined in accordance with
ASTM D2412 and AWWA C-950-01.(For inspection sampling
requirements see note 3).

0020 W Visual Inspection Shall be conducted for compliance with table 3 of


01-SAMSS-034.(For inspection sampling requirements see
note 4).

0030 W Fire Retardant Additive Volume (%) (For fire-retardant RTR pipe & The vol. ratio of Fire Retardant Additive to resin (% vol.) as
fittings only) specified by the manufactured.(For inspection sampling
requirements see note 4).

0040 W X Hydrostatic Leak Testing Shall be conducted in accordance with AWWA C950-01.(For
inspection sampling requirements see note 4).

IR012000 Continued...
INSPECTION & TESTING REQUIREMENTS REVISION: 07/25/2018 CODE NUMBER: PAGE:
SAUDI ARAMCO FORM-175 REPLACES: 04/10/2018 IR012000 2 of 2
(1).VISUAL INSPECTION BY BUYER INSPECTION REPRESENTATIVE
(2) REVIEW AND VERIFICATION OF MATERIAL CERTIFICATES AND INSPECTION RECORDS
(3) SUBMISSION OF MANUFACTURING, INSPECTION AND QUALITY RECORDS
0050 W Threads Shall be per ASME B1.20.1 conforming to ASME B31.3.

0030
0010
***
H
Final inspection & test requirements
Dimensions and surface finish
Specification Details / Notes:
Shall be measured in accordance with ASTM D3567, ASME
B46.1.(For inspection sampling requirements see note 4).

0020 H FR layer thickness measurement (For fire-retardant RTR pipe & Thickness shall not be less than the value listed in the
fittings only) limitations under 9COM 6000017130 vendor approval.(For
inspection sampling requirements see note 4).

0022 H Barcol Hardness (For fire-retardant RTR pipe & fittings only) Barcol Hardness of the top coatShall not be less than 70.(For
inspection sampling requirements see note 4).

0024 W Special Fabrications (Spools) Shall have a tolerance of + 6 mm, unless otherwise defined in
Purchase Order.(For inspection sampling requirements see
note 4).

0030 W Flange Bolt Hole Sizing Shall comply with ASME B16.5 up to 600 mm NPS and AWWA
C207 or MSS SP-44 for larger than 600 mm NPS.(For
inspection sampling requirements see note 4).

0040 W Marking & Identification Tagging Shall be permanent including markings specified in
01-SAMSS-034.(For inspection sampling requirements see
note 4).

0050 W Crating and End Protectors Per 01-SAMSS-034.(For inspection sampling requirements see
note 4).

0060 R Potable Water Certification Shall be in accordance with NSF 14 and or NSF 61 or approved
equal (as approved Standard Chairman)

0070 R Fire Water Certification Per Factory Manual (FM) or approved equal agency (as
approved by the Standard Chairman)

0080 R X Product test certificates

0090 R X Certificate of Compliance

Notes:
(1) Refer detailed instruction sheet SA175 form IR000003 of inspection requirement for ideal use of this form.
(2) Random witnessing required only, unless otherwise specified by the responsible Inspection Office.
(3) One inspection sampling test for each 100 lengths of pipe produced or from each manufacturing run, whichever provides the most frequent
sampling of each class and size.
(4) The inspection sampling test shall be 10% of the offered materials for inspection.

End of IR012000