Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Data sheet 3VA5220-6EF31-0AA0

circuit breaker 3VA5 UL frame 250 breaking capacity class H 65kA


@ 480V 3-pole, line protection TM240, ATAM, In=200A overload
protection Ir=160A...200A short-circuit protection Ii=5...10 x In without
connection

Model
Product brand name SENTRON
Product designation Molded-case circuit breaker
Product designation / according to UL file HFAS
Product version System protection
Design of the load switch / acc. to UL 489 / Heating, Yes
Air Conditioning, and Refrigeration circuit breaker
(HACR Type)
Design of the overcurrent release TM240
protection function of the overcurrent release LI
Number of poles 3

General technical data


Rated insulation voltage Ui 800 V
Max. rated operational voltage Ue with AC 50/60Hz 690 V
Max. rated operational voltage Ue with DC 750 V
Power loss [W] / maximum 42.5 W
Active power loss / for rated value of the current / at 14.17 W
AC / in hot operating state / per pole
Mechanical service life (switching cycles) / typical 20 000

3VA5220-6EF31-0AA0 Subject to change without notice


Page 1/8 08/05/2020 © Copyright Siemens
Electrical endurance (switching cycles) / at AC-1 / at 8 000
380/415 V 50/60 Hz
Electrical endurance (switching cycles) / at AC-1 / at 4 000
690 V 50/60 Hz
Electrical endurance (switching cycles) / at 480 V / at 8 000
50/60 Hz
Electrical endurance (switching cycles) / at 600 V / at 4 000
50/60 Hz
Neutral conductors / upgradeable/retrofittable No
Ground fault monitoring version Without
Product function
● communication function No
● other measurement function No

Current
Marking / acc. to UL 489 / 100%-rated breaker No
Max. rated operational current of the frame size 250 A
Rated continuous current Iu 200 A
Operating current
● at 40 °C 200 A
● at 45 °C 200 A
● at 50 °C 200 A
● at 55 °C 194 A
● at 60 °C 190 A
● at 65 °C 184 A
● at 70 °C 176 A

Switching capacity according to IEC 60947


Switching capacity class of the circuit breaker H
Maximum short-circuit current breaking capacity (Icu)
● at 240 V 100 kA
● at 415 V 70 kA
● at 690 V 10 kA
Operational short-circuit current breaking capacity
(Ics)
● at 240 V 100 kA
● at 415 V 70 kA
● at 690 V 10 kA
Short-circuit current making capacity (Icm)
● at 240 V 220 kA
● at 415 V 154 kA
● at 690 V 17 kA
Design of short-circuit protection For switching power values in DC networks, see the 3VA molded
case circuit breaker device manual; link to be found under Service
& Support in the last chapter

3VA5220-6EF31-0AA0 Subject to change without notice


Page 2/8 08/05/2020 © Copyright Siemens
Switching capacity according to UL 489
Breaking capacity current
● at 240 V 100 kA
● at 480 V 65 kA
● at 600 Y/347 V 25 kA

Adjustable parameters
Adjustable response value current / lg min. 140 A
Adjustable response value current / lg min. 200 A
Adjustable response value current / li min. 1 000 A
Adjustable response value current / li max. 2 000 A
Ground fault protection / tripping switchable / No
I2t=ON/OFF

Mechanical Design
Height [in] 7.3 in
Height 185 mm
Width [in] 4.1 in
Width 105 mm
Depth [in] 3.3 in
Depth 83 mm

Connections
Arrangement of electrical connectors / for main Without connection
current circuit
Type of electrical connection / for main current circuit Without

Auxiliary circuit
Number of CO contacts / for auxiliary contacts 0

Accessories
Product extension / optional / motor drive Yes

Environmental conditions
Protection class IP / on the front IP40
Ambient temperature
● during operation / minimum -25 °C
● during operation / maximum 70 °C
● during storage / minimum -40 °C
● during storage / maximum 80 °C

Certificates
Reference code / acc. to DIN EN 81346-2 Q
Certificate of suitability / as approval for NAVAL (no No
combat vessels) / Supplement SB

3VA5220-6EF31-0AA0 Subject to change without notice


Page 3/8 08/05/2020 © Copyright Siemens
General Product Approval EMC Declaration of
Conformity
Miscellaneous

Shipping Approval other


Miscellaneous

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/lowvoltage/catalogs
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3VA5220-6EF31-0AA0
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3VA5220-6EF31-0AA0
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3VA5220-6EF31-0AA0
CAx-Online-Generator
http://www.siemens.com/cax
Tender specifications
http://www.siemens.com/specifications

3VA5220-6EF31-0AA0 Subject to change without notice


Page 4/8 08/05/2020 © Copyright Siemens
107

[4.21]

93

[3.66]

9 83 35

[0.35] [3.27] [1.38]

35 35 18 17.5

[1.38] [1.38] [0.71] [0.69]

20 4

[0.79] [0.81] [0.16]


20.5

[1.11]
28.3

[1.22]
31
1 3

66.6

[2.62]
[3.19]
81
[2.76]
70

133

[5.24]
185

144

123
[7.28]

[5.67]

[4.84]

[1.02]
26.1
2 4
[1.11]

[1.22]
31
28.3
[0.81]
20.5

4.7

52.5 18 [0.19]

[2.07] [0.71]

105 71.8

[4.13] [2.83]

83

[3.27]

19

[0.75]

38

[1.50]

3VA5220-6EF31-0AA0 Subject to change without notice


Page 5/8 08/05/2020 © Copyright Siemens
-Q 1 3 5

I> I> I>

2 4 6

3VA5220-6EF31-0AA0 Subject to change without notice


Page 6/8 08/05/2020 © Copyright Siemens
-CB
SIEMENS

1 2

3 4

5 6

3VA5220-6EF31-0AA0 Subject to change without notice


Page 7/8 08/05/2020 © Copyright Siemens
last modified: 07/18/2020

3VA5220-6EF31-0AA0 Subject to change without notice


Page 8/8 08/05/2020 © Copyright Siemens

You might also like