1 April 2020 NBTC-TS/FO-ML24 Rev.

00

Naser M. AL-Baddah & Partner General Trading & Contracting Co. W.l.l
Technical Services Division
Block-5, Shuaiba Industrial Area-P.O.Box 9088,Ahmadi 61001 Kuwait
Tel:(+965) 186 7777 Ext: 4252/4262 Fax:(+965) 2228 4444 - E-mail:tech.services@nbtc-kuwait.com,Web:www.nbtcgroup.com

CHEMICAL ANALYSIS REPORT ( PMI / Spectro - OES )


Report No. : TSD / CMA / 0645 Date of Receipt : 20-Oct-2020
Customer Name
: Wuhan lingyun Building Decoration Engineering Co,.LTD Date of Test : 24-Oct-2020
& Address
Client : Ministry of Public Works / PIZZA ROTTI Job Order No. : TSD / 2029 / 20
Project No. /
Project Name : Kuwait New Maternity Hospital Project : SPA - 235
Contract No.
Material : ASTM A 36 Carbon Steel Plate

Description : Chemical Analysis ( Spectro ) Testing of CS Plate

REFERENCE

Equipment : PMI - Master Smart Calibration Certificate No. : HST-01/CR/031-2020

Equipment Sl.No. : 57-T0102 Calibration Date : 15-Jun-20

Make / Model : Hitachi High-Tech Analytical Sciences Calibration Due Date : 04-Dec-20

Ref.Standard : N/A

Ref.Specification : E 415 / A 36 Procedure No. : WI -09

Sample / Specimen
: A 5462 CMA - 1
Identification
TEST DETAILS
Acceptable Measured Value %
Serial No. Elements Remarks
Value ( Max ) 1

1 C 0.250 0.156

2 Mn - 0.810

3 P 0.040 0.013

4 S 0.050 0.010

5 Si 0.400 0.193

6 Cu 0.200 0.015

Authorized Signatory Witnessed By Client

Muhammad Ali

NBTC-TSD
Date: Date: Date:
Test results pertain to samples received at NBTC Lab

1 of 1