DATA SHEET

REVERSIBLE AIR-TO-
FGAH 4060 - 4120 BG2 (.SL/.HE)
WATER HEAT PUMP

Table of contents

Type code ................................................................... 1


Unit description ........................................................... 2
Options and accessories ............................................ 3
Defrosting operation ................................................... 9
Operating limits ........................................................... 9
General Data ............................................................ 11
Noise levels .............................................................. 14
Footprint .................................................................... 15
Anti-vibration mounts ................................................ 15
Electrical data ........................................................... 16
Terminal scheme ...................................................... 17
Order-related documentation .................................... 17
Fig. 1: Unit view (example version)

Type code
FG A H 4 060 B G 2 _
Number of compressors
Operating mode

Supply voltage
Capacity stage
Condensing

Unit model
Refrigerant
Unit series

Series

FG FläktGroup Series
Air cooled
A
(outdoor installation)
H Reversible heat pump (heating/cooling)
4 4 Scroll compressors
060-
060, 070, 080, 090, 100, 110, 120
120
B B unit series
G Refrigerant R-454B
2 400 V / 3~ / 50 Hz / PE
_ Standard
.SL SL unit - especially quiet version
.HE HE unit - especially efficient design
Fig. 2: Explanation of unit type code
Reversible air-to-water heat pump
FGAH 4060 - 4120 BG2 (.SL/.HE)

Unit description
FläktGroup reversible air-to-water heat pump with scroll compressors
- Air-to-water model for outdoor installation
- For seasonal switch-over of the operating modes heating or cooling
- ErP-compliant according to 813/2013 EU
- High energy efficiency at full and part-load mode
- Refrigerant R-454B (GWP 466), safety class A2L according to ISO 817
- 7 unit sizes available
- 3 unit models:
- Standard design, electronic expansion valves optional, increased SCOP values through optional EC
fans
- SL version with a noise reduction of approx. 9 dB(A), electronic expansion valves optional, increased
SCOP values through optional EC fans
- HE version with particularly high SCOP values by using enlarged heat exchanger surfaces and EC fans;
electronic expansion fans as standard, noise reduction of approx. 5 dB(A)
- Range approx. from 142 to 312 kW cooling capacity and 151 to 337 kW heating capacity
- Built-in pump or double pump (redundancy) optionally available, models with standard delivery head or
increased delivery head, as well as on/off controlled or variable speed controlled
- Units with built-in pump or pumps are optionally available with built-in buffer tank
- 2 refrigerant circuits with 2 compressors each as tandem unit
- 4 quiet, low-vibration, fully hermetic scroll compressors
- Air-side heat exchanger with Cu/Al fins
- Optionally with coated fins or fully coated
- Optional with protective grille (Option .I04)
- Plate heat exchanger as water-side heat exchanger, incl. antifreeze heating for unit stand-by without glycol
at ambient temperatures ≥ -10 °C (standard and SL units)
- Shell and tube heat exchanger as water-side heat exchanger, incl. antifreeze heating for stand-by without
glycol at ambient temperatures ≥ -10 °C (HE units)
- Direct driven axial fans with protection against tampering
- Water outlet temperature in cooling operation -8 to +15 °C (partly depending on outdoor temperature)
- Water outlet temperature in heating mode from +24 up to +52 °C (standard and SL units) or up to +55 °C
(HE units) (Depending on the selected medium and outside temperature)
- Air inlet temperature in cooling operation possible from min. -10 °C to max. +46 °C depending on selected
option (depending on selected medium and water temperature; see operating limit diagram)
- Air intake temperature in heating mode down to -15 °C possible with water temperatures up to 40 °C
(standard and SL units) or 42 °C (HE units); see application limits diagram
- If the temperature falls below the minimum air inlet temperature or exceeds the maximum air inlet
temperature, the unit must be disabled
- Automatic defrost function in heating operation by reversing the refrigeration circuit
- Built-in electrical heating elements at the bottom of the air-side heat exchanger to support the defrosting
process
- Power supply 400V / 3~ / 50 Hz / PE
- Numbered connecting terminals
- Automatic circuit breaker for load and control circuit
- Pump relay and, if necessary, 0-10 V output for controlling one or two on-site water pump(s) for units
without built-in pump(s) (optional)
- FläktGroup controller
- Compact display with 8-line display
- Water-inlet temperature control as standard
- Setpoint shift with 4-20 mA signal as standard
- Demand limit contact to reduce electrical power consumption by deactivating compressors or their capacity
stages (optional)
- Seasonal heating/cooling changeover via external digital input or optionally via the BMS
- Flow monitor for on-site installation available as accessory (Option .I10/ I.67)
- Water filter 4" for on-site installation available as accessory (option .I72)
- On-site pipe expansion joints must be installed to decouple vibrations, noise transmission and linear
expansion
- All units of the FGAH 4060-4120 BG2(.SL/.HE) series are Eurovent certified

Page 2/20 PR-2020-1029-GB • R1-04/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.
Reversible air-to-water heat pump
FGAH 4060 - 4120 BG2 (.SL/.HE)

Options and accessories

Mechanics accessories
FGPE modules - Built-in pump module
Consisting of one pump or two parallel pumps with redundancy function. The
water connections are equipped with internal screw threads.
Other components are:
- Steel pipes, water vapour proof insulated
- Pump protection with overcurrent relay
- Pump control with lead time and overrun time
- Prevention of pump blockages through regular activation
Pump modules assembled and wired by the manufacturer result in significant
savings in installation costs.
Pumps or two parallel pumps with standard delivery head or increased delivery
head are available. All pumps are designed as on/off pumps or speed controlled
with inverter.
Options - Built-in buffer tank to increase the water volume of the system
.M03/ .M04/ .M06 This results in considerable savings in installation costs. Other components are:
- Expansion tank (dimensioned for internal buffer tank)
- Safety valve
- Inlet, air vent and drain valve
- Manometer
.M03 400 L tank for unit sizes 4060
4060 .SL

.M04 500 L Tank for unit sizes 4070-4100


4070-4080 .SL
4060-4070 .HE
.M06 850 L Tank for unit sizes 4110-4120
4090-4120 .SL
4080-4120 .HE
Only for units with built-in pumps

Installation of accessories
Option .I01 - Spring anti-vibration mounts
Anti-vibration mounts with spring elements for reduction of vibration transfer
(enclosed).
Option .I02 - Rubber anti-vibration mounts
Anti-vibration mounts with rubber elements to minimize vibration transmission
(supplied separately).
FläktGroup recommends the use of rubber anti-vibration isolators. Alternatively,
spring anti-vibration mounts can be used depending on the project specifications.
Option .I04 - Protection grille for air-cooled heat exchanger
Protection grille on external sides of the air-cooled heat exchanger for protecting
fins against damage due to shipping and weather.
Option .I06 - External evaporator water connections
Installation of the water connections up to the outside of the unit for easier on-site
(only for units without connection. Frost protection must be provided on-site by the customer!
pumps)

PR-2020-1029-GB • R1-04/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 3/20
Reversible air-to-water heat pump
FGAH 4060 - 4120 BG2 (.SL/.HE)

Option .I09 or - Cu/Al heat exchanger with anti-corrosive coating for the fins
.I52 for HE units or Anti-corrosion coating for fins of Cu/Al heat exchanger. The use of chemical
.I23 for SL units cleaning methods and protective paint coating made of polyester resin ensures
the following characteristics for the fins:
- Corrosion resistance in a salt-spray test according to ASTM B117 for at least
1000 hours
- UV durability
Option .I18 or - Cu/Al heat exchanger with polyurethane paint coating
.I51 for HE units or Cu/Al heat exchanger with polyurethane paint. The entire heat exchanger
.I22 for SL units receives protective coating using polyurethane paint, so that the following
qualities are ensured:
- Corrosion resistance in a salt-spray test according to ASTM B117 for at least
4000 hours
- UV durability
Option .I58 - Display protection
Option .I10 /.I67 - Flow switch (supplied separately)
with paddle for installation in hydraulic circuit at chilled water outlet.
The on-site installation and wiring of the flow switch is a prerequisite for warranty
claims!
Option .I67 Type 1 (device size 4060-4090)
Option .I10 Type 2 (device size 4100-4120)
Option.I72 - Water strainer for installation in the hydraulic circuit at the unit inlet
(supplied separately)
A water strainer must be installed before the direct inlet into the heat exchanger(s)
to protect the heat exchanger(s) from dirt and deposits. The "Y-type" water
strainer has a mesh width of 0.9 mm. The filter insert can be removed without
difficulty and cleaned for maintenance purposes without dismantling the valve
body.
Option .I72 Filter 4" (unit size 4060-4120)

Refrigeration circuit
accessories
Option .R12 or .R11 - Electronic expansion valves (EEV)
for standard devices Instead of thermal expansion valves (TEV), one electronic expansion valve is
with option .E37 used per refrigeration circuit. Additionally, the according hardware for the control
of the EEVs is included. EEVs reduce the superheat of the refrigerant compared
(only for standard and to TEVs, resulting in energy savings.
SL devices)
Included as standard for HE devices.
Option .R02 - Shut-off valves for compressor, suction side
Service shut-off valve assembled for fast and easy maintenance
Option .R10 - Shut-off valves for compressor pressure side
Service shut-off valve assembled for fast and easy maintenance
Option .R01 - Solenoid valves in the liquid lines
Prevents refrigerant migration during standby phases when operating in winter.
(only for standard and
SL devices) Required for devices with EEV (option .R11/ .R12).
Included as standard for HE units.
Option .R13 - High and low pressure gauges
Refrigerant gauge for high and low pressure side for reading off current operating
pressures.

Page 4/20 PR-2020-1029-GB • R1-04/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.
Reversible air-to-water heat pump
FGAH 4060 - 4120 BG2 (.SL/.HE)

Option .R19 - Safety valve in double model for high and low pressure side
Two safety valves are connected via a changeover valve on the high and low
pressure side each. By using a changeover valve a trouble-free and fast
replacement of safety valves without refrigerant loss is possible for maintenance
and service jobs.
Mandatory for devices with option .C02 (UDT / delivery to Poland).

Electrical accessories
Option .E02 - Cabling in colour sequence: L1: brown L2: black L3: grey
The wiring of the load circuit for the unit is carried out in the following colour
sequence:
L1: brown, L2: black, L3: gray
This colour sequence is frequently requested in Great Britain.
Option .E06 - Soft starter for the compressors
Cannot be combined with reactive current compensators
Option .E13 /.E11 - Frost protection heating for operation without glycol
suitable for stand-by units without glycol at ambient temperatures ≥ -10 °C.
Standard for units without pumps and without buffer tank
.E13 Units with pump(s) without buffer tank
.E11 Units with pump(s) and buffer tank
Option .E37 - Standard operating range for cooling operation
Operation up to an outside temperature of ≥ +5 °C based on water outlet
(only for standard temperatures of ≥ 5 °C. Refer to the operating limit diagrams for the operating
units) limits.
Option .E38 - Standard operating range for cooling operation
Operation up to an outside temperature of ≥ -10 °C based on water outlet
(only for SL units) temperatures of ≥ 5 °C. Refer to the operating limit diagrams for the operating
limits.
Option .E39 - Extended operating range for cooling operation
Operation up to an outside temperature of ≥ -10 °C based on water outlet
(only for standard temperatures of ≥ 5 °C. Refer to the operating limit diagrams for the operating
devices) limits.
Option .E48 or .E49 - Extended operating range for cooling operation
for SL units For operation with water outlet temperatures ≥ -5 °C and < +5 °C for outside
temperatures until ≥ -10 °C. Refer to the operating limit diagrams for the exact
application limits.
Option .E50 or .E53 - Extended operating range for cooling operation
for SL units For operation with water outlet temperatures < -5 °C for outside temperatures until
≥ -10 °C. Refer to the operating limit diagrams for the exact application limits.
Option .E81 or .E82 - EC fans
for SL units Continuously variable EC fans increase the SCOP values of the unit. For cooling
operation with water outlet temperatures from -8 to +15 °C for outside
temperatures down to -10 °C. Refer to the operating limit diagrams for the exact
application limits.
EC fans are included as standard on HE units.
Option .E79 - Variable setpoint temperature using outdoor temperature
The setpoint temperature can be controlled in a variable manner depending on
the outdoor temperature.

PR-2020-1029-GB • R1-04/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 5/20
Reversible air-to-water heat pump
FGAH 4060 - 4120 BG2 (.SL/.HE)

On request - Compensation of reactive current for individual compressor motors


Individual PFC capacitors are connected in parallel to each compressor motor in
order to reduce the idle current to a minimum and to improve the cos-phi of the
unit.
Cannot be combined with soft starters (option .E06).

For units without built-in pumps, one of the four following option numbers must be ordered to define the hardware
control of the on-site pump:
Option .E04 - Relay for actuating one on-site chilled water pump
An on/off pump provided on-site is controlled via a floating contact.
Option .E34 - Relay for actuating two parallel on-site chilled-water pumps
Two on-site on/off pumps are controlled via two floating contacts. To increase
system availability, the pumps are alternately activated by the controller; if one
pump fails, the system automatically switches to the other pump permanently.
The pumps must be fitted on-site with non-return valves.
Option .E30 - 0-10 V signal for controlling a customer supplied inverter chilled-water
pump
A speed-controlled inverter pump provided on-site is controlled by a 0-10 V signal.
In addition, there is a floating contact for enabling the pump.
Option .E31 - 0-10 V signal for controlling two parallel inverter chilled-water pumps
provided on-site
Two on-site speed-regulated inverter pumps are controlled by a common 0-10 V
signal. In addition, there are two floating contacts for activating the pumps. To
increase system availability, the pumps are alternately activated by the release
contact of the controller; if one pump fails, the system automatically switches to
the other pump permanently. The pumps must be fitted on-site with non-return
valves.

Accessories for controls


Option .E03 - Compressor operation signal contacts
Floating contacts for status indication of each respective compressor.
Option .E22 - 2nd setpoint via on-site normally open contact
External switch-over between two setpoint values set for unit by closing an on-site
floating contact. Raising the setpoint, e.g. during night operation, can realize
significant savings potential.
For devices with option .E22, the floating setpoint adjustment by means of a
4-20 mA signal cannot be used.
Option .E23 - Demand limit / load limitation
Reduction of electrical power consumption by deactivating compressors or their
speed (demand limit switch) by opening an on-site floating contact.
Option .E19/E20 - Second remote control connection for remote monitoring and control
Up to 10 units in the same controller family can be connected to an additional
remote control
Option .E19 for remote controls up to 200 meters away
Option .E20 for remote controls up to 500 meters away

Page 6/20 PR-2020-1029-GB • R1-04/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.
Reversible air-to-water heat pump
FGAH 4060 - 4120 BG2 (.SL/.HE)

Serial card for - Serial interface board for connecting the unit to a building management
connection to a system (BMS)
building management
system or for The following protocols are used to transmit digital and analog values:
master/slave control – Retrieval of alarm signals
– Retrieval of temperature and pressure values provided by the controller
– Operating status of individual compressors
– Enabling the unit
– Setpoint shift
– Heating / cooling changeover

Option .E14 - Modbus (RS485),


Built-in Modbus interface for connection to the building management system or for
internal group communication with a sequencer
Option .E15 - LonWorks® ,
Built-in LonWorks interface for connection to the building management system
Option .E16 - BACnet via IP,
Built-in BACnet via IP interface for connection to the building management system

Option .E17 - BACnet via MS/TP RS485,


Built-in BACnet via MS/TP RS485 interface for connection to the building
management system
Option .E18 - Sequencer without connection to a BMS:
Upstream master/slave control. Up to a maximum 5 units of the FläktGroup
controller family can be used in a hydraulic circuit and connected to a sequencer.
The sequencer is supplied in a separate switch cabinet with two temperature
sensors that must be installed in a common water inlet and outlet. Depending on
the water inlet temperature, individual capacity steps or units are switched on or
off. Every unit needs a serial card of Modbus type (option .E14) in order to
communicate with the sequencer and its own chilled-water pump that also must
be controlled by the chiller/heat pump.
Option .E24 - Sequencer with connection to a BMS via Modbus protocol
Option .E25 - Sequencer with integration to a BMS via LONWORKS® protocol
Option .E26 - Sequencer with integration to a BMS via BACnet over IP.
Option .E27 - Sequencer with integration to a BMS via BACnet protocol MS/TP RS485

PR-2020-1029-GB • R1-04/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 7/20
Reversible air-to-water heat pump
FGAH 4060 - 4120 BG2 (.SL/.HE)

For units with built-in inverter pumps or on-site inverter pump(s), one of the following three option numbers must
be ordered to define the software type of pump control:
Option .E84 - Setting constant pump speed
on the unit controller for pumps with variable speed. The speed is fixed once
(only when using during commissioning, so that the required water volume flows through the heat
inverter pumps) exchanger.
Option .E85 - VPS-D control
In order to exploit further potential energy savings, the speed of the on-site or
(only when using installed inverter pump(s) is reduced to 50% in part-load mode. As far as possible,
inverter pumps) the Delta T at the evaporator is kept constant on the water side during part-load
mode. VPS-D is intended for systems without system separation, a single-circuit
buffer storage tank and a distributor with overflow to the collector. For the
consumer circuits, additional on-site pumps with on-site control are required,
which are usually designed as pressure-controlled inverter pumps in conjunction
with 2-way valves at the consumers. Included in delivery are two separately
supplied temperature sensors as well as an extended controller hardware with the
required connection points. The temperature sensors must be installed on-site at
the water inlet to the manifold and in the overflow pipe in immersion wells with
heat-conducting paste. Measurement at the temperature sensors has a higher-
ranking influence on the pump speed and always ensures an overflow from the
inlet to the outlet.
It should be noted that
- the hydraulic system is designed so that the primary circuit pump(s) can always
deliver at least 50% of the water volume. If this value is not reached, the unit will
malfunction.
- the overflow line is designed for 50% of the nominal water flow rate
- the flow monitor is calibrated to a value of 35% of the nominal water volume
flow. For this purpose, the maximum pipe cross-section in the area of the flow
monitor must be observed in order to ensure proper functioning.
Observe the separate planning instructions and hydraulic diagrams for VPS-D
systems.
Option .E86 - VPS-E control
In order to exploit further potential energy savings, the speed of the on-site or
(only when using installed inverter pump(s) is reduced to 50% in part-load mode. As far as possible,
inverter pumps) the Delta T at the evaporator is kept constant on the water side during part-load
mode. VPS-E is intended for systems with system separation (plate heat
exchangers) and a single-circuit buffer tank on the primary side. For the consumer
circuits on the secondary side of the system separation (plate heat exchanger),
one or more additional on-site pumps with on-site control are required, which are
usually designed as pressure-controlled inverter pumps in conjunction with 2-way
valves at the consumers. Alternatively, the system can be used for single circuit
systems with a single-circuit buffer and a single consumer with 3-way valve. A
corresponding software for the function is included in the scope of delivery.
It should be noted that
- the hydraulic system is designed so that the primary circuit pump(s) can always
deliver at least 50% of the water volume. If this value is not reached, the unit will
malfunction.
- the flow monitor is calibrated to a value of 35% of the nominal water volume
flow. For this purpose, the maximum pipe cross-section in the area of the flow
monitor must be observed in order to ensure proper functioning.
Observe the separate planning instructions and hydraulic diagrams for VPS-E
systems.

Page 8/20 PR-2020-1029-GB • R1-04/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.
Reversible air-to-water heat pump
FGAH 4060 - 4120 BG2 (.SL/.HE)

Other accessories
Option .O01 - Packaging in timber crate and nylon foil
The unit is supplied for shipping in a timber crate and is additionally shrink-
wrapped in nylon foil to protect it from the weather and dirt.
Option .O11 - Packing of the unit with nylon cover
The unit is shrink-wrapped in nylon foil for shipping and storage to protect it from
weather and dirt.
Option .O27 - Refrigerant leak detection (Alarm)
The compressor section is monitored for leaking refrigerant. A detected refrigerant
leak is signaled by a fault message from the device controller.
Option .O28 - Refrigerant leak detection (compressor switch off)
The compressor section is monitored for leaking refrigerant. In the event of
refrigerant leakage, the compressor is switched off and an alarm signal is
triggered by the controller.
Option .O30 or .O32 - Reinforced thermal insulation for the water-side heat exchanger
for SL devices or To reduce heat losses for units that are operated in heating mode at outdoor
.O24 for HE devices temperatures below -10 °C or to avoid condensate formation for units with chilled
water outlet temperatures below 0 °C in chiller mode.

Defrosting operation
In heating operation, the air-side heat exchanger acts as an evaporator so that heat is extracted from the ambient
air. Depending on the air humidity, a considerable amount of condensate is produced. At evaporation
temperatures below the freezing point, ice forms on the heat exchanger fins as a result. To defrost the ice layer, the
heat pump switches to a reverse circuit as soon as the controller has detected a certain amount of ice formation.
During the defrosting phase, the medium is briefly cooled instead of heated. Please therefore observe the minimum
system charges specified, so that in addition to adhering to the minimum running period of the compressors, it is
also ensured that the medium does not cool down too much during the defrosting phase, thus excluding any loss of
comfort.

Operating limits
On the water side, the operating limits according to Table 1, and on the air and water side, the limits of the selected
options according to the following operating limit chart must be observed. The specified limits change when using
glycol in the range up to approx. -5 K. The exact operating limits are output in the selection software.
Tab. 1: Operating limits water (glycol) circuit

Min Max
Water inlet (cooling) [°C] -5 23
Water outlet (cooling) [°C] -8 15
dT (for water outlet >5 °C) (cooling) [K] 4 8
dT (for water outlet ≤5 °C) (cooling) [K] 3 5
Water inlet (heating) [°C] 18 47 *) or 52 °C **)
Water outlet (heating) [°C] 24 50 *) or 55 °C **)
dT (heating) [K] 3 8
Glycol concentration [%] 50
*) Applies to standard units without EC fan, as well as SL units with or without EC fan
**) Applies to standard units with EC fan, as well as all HE units.

PR-2020-1029-GB • R1-04/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 9/20
Reversible air-to-water heat pump
FGAH 4060 - 4120 BG2 (.SL/.HE)

50 50

40 40

30 30 Operation with
increased sound
.E37
level
20 20
.E38
10 10
tAir,suction (cooling operation)

tAir,suction (cooling operation)


0 .E39 0
.E48 .E49
-10 -10
.E50 .E53
-20 -20
-10 -5 0 5 10 15 20 -10 -5 0 5 10 15 20
tWater, outlet (cooling operation) tWater, outlet (cooling operation)

Fig. 3: Application range in cooling mode (standard units without EC fans) Fig. 4: Application range in cooling mode (SL units without EC fans)

50 50

40 40

30 30 Operation with
increased sound
level
20 20

10 10
tAir,suction (cooling operation)

tAir,suction (cooling operation)

0 0

-10 -10

-20 -20
-10 -5 0 5 10 15 20 -10 -5 0 5 10 15 20
tWater, outlet (cooling tWater, outlet (cooling
operation) operation)

Fig. 5: Application range in cooling mode (standard units with EC fans option Fig. 6: Application range in cooling mode (SL units with EC fans option .E82)
.E81, and all HE units)

40 40

30 30

20 20

10 10
tAir,Intake (heating operation)

HE units
tAir,Intake (heating operation)

0 0 only

-10 -10

-20 -20
20 25 30 35 40 45 50 55 60 20 25 30 35 40 45 50 55 60
tWater,outlet (heating tWater,outlet (heating
operation) operation)

Fig. 7: Application range for heating operation (standard units without EC fans, Fig. 8: Application range for heating operation (standard units with EC fans
as well as SL units with or without EC fans Opt. E.82) option .E81, as well as all HE units)

Notices
For operational reasons, water at evaporator outlet temperatures below 5 °C must be protected from freezing by adding glycol.
FläktGroup recommends the use of at least 30% ethylene glycol.

The unit must be protected from freezing at ambient temperatures lower than 5 °C. Frost protection heating for the water-side heat exchanger is provided as standard
for this purpose. The frost protection heaters are designed for outdoor temperatures down to -10 °C. In installation locations where colder outdoor temperatures may
occur, the unit must be configured with glycol.

Page 10/20 PR-2020-1029-GB • R1-04/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.
Reversible air-to-water heat pump
FGAH 4060 - 4120 BG2 (.SL/.HE)

General Data
Tab. 2: General data for standard units with 4 compressors

Unit type FGAH ### BG2 4060 4070 4080 4090 4100 4110 4120
6)
Capacity data (catalog)
Cooling capacity 1) Qe [kW] 153.7 178.4 202.5 235.4 263.2 286 306.5
Power consumption 5) P [kW] 53.5 63.3 71.1 83.4 93.3 99.8 108.6
EER 2.87 2.82 2.85 2.82 2.82 2.87 2.82
Chilled water flow rate Ve [m³/h] 26.5 30.7 34.9 40.5 45.3 49.2 52.8
Pressure drop evaporator ∆pe [kPa] 39.2 39.8 41.3 45.3 45.4 40.3 46.2
Heating performance data (catalog) 6)
Heating capacity 7) Qe [kW] 163.1 189.6 216.6 255 281.5 304.5 323.9
Power consumption 5) P [kW] 52.0 61.1 69.4 82.3 90.5 97.3 103.8
COP 3.14 3.10 3.12 3.10 3.11 3.13 3.12
Warm water flow rate Ve [m³/h] 28.3 33.0 37.7 44.3 48.9 52.9 56.3
Pressure drop condenser ∆pc [kPa] 45 45.8 48.2 54.2 52.9 46.5 52.6
ERP conformity
SCOP (813/2013 EU) 4) 3.51 3.54 3.54 3.46 3.51 3.52 3.47
ηS (813/2013 EU) 4) [%] 137 138 138 135 137 138 136
Meets ErP requirements       
Cooling performance values according to EN14511-3:2011
Cooling capacity 1) Qe [kW] 153.3 178 202.2 235.1 262.8 285.7 306.1
EER 2.83 2.78 2.81 2.79 2.79 2.83 2.79
Heating performance values according to EN14511-3:2011
Heating capacity 7) [kW] 163.4 190 216.9 255.4 281.9 304.9 324.4
COP 3.10 3.07 3.08 3.06 3.07 3.09 3.08
Controls Compact display / controller with TA Software
Fans Axial fans
Number of fans n 4 4 4 6 6 6 6
Total air volume flow [m³/h] 70128 82512 80280 105192 105192 117036 117036
Compressors Scroll compressors
Number of compressors 4 4 4 4 4 4 4
Number of refrigeration circuits 2 2 2 2 2 2 2
Minimum part-load speed [%] 25 25 25 25 25 25 25
Heat exchanger, water side
Min. water flow rate Ve,min [m³/h] 16.3 19.0 21.6 25.1 28.1 30.6 32.8
Max. water flow rate Ve,max [m³/h] 46.1 53.5 60.7 62.0 68.8 68.8 68.8
Max. operating pressure2) pmax [bar] 10 10 10 10 10 10 10
On-site minimum system content [l] 400 465 528 613 685 745 798
Water charge of heat exchanger [l] 8.6 10.5 12.3 15.1 18.9 23 23
Heat exchanger connection 3“ 3“ 3“ 3“ 3“ 4“ 4“
Refrigeration circuit charge
Refrigerant R454B (GWP 466) 3) [kg] 32.2 50.0 71.2 71.3 74.5 93.6 93.6
Oil charge [kg] 10.8 10.8 10.8 16.0 21.2 21.2 21.2
Power supply line 8)
Max. cable cross-section, round [mm²] 20 x 5 20 x 5 20 x 5 20 x 5 2 x 25 x 5 2 x 25 x 5 2 x 25 x 5
Max. cable cross-section, 120 120 120 120 240 240 240
[mm]
rectangle
Dimensions and weight
A (length) [mm] 3110 4110 4110 4110 4110 5110 5110
B (width) [mm] 2220 2220 2220 2220 2220 2220 2220
H (height) [mm] 2150 2150 2150 2150 2150 2150 2150
Weight 2) [kg] 1670 1880 2000 2280 2460 2790 2800
1) Performance data for input parameters: chilled water temperatures (inlet/outlet) 12/7 °C; outside-air temperature 35 °C; values partially rounded off
2) Applies to unit without hydraulic module (pump / buffer tank)
3) For exact refrigerant charge volume, refer to the unit name plate
4) Applies to units without pumps, low-temperature use in average climate (EN14825), data according to ERP guideline for heating units (EU law 813/2013 EU), which does not require
stricter requirements from 2021, certified in Eurovent
5) Based on the entire unit (without pump)
6) Data apply to input parameters as described under 1/7) and without glycol; conversion required when using glycol
7) Performance data for input parameters: warm water temperature (inlet/outlet) 40/45 °C; outdoor air temperature +7 °C, 87% r.h.; values partially rounded off
8) Please observe the regionally applicable safety regulations and constructional conditions relevant to the dimensioning of the supply line.

PR-2020-1029-GB • R1-04/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 11/20
Reversible air-to-water heat pump
FGAH 4060 - 4120 BG2 (.SL/.HE)

Tab. 3: General data for SL units with 4 compressors

Unit type FGAH #### BG2.SL 4060 4070 4080 4090 4100 4110 4120

Capacity data (catalog) 6)


Cooling capacity 1) Qe [kW] 142.1 168.5 193.6 222.7 245.4 269.8 291.2
Power consumption 5) P [kW] 54.0 64.1 73.8 82.4 93.7 103.3 111.6
EER 2.63 2.63 2.62 2.70 2.62 2.61 2.61
Chilled water flow rate Ve [m³/h] 24.5 29.0 33.3 38.3 42.3 46.4 50.1
Pressure drop evaporator ∆pe [kPa] 33.5 35.5 37.8 40.6 39.5 35.8 41.7
Heating performance data (catalog) 6)
Heating capacity 7) Qe [kW] 150.6 181.4 209.8 241.4 265.7 288.9 310.3
Power consumption 5) P [kW] 46.9 58.4 66.5 75.3 83.5 91.9 99.2
COP 3.21 3.11 3.16 3.21 3.18 3.14 3.13
Warm water flow rate Ve [m³/h] 7.27 8.757 10.13 11.65 12.83 13.94 14.98
Pressure drop condenser ∆pc [kPa] 26.2 31.5 36.5 41.9 46.2 50.2 53.9
ERP conformity
SCOP (813/2013 EU) 4) 3.77 3.52 3.8 3.89 3.80 3.70 3.72
ηS (813/2013 EU) 4) [%] 148 138 149 152 149 145 146
Meets ErP requirements       
Cooling performance values according to EN14511-3:2011
Cooling capacity 1) Qe [kW] 141.8 168.1 193.3 222.4 245.1 269.5 290.9
EER 2.6 2.6 2.59 2.67 2.59 2.59 2.58
Heating performance values according to EN14511-3:2011
Heating capacity 7) [kW] 151 181.7 210.2 241.8 266.1 289.2 310.7
COP 3.18 3.07 3.12 3.17 3.14 3.11 3.09
Controls Compact display / controller with TA Software
Fans Axial fans
Number of fans n 4 6 6 6 6 8 8
Total air volume flow [m³/h] 38412 62460 57636 65340 65340 76824 84780
Compressors Scroll compressors
Number of compressors 4 4 4 4 4 4 4
Number of refrigeration circuits 2 2 2 2 2 2 2
Minimum part-load speed [%] 25 25 25 25 25 25 25
Heat exchanger, water side
Min. water flow rate Ve,min [m³/h] 16.3 19.0 21.6 25.1 28.1 30.6 32.8
Max. water flow rate Ve,max [m³/h] 46.1 53.5 60.7 62.0 68.8 68.8 68.8
Max. operating pressure2) pmax [bar] 10 10 10 10 10 10 10
On-site minimum system content [l] 400 465 528 613 685 745 798
Water charge of heat exchanger [l] 8.6 10.5 12.3 15.1 18.9 23 23
Heat exchanger connection 3“ 3“ 3“ 3“ 3“ 4“ 4“
Refrigeration circuit charge
Refrigerant R454B (GWP 466) 3) [kg] 33.8 56.1 74.5 73.9 77.1 97.0 97.0
Oil charge [kg] 10.8 10.8 10.8 16.0 21.2 21.2 21.2
Power supply line 8)
Max. cable cross-section, round [mm²] 20 x 5 20 x 5 20 x 5 20 x 5 2 x 25 x 5 2 x 25 x 5 2 x 25 x 5
Max. cable cross-section, 120 120 120 120 240 240 240
[mm]
rectangle
Dimensions and weight
A (length) [mm] 3110 4110 4110 5110 5110 5110 5110
B (width) [mm] 2220 2220 2220 2220 2220 2220 2220
H (height) [mm] 2150 2150 2150 2150 2150 2150 2150
Weight 2) [kg] 1720 2020 2130 2620 2790 2950 2960
1) Performance data for input parameters: chilled water temperatures (inlet/outlet) 12/7 °C; outside-air temperature 35 °C; values partially rounded off
3) Applies to unit without hydraulic module (pump / buffer tank)
3) For exact refrigerant charge volume, refer to the unit name plate
4) Applies to units without pumps, low-temperature use in average climate (EN14825), data according to ERP guideline for heating units (EU law 813/2013 EU), which does not require
stricter requirements from 2021, certified in Eurovent
5) Based on the entire unit (without pump)
6) Data apply to input parameters as described under 1/7) and without glycol; conversion required when using glycol
7) Performance data for input parameters: warm water temperature (inlet/outlet) 40/45 °C; outdoor air temperature +7 °C, 87% r.h.; some values rounded off
8) Please observe the regionally applicable safety regulations and constructional conditions relevant to the dimensioning of the supply line.

Page 12/20 PR-2020-1029-GB • R1-04/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.
Reversible air-to-water heat pump
FGAH 4060 - 4120 BG2 (.SL/.HE)

Tab. 4: General data for HE units with 4 compressors

Unit type FGAH #### BG2.HE 4060 4070 4080 4090 4100 4110 4120

Capacity data (catalog) 6)


Cooling capacity 1) Qe [kW] 152.3 179.9 207.4 237.9 265.4 288.4 311.7
Power consumption 5) P [kW] 50.0 58.0 65.7 76.4 87.0 93.6 101.4
EER 3.05 3.10 3.16 3.11 3.05 3.08 3.07
Chilled water flow rate Ve [m³/h] 26.2 31.0 35.7 41.0 45.7 49.6 53.7
Pressure drop evaporator ∆pe [kPa] 19.9 27.8 46.1 41.8 28.2 33.3 38.9
Heating performance data (catalog) 6)
Heating capacity 7) Qe [kW] 159.8 195 224.3 258.3 285.7 309 336.8
Power consumption 5) P [kW] 47.2 58.4 66.6 77.1 85.5 92.2 100.6
COP 3.39 3.34 3.37 3.35 3.34 3.35 3.35
Warm water flow rate Ve [m³/h] 27.8 33.9 39.0 44.9 49.6 53.7 58.5
Pressure drop condenser ∆pc [kPa] 22.3 33.3 55 50.2 33.3 38.9 46.2
ERP conformity
SCOP (813/2013 EU) 4) 4.20 4.30 4.37 4.38 4.21 4.25 4.23
ηS (813/2013 EU) 4) [%] 165 169 172 172 165 167 166
Meets ErP requirements       
Cooling performance values according to EN14511-3:2011
Cooling capacity 1) Qe [kW] 152.1 179.5 207 237.6 265.1 288.1 311.3
EER 3.02 3.07 3.11 3.07 3.02 3.05 3.04
Heating performance values according to EN14511-3:2011
Heating capacity 7) [kW] 160 195.3 224.7 258.7 286 309.4 337.2
COP 3.36 3.3 3.32 3.31 3.31 3.32 3.31
Controls Compact display / controller with TA Software
Fans Axial fans
Number of fans n 4 6 6 8 8 8 10
Total air volume flow [m³/h] 61272 78012 86364 104004 104004 113292 129996
Compressors Scroll compressors
Number of compressors 4 4 4 4 4 4 4
Number of refrigeration circuits 2 2 2 2 2 2 2
Minimum part-load speed [%] 25 25 25 25 25 25 25
Heat exchanger, water side
Min. water flow rate Ve,min [m³/h] 15.7 18.3 21.3 24.3 27.2 29.8 32.3
Max. water flow rate Ve,max [m³/h] 47.2 54.9 58.8 68.2 81.4 89.1 92.8
Max. operating pressure2) pmax [bar] 10 10 10 10 10 10 10
On-site minimum system content [l] 410 477 556 633 708 775 838
Water charge of heat exchanger [l] 41.4 41.4 35.8 39.6 86 86 86
Heat exchanger connection 3“ 3“ 3“ 3“ 4“ 4“ 4“
Refrigeration circuit charge
Refrigerant R454B (GWP 466) 3) [kg] 40.5 62.8 81.4 81.5 81.5 104 104
Oil charge [kg] 10.8 10.8 10.8 16.0 21.2 21.2 21.2
Power supply line 8)
Max. cable cross-section, round [mm²] 20 x 5 20 x 5 20 x 5 20 x 5 2 x 25 x 5 2 x 25 x 5 2 x 25 x 5
Max. cable cross-section, 120 120 120 120 240 240 240
[mm]
rectangle
Dimensions and weight
A (length) [mm] 4110 4110 5110 5110 5110 6110 6110
B (width) [mm] 2220 2220 2220 2220 2220 2220 2220
H (height) [mm] 2150 2150 2150 2150 2150 2150 2150
Weight 2) [kg] 2100 2320 2630 2890 3200 3550 3660
1) Performance data for input parameters: chilled water temperatures (inlet/outlet) 12/7 °C; outside-air temperature 35 °C; values partially rounded off
2) Applies to unit without hydraulic module (pump / buffer tank)
3) For exact refrigerant charge volume, refer to the unit name plate
4) Applies to units without pumps, low-temperature use in average climate (EN14825), data according to ERP guideline for heating units (EU law 813/2013 EU), which does not require
stricter requirements from 2021, certified in Eurovent
5) Based on the entire unit (without pump)
6) Data apply to input parameters as described under 1/7) and without glycol; conversion required when using glycol
7) Performance data for input parameters: warm water temperature (inlet/outlet) 40/45 °C; outdoor air temperature +7 °C, 87% r.h.; some values rounded off
8) Please observe the regionally applicable safety regulations and constructional conditions relevant to the dimensioning of the supply line.

PR-2020-1029-GB • R1-04/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 13/20
Reversible air-to-water heat pump
FGAH 4060 - 4120 BG2 (.SL/.HE)

Noise levels
Tab. 5: Noise level

Total sound level Octave band [Hz]

Sound power level [dB]

Sound
Sound power
Unit type FGAH pressure level 63 125 250 500 1000 2000 4000 8000
[dB(A)] 1)
[dB(A)] 10 m 2)

Standard units
4060BG2 92 60 95 94 91 89 88 83 77 72
4070BG2 92 60 95 94 91 89 88 83 77 72
4080BG2 93 61 96 95 92 90 89 84 78 73
4090BG2 94 62 97 96 93 91 90 85 79 74
4100BG2 95 63 98 97 94 92 91 86 80 75
4110BG2 95 63 98 97 94 92 91 86 80 75
4120BG2 95 63 98 97 94 92 91 86 80 75
SL units (super low noise units)
4060BG2.SL 82 50 84 83 82 80 77 72 65 59
4070BG2.SL 83 51 85 84 83 81 78 73 66 60
4080BG2.SL 83 51 85 84 83 81 78 73 66 60
4090BG2.SL 84 52 86 85 84 82 79 74 67 61
4100BG2.SL 85 53 87 86 85 83 80 75 68 62
4110BG2.SL 86 54 88 87 86 84 81 76 69 63
4120BG2.SL 87 55 89 88 87 85 82 77 70 64
HE units (high efficient units)
4060BG2.HE 86 54 88 87 86 84 81 76 69 63
4070BG2.HE 87 55 89 88 87 85 82 77 70 64
4080BG2.HE 88 56 90 89 88 86 83 78 71 65
4090BG2.HE 89 57 91 90 89 87 84 79 72 66
4100BG2.HE 90 58 92 91 90 88 85 80 73 67
4110BG2.HE 90 58 92 91 90 88 85 80 73 67
4120BG2.HE 91 59 93 92 91 89 86 81 74 68
Data on operating conditions
Data applies only to water inlet and discharge temperatures of 12 °C/ 7 C° and outside-air temperatures of 35 °C.
1) Specification of sound power (EUROVENT certified value)
The manufacturer determines the sound power value for Eurovent-certified units in accordance with ISO 9614 standard.
This certification expressly refers to sound power in dB(A), which thus constitutes obligatory data in this case.
2) Specification of sound pressure level
The sound pressure level is determined according to enveloping surface method with a reflecting plane (Q = 2). The distance of
10 m refers to the external dimensions of the unit. For sound pressure level the following corrections can be used:
Sound pressure level at 5 m: +5 dB as compared to sound pressure level at 10 meters distance
Sound pressure level at 15 m: -3 dB as compared to sound pressure level at 10 meters distance
Sound pressure level at 20 m: -6 dB as compared to sound pressure level at 10 meters distance
Only an externally engaged acoustics engineer should carry out specific sound level calculations to be valid for your installation site.

Page 14/20 PR-2020-1029-GB • R1-04/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.
Reversible air-to-water heat pump
FGAH 4060 - 4120 BG2 (.SL/.HE)

Footprint
R4 CLEARANCE FOR AIR SUPPLY!
Unit must be able to freely discharge air upwards. Air short-circuiting must be
impossible! The necessary clearances near and over the unit may exceed the
depicted maintenance clearance by many times.
Tab. 6: Clearances
R3 Unit sizes R1 R2 R3 R4

4060-4120 [mm] 2000 2000 1100 2000

Fig. 9: Required clearances (example)

Anti-vibration mounts
Tab. 7: Required anti-vibration mounts according to the unit model

Spring vibration damper (Option .I01) Rubber anti-vibration isolators (option .I02)

FläktGroup individual part designation FläktGroup individual part designation


Unit type FGAH…
Units with pump(s) Units with
Units without Units with pump(s) Units without Units with
and with buffer pump(s) and
pump(s) and without buffer pump(s) pump(s) and with
tank without buffer
tank buffer tank
tank
Standard units
4060BG2 6x SR21-550H 6x SR21-550H 6x SR21-550H 6 x FZ-200-57 6 x FZ-200-57 6 x FZ-400-51
4070BG2 8x SR21-550H 8x SR21-550H 8x SR21-550H 8 x FZ-200-57 8 x FZ-200-57 8 x FZ-400-51
4080BG2 8x SR21-550H 8x SR21-550H 8x SR21-550H 8 x FZ-200-57 8 x FZ-200-57 8 x FZ-400-51
4090BG2 8x SR21-550H 8x SR21-550H 8x SR21-550H 8 x FZ-200-57 8 x FZ-200-57 8 x FZ-400-51
4100BG2 8x SR21-550H 8x SR21-550H 8x SR21-550H 8 x FZ-400-51 8 x FZ-400-51 8 x FZ-400-51
2x SR21-800 2x SR21-800
4110BG2 8x SR21-800 8 x FZ-400-51 8 x FZ-400-51 8 x FZ-400-51
+ 6x SR21-550H + 6x SR21-550H
2x SR21-800 2x SR21-800
4120BG2 8x SR21-800 8 x FZ-400-51 8 x FZ-400-51 8 x FZ-400-51
+ 6x SR21-550H + 6x SR21-550H
SL units (super low noise units)
4060BG2.SL 6x SR21-550H 6x SR21-550H 6x SR21-550H 6 x FZ-200-57 6 x FZ-200-57 6 x FZ-400-51
4070BG2.SL 8x SR21-550H 8x SR21-550H 8x SR21-550H 8 x FZ-200-57 8 x FZ-200-57 8 x FZ-400-51
4080BG2.SL 8x SR21-550H 8x SR21-550H 8x SR21-550H 8 x FZ-200-57 8 x FZ-200-57 8 x FZ-400-51
2x SR21-800 2x SR21-800
4090BG2.SL 8x SR21-800 8 x FZ-400-51 8 x FZ-400-51 8 x FZ-400-51
+ 6x SR21-550H + 6x SR21-550H
2x SR21-800 2x SR21-800
4100BG2.SL 8x SR21-800 8 x FZ-400-51 8 x FZ-400-51 8 x FZ-400-51
+ 6x SR21-550H + 6x SR21-550H
2x SR21-800 2x SR21-800
4110BG2.SL 8x SR21-800 8 x FZ-400-51 8 x FZ-400-51 8 x FZ-400-51
+ 6x SR21-550H + 6x SR21-550H
2x SR21-800 2x SR21-800
4120BG2.SL 8x SR21-800 8 x FZ-400-51 8 x FZ-400-51 8 x FZ-400-51
+ 6x SR21-550H + 6x SR21-550H
HE units (high efficient units)
2x SR21-800
4060BG2.HE 8x SR21-550H 8x SR21-550H 8 x FZ-200-57 8 x FZ-200-57 8 x FZ-400-51
+ 6x SR21-550H
2x SR21-800
4070BG2.HE 8x SR21-550H 8x SR21-550H 8 x FZ-200-57 8 x FZ-200-57 8 x FZ-400-51
+ 6x SR21-550H
2x SR21-800
4080BG2.HE 8x SR21-550H 8x SR21-800 8 x FZ-400-51 8 x FZ-400-51 8 x FZ-400-51
+ 6x SR21-550H
2x SR21-800
4090BG2.HE 8x SR21-550H 8x SR21-800 8 x FZ-400-51 8 x FZ-400-51 8 x FZ-400-51
+ 6x SR21-550H
2x SR21-800
4100BG2.HE 8x SR21-550H 8x SR21-800 8 x FZ-400-51 8 x FZ-400-51 8 x FZ-400-51
+ 6x SR21-550H
2x SR21-800
4110BG2.HE 8x SR21-800 8x SR21-800 8 x FZ-400-51 8 x FZ-400-51 8 x FZ-400-51
+ 6x SR21-550H
2x SR21-800
4120BG2.HE 8x SR21-800 8x SR21-800 8 x FZ-400-51 8 x FZ-400-51 8 x FZ-400-51
+ 6x SR21-550H

NOTICE!
If the units are operated without the appropriate anti-vibration mounts, the warranty is void!

PR-2020-1029-GB • R1-04/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 15/20
Reversible air-to-water heat pump
FGAH 4060 - 4120 BG2 (.SL/.HE)

Electrical data
Tab. 8: Electrical data

Unit Type Compressor(s) Fans3) Total 1) 2) 3)

Voltage

Softstart
L.R.A.
F.L.A.

F.L.A.
supply

F.L.A
F.L.I.

F.L.I.

F.L.I.

arter
[kW]

[kW]

[kW]

with
FGAH…

S.A.

S.A.
n

[A]

[A]

[A]

[A]
Standard units
4060BG2 400/3/50 4 4x15.36 4x24.9 4x172 8 16 77 133 301 194
4070BG2 400/3/50 4 2x15.36+2x21.4 2x24.9+2x34.2 2x172+2x211 8 16 90 157 332 227
4080BG2 400/3/50 4 4x21.4 4x34.2 4x211 8 16 103 176 351 246
4090BG2 400/3/50 4 2x21.4+2x27 2x34.2+2x42.5 2x211+2x210 12 24 120 207 415 261
4100BG2 400/3/50 4 4x27 4x42.5 4x210 12 24 132 229 438 278
4110BG2 400/3/50 4 2x27+2x34.5 2x42.5+2x55.1 2x210+2x326 12 24 143 243 505 360
4120BG2 400/3/50 4 4x34.5 4x55.1 4x326 12 24 153 256 518 385
4060BG2+.E81 400/3/50 4 4x15.36 4x24.9 4x172 6.8 12 68.2 110 258 190
4070BG2+.E81 400/3/50 4 2x15.36+2x21.4 2x24.9+2x34.2 2x172+2x211 6.8 12 80.3 129 306 223
4080BG2+.E81 400/3/50 4 4x21.4 4x34.2 4x211 6.8 12 92.4 148 324 242
4090BG2+.E81 400/3/50 4 2x21.4+2x27 2x34.2+2x42.5 2x211+2x210 10.2 18 107 170 338 255
4100BG2+.E81 400/3/50 4 4x27 4x42.5 4x210 10.2 18 118.2 186 354 272
4110BG2+.E81 400/3/50 4 2x27+2x34.5 2x42.5+2x55.1 2x210+2x326 10.2 18 133.2 211 482 354
4120BG2+.E81 400/3/50 4 4x34.5 4x55.1 4x326 10.2 18 148.2 237 508 379
SL units (super low noise units)
4060BG2.SL 400/3/50 4 4x15.36 4x24.9 4x172 4.8 16 74 133 301 194
4070BG2.SL 400/3/50 4 2x15.36+2x21.4 2x24.9+2x34.2 2x172+2x211 7.2 24 89 165 340 235
4080BG2.SL 400/3/50 4 4x21.4 4x34.2 4x211 7.2 24 102 184 359 254
4090BG2.SL 400/3/50 4 2x21.4+2x27 2x34.2+2x42.5 2x211+2x210 7.2 24 115 207 415 261
4100BG2.SL 400/3/50 4 4x27 4x42.5 4x210 7.2 24 127 229 438 278
4110BG2.SL 400/3/50 4 2x27+2x34.5 2x42.5+2x55.1 2x210+2x326 9.6 32 140 251 513 368
4120BG2.SL 400/3/50 4 4x34.5 4x55.1 4x326 9.6 32 151 264 527 393
4060BG2.SL+.E82 400/3/50 4 4x15.36 4x24.9 4x172 6.8 12 68.2 110 258 190
4070BG2.SL+.E82 400/3/50 4 2x15.36+2x21.4 2x24.9+2x34.2 2x172+2x211 10.2 18 83.7 134 311 229
4080BG2.SL+.E82 400/3/50 4 4x21.4 4x34.2 4x211 10.2 18 95.8 153 330 248
4090BG2.SL+.E82 400/3/50 4 2x21.4+2x27 2x34.2+2x42.5 2x211+2x210 10.2 18 107 170 338 255
4100BG2.SL+.E82 400/3/50 4 4x27 4x42.5 4x210 10.2 18 118.2 186 354 272
4110BG2.SL+.E82 400/3/50 4 2x27+2x34.5 2x42.5+2x55.1 2x210+2x326 13.6 24 136.6 217 488 360
4120BG2.SL+.E82 400/3/50 4 4x34.5 4x55.1 4x326 13.6 24 151.6 242 513 385
HE units (high efficient units)
4060BG2.HE 400/3/50 4 4x15.36 4x24.9 4x172 6.8 12 68.2 110 258 190
4070BG2.HE 400/3/50 4 2x15.36+2x21.4 2x24.9+2x34.2 2x172+2x211 10.2 18 83.7 134 311 229
4080BG2.HE 400/3/50 4 4x21.4 4x34.2 4x211 10.2 18 95.8 153 330 248
4090BG2.HE 400/3/50 4 2x21.4+2x27 2x34.2+2x42.5 2x211+2x210 13.6 24 110.4 175 344 261
4100BG2.HE 400/3/50 4 4x27 4x42.5 4x210 13.6 24 121.6 192 359 278
4110BG2.HE 400/3/50 4 2x27+2x34.5 2x42.5+2x55.1 2x210+2x326 13.6 24 136.6 217 488 360
4120BG2.HE 400/3/50 4 4x34.5 4x55.1 4x326 17.0 30 155 247 518 391

All values refer to units without built-in pumps. For units with built-in pumps, the pump data must be added.
n Number of compressors
F.L.I. El. Power consumption
F.L.A. Operating current
L.R.A. Starting current of each compressor
S.A. Starting current of entire unit

1) Please observe the regionally applicable safety regulations and constructional conditions relevant to the dimensioning of the supply line.
2) Please observe the regionally applicable standards for cable cross-sections and backup fuses. Voltage tolerance: max. 10%, voltage imbalance between
phases: max. 3%.
3) Values are based on the total number of fans operating at maximum speed.

Page 16/20 PR-2020-1029-GB • R1-04/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.
Reversible air-to-water heat pump
FGAH 4060 - 4120 BG2 (.SL/.HE)

Terminal scheme
Setpoint shift On-site inverter pumps Activation
Demand limit*
4-20 mA signal 0-10 V signal 2nd setpoint*
2) (option .E23)
Put on Put on (option .E21) Put on (option .E30/.E31) (option .E22)
shielding shielding shielding

Y + -
G
0V

07 08 GND 200/202 201/203 GND R S R M


GND + -
Serial card RS485/Modbus, LonWorks FGAC 4061-4121 BG2 (.D/.SL/.SD/ .HE/ .HD)
or BACnet as option, .E14 - .E17
Four times:
Compressor 2: FC2-FC2
G FC1 FC1 Compressor 3: FC3-FC3 FP1 FP1 FP2 FP2
E F A B H AA AA
Compressor 4: FC4-FC4
J1

Contact Flow Seasonal Common alarm Operation message compressor 1-4 Relay for Relay for 2nd
1)
switch* switch over signal # # on-site on-site
Remote On/Off*
summer / max. 2 A~/50 Hz (option .E03) chilled-water chilled-water
3)
winter * 2) Pump # Pump #
3)

Cabling on-site provided by others (Option E.04/E.34) (option .E34)


# on-site potential necessary (max. 230 V / 50 Hz / 2 A)
* potential may not be supplied on-site (potential supplied by controller)
1) Remove jumper J1 if remote contact is used. For connecting, for example, a timer or outdoor temperature switch (with hysteresis) to
enable the unit. Switching over the water temperature (e.g., in the buffer tank) is not permitted (caution: not covered by the warranty,
possible damage to the unit!)
2) Seasonal switch over between summer operation (cooling) and winter operation (heating); for example use the heating operation from
mid-September to mid-May and the cooling operation during the rest of the time depending on the local climatic conditions. Contact open =
heating; contact closed = cooling; to switch from heating operation to cooling operation or vice versa, the Remote On/Off contact E-F must
first be opened. The operating mode of the unit must then be changed by opening or closing the G-H contact. Then, the remote contact for
switching the unit on and off can be closed again and the machine will commence operation. Please consider the operating limits of the
unit. Changing over e.g. from heating to cooling operation at increased water temperatures can lead to faults and disruptions. If necessary,
use a sufficiently long neutral phase between the heating and cooling seasons during which the unit is deactivated via remote on/off.
3) With two parallel inverter pumps (redundancy) provided by the customer, use the 0-10 V signal equally as control signal for both pumps.
Additionally, apply the enable signals of the corresponding terminals to the pumps. The pumps are switched over via the enable signals.
If available, connect the pumps’ fault contacts to terminals 041-042 for pump 1 and terminals 043-044 for pump 2. Remove the jumper.
4) Notice: If the setpoint shift is not required or not connected, parameter REG0047 must be set to 0 in the service menu of the controller,
otherwise an error will be displayed.

Fig. 10: Terminal scheme

Order-related documentation

NOTICE!
For detailed planning, please only use the order-related documentation. Detailed dimensional drawings can be
obtained on request from your responsible FläktGroup sales office. Specifications and technical data are subject to
regular updates. The manufacturer reserves the right to make necessary changes to information without prior
written notice.

PR-2020-1029-GB • R1-04/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 17/20
Reversible air-to-water heat pump
FGAH 4060 - 4120 BG2 (.SL/.HE)

___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________

Page 18/20 PR-2020-1029-GB • R1-04/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.
Reversible air-to-water heat pump
FGAH 4060 - 4120 BG2 (.SL/.HE)

___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________

PR-2020-1029-GB • R1-04/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice. Page 19/20
Reversible air-to-water heat pump
FGAH 4060 - 4120 BG2 (.SL/.HE)

Page 20/20 PR-2020-1029-GB • R1-04/2021 • FläktGroup is not liable for printing errors and reserves the right to change content without notice.