TECHNICAL NOTE 01/2007

Telnet and HyperTerminal Access


This document describes how to access certain PowerLogic® meter settings with 
Microsoft Telnet or Windows HyperTerminal applications: 
If your meter is connected to an Ethernet network, use a telnet application such 
as Microsoft Telnet. 
If your meter is connected serially or through a modem to your workstation, use 
a terminal application such as Windows HyperTerminal. 

In This Document

Using Telnet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Meter Logins  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  3
Telnet Menu   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  4

Using HyperTerminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Terminal Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8

Additional Information
Your meter’s technical documentation
ION Reference

Electrical equipment should be


installed, operated, serviced, and
maintained only by qualified
personnel. No responsibility is
assumed by Schneider Electric for
any consequences arising out of
the use of this material.
© 2007 Schneider Electric.
All rights reserved.
www.powerlogic.com
Using Telnet Telnet and HyperTerminal Access

Using Telnet
If your meter is connected to an Ethernet network, use Telnet to perform various 
functions:
access certain Ethernet communications module settings
view Ethernet statistics
access certain Power Meter module settings
access certain Factory module settings
clear the front panel event log display (ION8600 meters)
configure Factory module setup registers for Current Probe Input applications 
(ION7550 / ION7650 meters).

NOTE
Remote access is limited on ION7300 series meters when connected via Ethernet. For full access to
commands, connect serially and use HyperTerminal.

Connecting to the meter


1. From the Windows Start menu on the lower left side of your computer screen, 
choose Run... and type the word telnet. Click OK.

2. Type Open and press Return.
3. Type in the meter IP address when prompted and press Enter.

NOTE
The IP address must match the IP address setup register in the meter Ethernet communications module.

Page 2 © 2007 Schneider Electric. All rights reserved.


Telnet and HyperTerminal Access Using Telnet

4. Type your meter’s login and press Enter. See below for details.

Meter Logins
The login is different for each meter.

Meter Login

ION7300 7300

ION7330 7300

ION7350 7300

ION7500 7500

ION7600 7500

ION7550 7550

ION7650 7650

ION7700 Xpress

ION8300 8300

ION8400 8400

ION 8500 8500

ION8600* 8600

* Login ID is the same for ION8600A, ION8600B and ION8600C meters.

5. Type the meter password (“0” by default). Press Enter. 

NOTE
If ten incorrect passwords are entered in succession the Telnet access locks-out for 24 hours or until the
security features are disabled with the front panel of the meter.

6. Type “?” for meter Help screen and press Enter. A list of menu options appears.

© 2007 Schneider Electric. All rights reserved. Page 3


Telnet Menu Telnet and HyperTerminal Access

Telnet Menu
The menu options available will vary by meter type. Shown below are the Telnet 
menu options for two meters, the ION8600 and the ION7300.

ION7300 ION8600

This option is available


for ION8600 meters
only.

On ION8600 meters, the available Telnet menu options are:

0) Logout

1) Ethernet Settings

2) Ethernet Stats

3) Meter Clear Functions*

4) Factory Login

Switch to Debug Parser (and


9)
route msgs to telnet)

?) Displays this menu

Logout – select this option to logout of the meter, and end the Telnet session.

Ethernet Settings – there are two options in this menu: one for viewing your 
current communications settings and one for configuring your IP Boot option, IP 
address, Subnet mask, Gateway address and SMTP address.

Ethernet Stats – there are three options available in this menu: one for viewing 
various Ethernet statistics, one for viewing an Ethernet collision histogram, and a 
third option for resetting these statistics.

Meter Clear Functions – there are two options available in this menu: one returns 
you to the Main Menu, and one clears the meter Event Log Display (ION8000 
series meters).

Page 4 © 2007 Schneider Electric. All rights reserved.


Telnet and HyperTerminal Access Telnet Menu

Switch to Debug Parser (and route msgs to telnet) – there are eight screens with 
options available in this menu:

? Display Help Screen

ALL? Display All Commands

COMM? Display Comm Help

MISC? Display Miscellaneous Help

RESET? Display Reset Help

SEC? Display Security Help

TIME? Display Time Help

KAL? Display Calibration Help

Factory Login
LOGIN (this menu is reserved for
Technical Services’ use)

LOGOUT Logout

Accessing menus
1. View the list of menus at any time by typing a question mark (?) and pressing 
Enter. 
2. To access a menu, press the corresponding number on your keyboard, then press 
Enter.

© 2007 Schneider Electric. All rights reserved. Page 5


Using HyperTerminal Telnet and HyperTerminal Access

Using HyperTerminal
If your meter is connected to your workstation via a serial or modem port, use 
Windows HyperTerminal to access certain meter module settings. 

NOTE
Ensure that the meter COM port you are using has its Protocol register set to “Factory.”

A HyperTerminal session lets you:
access certain Factory module settings.
access certain Power Meter module settings.
clear the front panel event log display (ION8000 series meters).
configure Factory module setup registers for Current Probe Input applications 
(ION7500 / ION7600 meters).

Connecting to the meter using Hyperterminal


1. If you have not already done so, set the COM port you are using on the meter 
to “Factory”.
2. Launch HyperTerminal from the Start > Programs > Accessories > Communications > 
HyperTerminal menu.

3. A window requesting a modem install appears. If you wish to install a modem, 
click Yes and follow the steps. If you do not need to install a modem, click No. 
The Connection Description window appears.
Type in the name for this HyperTerminal session in the Name box. Press Enter. 
The Connect To window appears.
 

4. In the Connect Using box, select your PC COM port (e.g. COM1). Press Enter. 
The COM1 Properties window appears.
5. In the Bits Per Second box, select 9600. 
6. In the Flow Control box, select None. 

Page 6 © 2007 Schneider Electric. All rights reserved.


Telnet and HyperTerminal Access Using HyperTerminal

7. For the other settings, use the defaults. The COM Properties window should 
resemble the window below.
 

8. Press Enter. A HyperTerminal session window appears.
9. Press Enter. A response indicating an “invalid command” appears. Below this 
there is a prompt that indicates the meter type and the PC port where the meter 
is connected.

10. Type “?” and press Enter for the Terminal menu.

© 2007 Schneider Electric. All rights reserved. Page 7


Terminal Menu Telnet and HyperTerminal Access

As you toggle between the different Terminal Commands menu options you are 
required to enter:
Login ‐ see “Meter Logins” on page 3.
Password ‐ type the meter password (default is “0”).

Terminal Menu
The Terminal Commands menu options are:

? Display Help Screen

ALL? Display All Commands

COMM? Display Comm Help Screen

MISC? Display Misc Help Commands

RESET Display Reset Help Commands

SEC? Display Security Help Screen

TIME? Display Time Help Screen

KAL? Display Calibration Help Screen

LOGIN Factory login

LOGOUT Logout

Display Help Screen – select this option to display the Factory Terminal menu 
(menu displayed above).

Display All Commands – select this option to display every Terminal Command 
that can be used in HyperTerminal.

Page 8 © 2007 Schneider Electric. All rights reserved.


Telnet and HyperTerminal Access Terminal Menu

Display Comm Help Screen – this option is not used if your meter is connected 
serially to your workstation. 

Display Misc Help Screen – this option lists commands that allow you to repeat 
the last command, and display the battery statistics, meter release version, and 
meter firmware version.   

Display Reset Help Screen – if your security level allows you to perform resets 
then this screen lists the following options: full or partial factory initialization; 
restore the factory framework; read power‐up style; and reset fatal error.   

Display Security Help Screen – select this option to enable/disable password or 
hardware security, or read the meter lock state. 

Display Time Help Screen – select this option to set or display the meter time, and 
human meter time:
meter time: Unix time (seconds since January 1, 1970)
human meter time: day/month/year and hour:minute:second

Display Calibration Help Screen – select this option to display or configure meter 
calibration parameters. 

Factory Login – this menu is reserved for Technical Support use. 

Logout – select this option to logout of the meter, and end the HyperTerminal 
session.