Earthing Conductors Size Calculation
Earthing Conductors Size Calculation
If S ≤ 16 then the Minimum cross-sectional area of the corresponding earth conductor = S mm2
If 16 < S ≤ 35 then the Minimum cross-sectional area of the corresponding earth conductor = 16 mm2
if S > 16 , then the Minimum cross-sectional area of the corresponding earth conductor = S/2 mm2
Zs < 50/Ia where Zs = Earth loop impedance and Ia is protective device operating current